INVT GD10 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive10 (GD10) compact mini drive series. Search or filter through the complete fault code directory below.

Compact Mini Economical VFD Power: 0.2 to 2.2 kW (0.25 to 3.0 HP) Space Vector PWM (SVPWM) Control
Power Range 0.2 – 2.2 kW (0.25 – 3.0 HP)
Supply Voltage 1PH/3PH 220V & 3PH 380–440V AC
Control Modes SVPWM (Space Vector V/F)
Operator Interface Integrated LED Keypad + Potentiometer

Complete INVT GD10 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, OV3, or Overcurrent).

Fault CodesCause & Solution
OC1
Overcurrent
during
acceleration
Cause:

- The acceleration or deceleration is too fast;
- The voltage of the grid is too low;
- The power of the VFD is too low;
- The load transients or is abnormal;
- The grounding is short circuited or the output is phase loss;
- There is strong external interference;
- The overvoltage stall protection is not open.

Solution:

- Increase the ACC time;
- Check the input power;
- Select the VFD with a larger power;
- Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth;
- Check the output configuration;
- Check if there is strong interference;
- Check the setting of related function codes
OC2
Overcurrent
during
deceleration
Cause:

- The acceleration or deceleration is too fast;
- The voltage of the grid is too low;
- The power of the VFD is too low;
- The load transients or is abnormal;
- The grounding is short circuited or the output is phase loss;
- There is strong external interference;
- The overvoltage stall protection is not open.

Solution:

- Increase the ACC time;
- Check the input power;
- Select the VFD with a larger power;
- Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth;
- Check the output configuration;
- Check if there is strong interference;
- Check the setting of related function codes
OC3
Overcurrent
at constant
speed
Cause:

- The acceleration or deceleration is too fast;
- The voltage of the grid is too low;
- The power of the VFD is too low;
- The load transients or is abnormal;
- The grounding is short circuited or the output is phase loss;
- There is strong external interference;
- The overvoltage stall protection is not open.

Solution:

- Increase the ACC time;
- Check the input power;
- Select the VFD with a larger power;
- Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth;
- Check the output configuration;
- Check if there is strong interference;
- Check the setting of related function codes
OV1/OU1
Overvoltage
during
acceleration
Cause:

- The input voltage is abnormal;
- There is large energy feedback;
- No braking components;
- Braking energy is not open.

Solution:

- Check the input power;
- Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components;
- Install the braking components;
- Check the setting of related function codes.
OV2/OU2
Overvoltage
during
deceleration
Cause:

- The input voltage is abnormal;
- There is large energy feedback;
- No braking components;
- Braking energy is not open.

Solution:

- Check the input power;
- Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components;
- Install the braking components;
- Check the setting of related function codes.
OV3/OU3
Overvoltage
at constant
speed
Cause:

- The input voltage is abnormal;
- There is large energy feedback;
- No braking components;
- Braking energy is not open.

Solution:

- Check the input power;
- Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components;
- Install the braking components;
- Check the setting of related function codes.
UV
Bus
undervoltage
Cause & Solution:

1. An instantaneous power failure occurs.
- Reset the fault

2. The AC drive's input voltage is not within the permissible range.
- Adjust the voltage to normal range.

3. The bus voltage is abnormal.
- Replace the AC drive.

4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal.
- Replace the AC drive.
OL1
Motor
overload
Cause:

- The voltage of the power supply is too low;
- The motor setting rated current is incorrect;
- The motor stall or load transients is too strong.

Solution:

- Check the power of the supply line;
- Reset the rated current of the motor;
- Check the load and adjust the torque lift.
OL2
VFD
overload
Cause:

- The acceleration is too fast;
- Reset the rotating motor;
- The voltage of the power supply is too low;
- The load is too heavy;
- The motor power is too large, and the power of the VFD is too small.

Solution:

- Increase the ACC time;
- Avoid the restarting after stopping;
- Check the power of the supply line;
- Select a VFD with bigger power;
- Select a proper motor.
OH1
Rectifier
module
overheat
Cause & Solution:

1. The ambient temperature is too high.
- Lower the ambient temperature.

2. The ventilation is clogged.
- Clean the ventilation.

3. The fan is damaged.
- Replace the cooling fan.
OH2
Inverter
module
overheat
Cause & Solution:

1. The ambient temperature is too high.
- Lower the ambient temperature.

2. The ventilation is clogged.
- Clean the ventilation.

3. The fan is damaged.
- Replace the cooling fan.
EF
External
Fault
Cause: SI external fault input terminals action. External fault comes when the drive has detected an issue with an external control circuit or device connected to it. This means the drive has detected an issue with an external device or control circuit connected to it. Unlike error codes specific to internal drive components, the EF code is more general and can be triggered by various external factors.

Solution:

1. An alarm function of the external equipment was activated.
- Inspect external equipment operation.
- Remove the cause of the alarm that occurred.

2. Connection has been performed incorrectly.
- Check if the wire for the external alarm signal is correctly connected to the terminal to which the "Alarm from external equipment" has been assigned.
- Connect the wire for the alarm signal correctly.

3. Incorrect settings.
- Check if the "Alarm from external equipment" has not been assigned to an unassigned terminal.
- Correct the assignment.
CE
RS485
communication
Fault
Cause:

- The baud rate setting is incorrect;
- Fault occurs to the communication wiring;
- The communication address is wrong;
- There is strong interference to the communication.

Solution:

- Set proper baud rate;
- Check the communication connection distribution;
- Set proper communication address;
- Chang or replace the connection distribution or improve the anti-interference capability.
EEP
EEPROM
operation
fault
Cause:

- Error of controlling the write and read of the parameters;
- Damage to EEPROM.

Solution:

- Press STOP/RST to reset;
- Change the main control panel.
PIDE
PID
feedback
offline
fault
Cause:

- PID feedback offline;
- PID feedback source disappear.

Solution:

- Check the PID feedback signal;
- Check the PID feedback source.
END
Running
time
reached
Cause: The actual running time of the VFD is above the internal setting running time.

Solution: Ask for the supplier and adjust the setting running time.
OL3
Electrical
overload
Cause: The VFD will report overload pre-alarm according to the set value.

Solution: Check the load and the overload pre-alarm threshold.
LL
Electronic
underload
fault
Cause: The VFD will report the underload pre-alarm according to the set value.

Solution:

1. Check the load and the underload pre-alarm point.
PoFF
System
power off
Cause: System power off or low DC voltage.

Solution: Check the grid.

How to Clear & Reset INVT GD10 Drive Faults

  1. Keypad Reset: Press the red STOP/RST button on the integrated keypad. Ensure any active run command via terminals or communication is removed before resetting.
  2. Digital Input Reset (DI): If any digital multi-function input terminal (S1–S5) is configured for function 4 (Fault reset) in parameter group P05.01 to P05.05, toggle the terminal to clear the trip condition.
  3. Automatic Fault Reset: Enable automated clearing attempts by configuring parameter P08.28 (Fault reset times) between 1 and 10, and parameter P08.29 (Interval time of automatic fault reset) for desired reset delay intervals.
  4. Modbus RTU Reset: Send the fault reset bit via serial RS485 communication into the drive control word register using standard Modbus RTU protocol (P14 group parameters).
  5. Power Cycle: Disconnect incoming mains supply power completely. Wait until the keypad LED screen turns dark and the internal DC bus capacitors discharge fully (approx. 5 minutes), then reapply AC power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [(+)] and [(-)] before inspecting wiring, servicing the drive, or touching motor terminals U, V, and W on the INVT GD10 drive.