INVT GD20-09 Crane Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive20-09 (GD20-09) crane and hoisting drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 37 kW (1.0 – 50 HP)
Supply Voltage
380–440V AC (3-Phase)
Control Modes
Open-Loop Vector (SVC) & V/F
Operator Interface
LED Keypad / Optional External Keypad
Complete INVT GD20-09 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, bEr, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUt1 Inverter unit U phase protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs. Remedy:
|
| OUt2 Inverter unit V phase protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs. Remedy:
|
| OUt3 Inverter unit W phase protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs. Remedy:
|
| OV1 Overvoltage during acceleration | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OV2 Overvoltage during deceleration | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OV3 Overvoltage during constant speed | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OC1 Overcurrent during acceleration | Cause: Acceleration is too fast; The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference. Remedy:
|
| OC2 Overcurrent during deceleration | Cause: Deceleration is too fast; The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference. Remedy:
|
| OC3 Overcurrent during constant speed | Cause: The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference. Remedy:
|
| UV Bus undervoltage | Cause: The voltage of the grid is low; Overvoltage stall protection is not enabled. Remedy:
|
| OL1 Motor overload | Cause: The voltage of the grid is too low; The rated current is set improperly; Motor stall or load jumps violently. Remedy:
|
| OL2 VFD overload | Cause: The acceleration is too fast; The rotating motor is restarted; The voltage of the grid is too low; The load is too heavy; The motor power is too large, and the power of the VFD is too small. Remedy:
|
| SPI Phase loss on the input side | Cause: Phase loss or violent fluctuation occurred to R, S and T input. Remedy:
|
| SPO Phase loss on the output side | Cause: Phase loss occurred to U, V, W output (or the three phases of the load are seriously asymmetrical). Remedy:
|
| OH1 Rectifier module overheat | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload. Remedy:
|
| OH2 Inverter module overheat | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload. Remedy:
|
| EF External fault | Cause: SI external fault input terminal acts. Remedy:
|
| CE 485 communication fault | Cause: Baud rate is set improperly; The communication line is faulty; Communication address error; Communication suffers from strong interference. Remedy:
|
| ItE Current detection fault | Cause: The connector of control board is in poor contact; Exception occurred to amplification circuit. Remedy:
|
| tE Motor autotuning fault | Cause: Motor capacity does not match with the VFD capacity; Motor parameters are set improperly; The parameters gained from autotuning deviate sharply from the standard parameters; Autotuning timeout. Remedy:
|
| EEP EEPROM operation fault | Cause: R/W error occurred to the control parameters; EEPROM is damaged. Remedy:
|
| bCE Brake unit fault | Cause: Brake circuit fault or brake tube is damaged; The resistance of external braking resistor is too small. Remedy:
|
| END Running time reached | Cause: The actual running time of the VFD is larger than the preset running time. Remedy:
|
| OL3 Electronic overload fault | Cause: The VFD performs overload pre-alarm based on the set value. Remedy:
|
| PCE Keypad communication error | Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board. Remedy:
|
| UPE Parameter upload error | Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board. Remedy:
|
| DNE Parameter download error | Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Data storage error occurred to the keypad. Remedy:
|
| ETH1 To-ground short circuit fault 1 | Cause: VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply from the VFD power. Remedy:
|
| ETH2 To-ground short circuit fault 2 | Cause: VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply from the VFD power. Remedy:
|
| LL Electronic underload fault | Cause: The VFD performs underload pre-alarm based on the set value. Remedy:
|
| LC Current limiting fault | Cause: The VFD performs current limit pre-alarm based on the set current limit value. Remedy:
|
| FAE Brake feedback fault | Cause: The brake feedback circuit is disconnected or poorly contacted; The brake feedback detection time is too short. Remedy:
|
| tPF Torque verification fault | Cause: The torque verification current, moment force setting, and torque verification fault detection time are set improperly. Remedy:
|
| StC Operating lever fault | Cause: After the zeroing function is enabled, the operating lever restarts the VFD operation when it does not return to the zero position successfully. Remedy:
|
| LSP Low-speed running protection fault | Cause: The running frequency is too low; Frequency for low-speed running protection is set to too high. Remedy:
|
| tCE Terminal command exception | Cause: Forward and reverse running commands are given simultaneously. Remedy:
|
| POE Terminal command exception at power-on | Cause: The wiring of running command terminals has been short-circuited before power-on, or the polarity of terminals is set to be wrong; The state of the input terminal is inconsistent with the actual input. Remedy:
|
| SFE Set frequency fault | Cause: After the brake control is enabled, set P27.18 to 1 to enable the reference frequency detection. Set frequency is less than the value set in P27.19. Remedy:
|
| PTCE PTC motor overtemperature fault | Cause: The terminal selects PTC signal, and the terminal is valid due to too high motor temperature. Remedy:
|
| dIS Failure to enable the VFD | Cause: The input terminal selects VFD enabling, but the terminal signal is invalid. Remedy:
|
| A-OL Overload protection alarm | Cause: The load is too heavy. Remedy:
|
| A-LvP Low voltage alarm | Cause: The bus voltage is too low. Remedy:
|
| A-LU Upward position limit alarm | Cause: The input terminal has set the upward limited position reaching function, and there is a signal reference to the terminal. Remedy:
|
| A-Ld Downward position limit alarm | Cause: The input terminal has set the downward limited position reaching function, and there is a signal reference to the terminal. Remedy:
|
| A-Pt PT100 disconnection alarm | Cause: PT100 wiring circuit is disconnected. Remedy:
|
| A-Ot P100 overtemperature alarm | Cause: The current ambient temperature is too high; PT100 overtemperature prealarm setting is improper. Remedy:
|
| A-PTC PTC overtemperature alarm | Cause: The current ambient temperature is too high. Remedy:
|
| A-SSF Set frequency before brake release too small | Cause: Set frequency before brake release is less than brake release frequency. Remedy:
|
| A-rSF Set frequency after brake release too small | Cause: Set frequency after brake release is less than brake closing frequency. Remedy:
|
| A-SPI Input phase loss alarm | Cause: During stop, a loss of either input phase R, S, or T occurs or fluctuation is great. Remedy:
|
| PoFF System power failure | Cause: The system is powered off or the bus voltage is too low. Remedy:
|
How to Clear & Reset INVT GD20-09 Drive Faults
- Keypad Reset: Press the red STOP/RST button on the drive keypad. Ensure all crane run or hoisting commands via terminals or fieldbus are released before attempting to clear the fault.
- Digital Input Reset (DI): If an assignable digital input terminal (S1–S8) is configured for function 4 (Fault reset) in parameter group P05.01 to P05.08, pulse that terminal to reset the trip state.
- Automatic Fault Reset: Parameter P08.28 (Fault reset times) can be set from 1 to 10 with P08.29 (Interval time of automatic fault reset) for delay timing. Note: In crane/hoist applications, confirm mechanical brake engagement before enabling auto-reset.
- Modbus RTU Reset: Send the fault reset bit via serial RS485 communication into the drive control word register using standard Modbus RTU protocol (P14 group parameters).
- AC Mains Power Cycle: Shut down the main 3-phase AC supply disconnect. Wait at least 5 minutes until the LED keypad display powers off completely and internal DC capacitors discharge, then reapply power.
⚠️ High-Voltage & Hoisting Safety Warning:
Ensure the crane load is grounded and mechanically secured before servicing. Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [(+)] and [(-)] (or [P1] and [(-)]) before inspecting mechanical brake wiring, power cables, or motor leads U, V, and W on the INVT GD20-09 drive.