INVT GD20-09 Crane Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive20-09 (GD20-09) crane and hoisting drive series. Search or filter through the complete fault code directory below.

Dedicated Crane & Hoisting VFD Power: 0.75 to 37 kW (1.0 to 50 HP) Built-in Brake Logic & Crane Macros
Power Range 0.75 – 37 kW (1.0 – 50 HP)
Supply Voltage 380–440V AC (3-Phase)
Control Modes Open-Loop Vector (SVC) & V/F
Operator Interface LED Keypad / Optional External Keypad

Complete INVT GD20-09 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, bEr, or Overcurrent).

Fault Code and MeaningCause and Remedy
OUt1
Inverter unit U phase protection

Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check the drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OUt2
Inverter unit V phase protection

Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check the drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OUt3
Inverter unit W phase protection

Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short-circuit occurs.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check the drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OV1
Overvoltage during acceleration

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power supply.

  • Check whether load deceleration time is too short.

  • Check if the motor starts during rotating.

  • Install dynamic braking units.

  • Check the setup of related function codes.


OV2
Overvoltage during deceleration

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power supply.

  • Check whether load deceleration time is too short.

  • Install dynamic braking units.

  • Check the setup of related function codes.


OV3
Overvoltage during constant speed

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power supply.

  • Install dynamic braking units.

  • Check the setup of related function codes.


OC1
Overcurrent during acceleration

Cause: Acceleration is too fast; The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference.



Remedy:

  • Increase the acceleration time.

  • Check the input power supply.

  • Select a VFD with larger power.

  • Check whether the load is short circuited (to-ground or line-to-line) or if rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.


OC2
Overcurrent during deceleration

Cause: Deceleration is too fast; The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference.



Remedy:

  • Increase the deceleration time.

  • Check the input power supply.

  • Select a VFD with larger power.

  • Check whether the load is short circuited (to-ground or line-to-line) or if rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.


OC3
Overcurrent during constant speed

Cause: The voltage of the grid is low; The power of the VFD is low; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference.



Remedy:

  • Check the input power supply.

  • Select a VFD with larger power.

  • Check whether the load is short circuited (to-ground or line-to-line) or if rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.


UV
Bus undervoltage

Cause: The voltage of the grid is low; Overvoltage stall protection is not enabled.



Remedy:

  • Check the input power supply of the grid.

  • Check the setup of related function codes.


OL1
Motor overload

Cause: The voltage of the grid is too low; The rated current is set improperly; Motor stall or load jumps violently.



Remedy:

  • Check the voltage of the grid.

  • Set the rated current of the motor again.

  • Check the load and adjust the torque boost.


OL2
VFD overload

Cause: The acceleration is too fast; The rotating motor is restarted; The voltage of the grid is too low; The load is too heavy; The motor power is too large, and the power of the VFD is too small.



Remedy:

  • Increase the acceleration time.

  • Avoid restarting the motor immediately after it stops.

  • Check the voltage of the grid.

  • Use a VFD with greater power.

  • Use a motor that meets the operation requirements.


SPI
Phase loss on the input side

Cause: Phase loss or violent fluctuation occurred to R, S and T input.



Remedy:

  • Check the input power supply.

  • Check the installation wiring.


SPO
Phase loss on the output side

Cause: Phase loss occurred to U, V, W output (or the three phases of the load are seriously asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cables.


OH1
Rectifier module overheat

Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


OH2
Inverter module overheat

Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


EF
External fault

Cause: SI external fault input terminal acts.



Remedy:

  • Check the external device input.


CE
485 communication fault

Cause: Baud rate is set improperly; The communication line is faulty; Communication address error; Communication suffers from strong interference.



Remedy:

  • Set proper baud rate.

  • Check the wiring of communication interfaces.

  • Set proper communication address.

  • Replace or change the wiring to enhance anti-interference capability.


ItE
Current detection fault

Cause: The connector of control board is in poor contact; Exception occurred to amplification circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the main control board.


tE
Motor autotuning fault

Cause: Motor capacity does not match with the VFD capacity; Motor parameters are set improperly; The parameters gained from autotuning deviate sharply from the standard parameters; Autotuning timeout.



Remedy:

  • Change the VFD model.

  • Set proper motor type and nameplate parameters.

  • Empty the motor load and carry out autotuning again.

  • Check motor wiring and parameter setup.

  • Check whether upper limit frequency is larger than 2/3 of the rated frequency.


EEP
EEPROM operation fault

Cause: R/W error occurred to the control parameters; EEPROM is damaged.



Remedy:

  • Press the STOP/RST key to reset.

  • Replace the main control board.


bCE
Brake unit fault

Cause: Brake circuit fault or brake tube is damaged; The resistance of external braking resistor is too small.



Remedy:

  • Check the brake unit, and replace with new brake tubes.

  • Increase the brake resistance.


END
Running time reached

Cause: The actual running time of the VFD is larger than the preset running time.



Remedy:

  • Ask help from the supplier, and adjust the preset running time.


OL3
Electronic overload fault

Cause: The VFD performs overload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


PCE
Keypad communication error

Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board.



Remedy:

  • Check the keypad wires to confirm whether fault exists.

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


UPE
Parameter upload error

Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


DNE
Parameter download error

Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Data storage error occurred to the keypad.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.

  • Re-backup keypad data.


ETH1
To-ground short circuit fault 1

Cause: VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply from the VFD power.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.

  • Check whether motor power parameters in P2 group are consistent with motor power.


ETH2
To-ground short circuit fault 2

Cause: VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply from the VFD power.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.

  • Check whether motor power parameters in P2 group are consistent with motor power.


LL
Electronic underload fault

Cause: The VFD performs underload pre-alarm based on the set value.



Remedy:

  • Check the load and underload pre-alarm threshold.


LC
Current limiting fault

Cause: The VFD performs current limit pre-alarm based on the set current limit value.



Remedy:

  • Check the set auto current limiting threshold and present current value.


FAE
Brake feedback fault

Cause: The brake feedback circuit is disconnected or poorly contacted; The brake feedback detection time is too short.



Remedy:

  • Check the brake feedback circuit.

  • Increase the detection time P19.24 to a proper value.


tPF
Torque verification fault

Cause: The torque verification current, moment force setting, and torque verification fault detection time are set improperly.



Remedy:

  • Check the set value of torque verification current and present current value.


StC
Operating lever fault

Cause: After the zeroing function is enabled, the operating lever restarts the VFD operation when it does not return to the zero position successfully.



Remedy:

  • Reset the start command.

  • Properly adjust the zero-point position detection delay set in P19.38 when the zero position is detected successfully.


LSP
Low-speed running protection fault

Cause: The running frequency is too low; Frequency for low-speed running protection is set to too high.



Remedy:

  • Check the actual running frequency.

  • Lower the frequency for low-speed running protection (P19.43) properly.


tCE
Terminal command exception

Cause: Forward and reverse running commands are given simultaneously.



Remedy:

  • Check the wiring of the forward running command.

  • Check the wiring of the reverse running command.

  • View the state of input terminals and check whether forward and reverse signals are sent simultaneously.


POE
Terminal command exception at power-on

Cause: The wiring of running command terminals has been short-circuited before power-on, or the polarity of terminals is set to be wrong; The state of the input terminal is inconsistent with the actual input.



Remedy:

  • Check the wiring of input terminals.

  • Check the polarity of input terminals.

  • View the state of the input terminals, and check whether input terminals suffer interference.


SFE
Set frequency fault

Cause: After the brake control is enabled, set P27.18 to 1 to enable the reference frequency detection. Set frequency is less than the value set in P27.19.



Remedy:

  • Check whether the frequency reference is exceptional.

  • If the frequency is given by terminals, check whether the input terminal wiring is exceptional or interfered.


PTCE
PTC motor overtemperature fault

Cause: The terminal selects PTC signal, and the terminal is valid due to too high motor temperature.



Remedy:

  • Check whether the motor temperature is too high.

  • Check the input terminal wiring is exceptional or interfered.


dIS
Failure to enable the VFD

Cause: The input terminal selects VFD enabling, but the terminal signal is invalid.



Remedy:

  • Check the input terminal setting and terminal signal.


A-OL
Overload protection alarm

Cause: The load is too heavy.



Remedy:

  • Check whether the load is too heavy.


A-LvP
Low voltage alarm

Cause: The bus voltage is too low.



Remedy:

  • Check whether the low voltage protection threshold is too high.

  • Check whether the grid voltage or rectifier module is abnormal.


A-LU
Upward position limit alarm

Cause: The input terminal has set the upward limited position reaching function, and there is a signal reference to the terminal.



Remedy:

  • Check whether the allowed highest position point has been reached.

  • Check the input terminal signal.


A-Ld
Downward position limit alarm

Cause: The input terminal has set the downward limited position reaching function, and there is a signal reference to the terminal.



Remedy:

  • Check whether the allowed lowest position point has been reached.

  • Check the input terminal signal.


A-Pt
PT100 disconnection alarm

Cause: PT100 wiring circuit is disconnected.



Remedy:

  • Check PT100 wiring circuit.


A-Ot
P100 overtemperature alarm

Cause: The current ambient temperature is too high; PT100 overtemperature prealarm setting is improper.



Remedy:

  • Check the current ambient temperature.

  • Check whether PT100 overtemperature protection threshold is too low.


A-PTC
PTC overtemperature alarm

Cause: The current ambient temperature is too high.



Remedy:

  • Check the current ambient temperature.

  • Check the input terminal signal.


A-SSF
Set frequency before brake release too small

Cause: Set frequency before brake release is less than brake release frequency.



Remedy:

  • Check whether set frequency is less than brake release frequency.


A-rSF
Set frequency after brake release too small

Cause: Set frequency after brake release is less than brake closing frequency.



Remedy:

  • Check whether set frequency is less than brake closing frequency.


A-SPI
Input phase loss alarm

Cause: During stop, a loss of either input phase R, S, or T occurs or fluctuation is great.



Remedy:

  • Check the input power source and wiring.


PoFF
System power failure

Cause: The system is powered off or the bus voltage is too low.



Remedy:

  • Check the grid conditions.


How to Clear & Reset INVT GD20-09 Drive Faults

  1. Keypad Reset: Press the red STOP/RST button on the drive keypad. Ensure all crane run or hoisting commands via terminals or fieldbus are released before attempting to clear the fault.
  2. Digital Input Reset (DI): If an assignable digital input terminal (S1–S8) is configured for function 4 (Fault reset) in parameter group P05.01 to P05.08, pulse that terminal to reset the trip state.
  3. Automatic Fault Reset: Parameter P08.28 (Fault reset times) can be set from 1 to 10 with P08.29 (Interval time of automatic fault reset) for delay timing. Note: In crane/hoist applications, confirm mechanical brake engagement before enabling auto-reset.
  4. Modbus RTU Reset: Send the fault reset bit via serial RS485 communication into the drive control word register using standard Modbus RTU protocol (P14 group parameters).
  5. AC Mains Power Cycle: Shut down the main 3-phase AC supply disconnect. Wait at least 5 minutes until the LED keypad display powers off completely and internal DC capacitors discharge, then reapply power.
⚠️ High-Voltage & Hoisting Safety Warning: Ensure the crane load is grounded and mechanically secured before servicing. Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [(+)] and [(-)] (or [P1] and [(-)]) before inspecting mechanical brake wiring, power cables, or motor leads U, V, and W on the INVT GD20-09 drive.