INVT GD10 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive10 (GD10) compact mini drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 2.2 kW (0.25 – 3.0 HP)
Supply Voltage
1PH/3PH 220V & 3PH 380–440V AC
Control Modes
SVPWM (Space Vector V/F)
Operator Interface
Integrated LED Keypad + Potentiometer
Complete INVT GD10 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, OV3, or Overcurrent).
| Fault Codes | Cause & Solution |
|---|---|
| OC1 Overcurrent during acceleration | Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC2 Overcurrent during deceleration | Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC3 Overcurrent at constant speed | Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OV1/OU1 Overvoltage during acceleration | Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV2/OU2 Overvoltage during deceleration | Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV3/OU3 Overvoltage at constant speed | Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| UV Bus undervoltage | Cause & Solution: 1. An instantaneous power failure occurs. - Reset the fault 2. The AC drive's input voltage is not within the permissible range. - Adjust the voltage to normal range. 3. The bus voltage is abnormal. - Replace the AC drive. 4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal. - Replace the AC drive. |
| OL1 Motor overload | Cause: - The voltage of the power supply is too low; - The motor setting rated current is incorrect; - The motor stall or load transients is too strong. Solution: - Check the power of the supply line; - Reset the rated current of the motor; - Check the load and adjust the torque lift. |
| OL2 VFD overload | Cause: - The acceleration is too fast; - Reset the rotating motor; - The voltage of the power supply is too low; - The load is too heavy; - The motor power is too large, and the power of the VFD is too small. Solution: - Increase the ACC time; - Avoid the restarting after stopping; - Check the power of the supply line; - Select a VFD with bigger power; - Select a proper motor. |
| OH1 Rectifier module overheat | Cause & Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. |
| OH2 Inverter module overheat | Cause & Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. |
| EF External Fault | Cause: SI external fault input terminals action. External fault comes when the drive has detected an issue with an external control circuit or device connected to it. This means the drive has detected an issue with an external device or control circuit connected to it. Unlike error codes specific to internal drive components, the EF code is more general and can be triggered by various external factors. Solution: 1. An alarm function of the external equipment was activated. - Inspect external equipment operation. - Remove the cause of the alarm that occurred. 2. Connection has been performed incorrectly. - Check if the wire for the external alarm signal is correctly connected to the terminal to which the "Alarm from external equipment" has been assigned. - Connect the wire for the alarm signal correctly. 3. Incorrect settings. - Check if the "Alarm from external equipment" has not been assigned to an unassigned terminal. - Correct the assignment. |
| CE RS485 communication Fault | Cause: - The baud rate setting is incorrect; - Fault occurs to the communication wiring; - The communication address is wrong; - There is strong interference to the communication. Solution: - Set proper baud rate; - Check the communication connection distribution; - Set proper communication address; - Chang or replace the connection distribution or improve the anti-interference capability. |
| EEP EEPROM operation fault | Cause: - Error of controlling the write and read of the parameters; - Damage to EEPROM. Solution: - Press STOP/RST to reset; - Change the main control panel. |
| PIDE PID feedback offline fault | Cause: - PID feedback offline; - PID feedback source disappear. Solution: - Check the PID feedback signal; - Check the PID feedback source. |
| END Running time reached | Cause: The actual running time of the VFD is above the internal setting running time. Solution: Ask for the supplier and adjust the setting running time. |
| OL3 Electrical overload | Cause: The VFD will report overload pre-alarm according to the set value. Solution: Check the load and the overload pre-alarm threshold. |
| LL Electronic underload fault | Cause: The VFD will report the underload pre-alarm according to the set value. Solution: 1. Check the load and the underload pre-alarm point. |
| PoFF System power off | Cause: System power off or low DC voltage. Solution: Check the grid. |
How to Clear & Reset INVT GD10 Drive Faults
- Keypad Reset: Press the red STOP/RST button on the integrated keypad. Ensure any active run command via terminals or communication is removed before resetting.
- Digital Input Reset (DI): If any digital multi-function input terminal (S1–S5) is configured for function 4 (Fault reset) in parameter group P05.01 to P05.05, toggle the terminal to clear the trip condition.
- Automatic Fault Reset: Enable automated clearing attempts by configuring parameter P08.28 (Fault reset times) between 1 and 10, and parameter P08.29 (Interval time of automatic fault reset) for desired reset delay intervals.
- Modbus RTU Reset: Send the fault reset bit via serial RS485 communication into the drive control word register using standard Modbus RTU protocol (P14 group parameters).
- Power Cycle: Disconnect incoming mains supply power completely. Wait until the keypad LED screen turns dark and the internal DC bus capacitors discharge fully (approx. 5 minutes), then reapply AC power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [(+)] and [(-)] before inspecting wiring, servicing the drive, or touching motor terminals U, V, and W on the INVT GD10 drive.