INVT BPD Series Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT BPD Series IP65 solar water pump inverter. Search or filter through the complete fault code directory below.
Power Range
0.75 – 5.5 kW (1 – 7.5 HP)
Input Voltage
PV DC (up to 800V) / 220–380V AC
Control Modes
Dynamic MPPT & V/F Control
Enclosure Rating
IP65 Outdoor (Fanless Design)
Complete INVT BPD Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type AL-S, At-F, or OC1).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OV1 Overvoltage when acceleration | Cause: 1. The input voltage is abnormal. 2. There is large energy feedback. 3. No brake components. 4. Braking energy is not open. 5. The overvoltage stall protection is not open. Remedy:
|
| OV2 Overvoltage when deceleration | Cause: 1. The input voltage is abnormal. 2. Large energy feedback during deceleration. 3. No brake components. 4. The overvoltage stall protection is not open. Remedy:
|
| OV3 Overvoltage when constant speed running | Cause: 1. The input voltage is abnormal. 2. Large energy feedback. 3. The overvoltage stall protection is not open. Remedy:
|
| OC1 Overcurrent when acceleration | Cause: 1. The acceleration is too fast. 2. The voltage of the grid is too low. 3. The power of the inverter is too low. 4. The load transients or is abnormal. 5. The grounding is short circuited or output phase loss. 6. Strong external interference. Remedy:
|
| OC2 Overcurrent when deceleration | Cause: 1. The deceleration is too fast. 2. The voltage of the grid is too low. 3. The power of the inverter is too low. 4. The load transients or is abnormal. 5. Grounding short circuit or output phase loss. 6. Strong external interference. Remedy:
|
| OC3 Overcurrent when constant speed running | Cause: 1. The voltage of the grid is too low. 2. The power of the inverter is too low. 3. The load transients or is abnormal. 4. Grounding short circuit or output phase loss. 5. Strong external interference. Remedy:
|
| UV Bus undervoltage | Cause: 1. The voltage of the power supply is too low. 2. The overvoltage stall protection is not open. Remedy:
|
| OL1 Motor overload | Cause: 1. The voltage of the power supply is too low. 2. The motor setting rated current is incorrect. 3. The motor stall or load transients is too strong. Remedy:
|
| OL2 Inverter overload | Cause: 1. The acceleration is too fast. 2. The rotating motor is reset. 3. The voltage of the power supply is too low. 4. The load is too heavy. 5. The motor power is too small. Remedy:
|
| SPI Input phase loss | Cause: Phase loss or fluctuation of input R,S,T. Remedy:
|
| SPO Output phase loss | Cause: U,V,W phase loss output (or serious asymmetrical three phase of the load). Remedy:
|
| OH1 Rectifier module overheat | Cause: 1. Air duct jam or fan damage. 2. Ambient temperature is too high. 3. The time of overload running is too long. Remedy:
|
| OH2 Inverter module overheat | Cause: 1. Air duct jam or fan damage. 2. Ambient temperature is too high. 3. The time of overload running is too long. Remedy:
|
| EF External fault | Cause: SI external fault caused by actions of input terminals. Remedy:
|
| CE 485 Communication error | Cause: 1. The baud rate setting is incorrect. 2. Fault occurs to the communication wiring. 3. The communication address is wrong. 4. There is strong interference to the communication. Remedy:
|
| ItE Current detection fault | Cause: 1. The control panel connector is in poor contact. 2. The Hall component is damaged. 3. The magnifying circuit is abnormal. Remedy:
|
| EEP EEPROM fault | Cause: 1. Error occurs in writing or reading control parameters. 2. EEPROM is damaged. Remedy:
|
| PIDE PID feedback fault | Cause: 1. PID feedback is offline. 2. The PID feedback source disappears. Remedy:
|
| END Running time reached | Cause: The actual running time of the inverter is longer than the preset running time. Remedy:
|
| OL3 Electrical overload | Cause: The inverter will report overload pre-alarm according to the set value. Remedy:
|
| dEu Velocity deviation fault | Cause: The load is too heavy or stalled. Remedy:
|
| STo Maladjustment fault | Cause: 1. The control parameters of the synchronous motors not set properly. 2. The autotuning parameter is not correct. 3. The inverter is not connected to the motor. Remedy:
|
| LL Electronic underload fault | Cause: The inverter will report the underload pre-alarm according to the set value. Remedy:
|
| tSF Hydraulic probe damage | Cause: The hydraulic probe is damaged. Remedy:
|
| PINV PV reverse connection fault | Cause: The solar wiring is not properly performed. Remedy:
|
| PVOC PV overcurrent | Cause: 1. The ACC/DEC is too fast. 2. The inverter power is too low. 3. The load suddenly changes or is abnormal. 4. The grounding is short circuited. Remedy:
|
| PVOV PV overvoltage | Cause: The solar panel input voltage is too high or the model is 380V but set to 220V. Remedy:
|
| PVLV PV undervoltage | Cause: 1. The power of the serially connected solar panels is too low, or it is rainy and cloudy. 2. The starting current of the motor is too high. Remedy:
|
| A-LS Weak light alarm | Cause: The sunlight is weak or too few solar panels are configured. Remedy:
|
| A-LL Underload alarm | Cause: The water pumping tank is empty. Remedy:
|
| A-tF Water full alarm | Cause: The water storing tank is full. Remedy:
|
| A-tL Water empty alarm | Cause: The water pumping tank is empty. Remedy:
|
How to Clear & Reset INVT BPD Series Drive Faults
- Keypad Reset: Press the red STOP/RST button on the external keypad interface when a fault occurs and the red FAULT LED is illuminated.
- Automatic Solar Alarm Recovery: Solar operational status warnings such as AL-S (weak sunlight hibernation), At-F (water tank full), and At-L (low water level / well empty) are auto-clearing and will restart pump operation automatically once sunlight or water level conditions normalize.
- Digital Input Reset (DI): If configured on multi-function terminals S1 to S4 for function 4 (Fault reset) in parameter group P05, momentarily pulse the terminal to reset the latching drive alarm.
- Fault Parameter Inspection: Review parameter group P07 and monitoring group P17 / P18 (such as P18.01 for current PV DC string voltage) to evaluate pump operating conditions and identify root causes prior to resetting.
- Complete Isolation Power Cycle: Switch off the DC photovoltaic isolator switch and disconnect any AC mains grid backup input. Wait until the status LEDs turn completely off (minimum 5 minutes) before re-energizing the inverter.
⚠️ High-Voltage Solar DC & AC Safety Warning:
Photovoltaic arrays generate lethal DC voltages whenever exposed to light. Always isolate the external DC circuit breaker and AC bypass disconnect switches, and wait at least 5 minutes before opening the IP65 enclosure. Confirm with a calibrated DC voltmeter that voltage across PV+ and PV- (or DC bus + and -) is safely below 36VDC before servicing terminals U, V, and W.