INVT GD600 Series Multi-Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive600 (GD600) common DC bus multi-drive inverter system. Search or filter through the complete fault code directory below.
Power Range
1.5 – 75 kW (Modules up to 500 kW)
Supply Voltage
3PH 380–440V AC / Common DC Bus
Control Modes
Closed-Loop Vector (VC), SVC & V/F
Operator Interface
Detachable LCD Keypad / Fieldbus Master
Complete INVT GD600 Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUT1, OC1, OV2, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| LV1 Input grid undervoltage | Cause: The grid voltage is 20% lower than the general value, or the internal hardware circuit of the rectifier unit is abnormal. Remedy:
|
| OV1 Grid voltage | Cause: The grid voltage is 20% higher than the general value, or the internal hardware circuit of the rectifier unit is abnormal. Remedy:
|
| SPI1 A phase loss on the input side | Cause: A phase on the input side is lost. Remedy:
|
| SPI2 B phase loss on the input side | Cause: B phase on the input side is lost. Remedy:
|
| SPI3 C phase loss on the input side | Cause: C phase on the input side is lost. Remedy:
|
| PLLF Phase-locked failed | Cause: The grid voltage is abnormal. Remedy:
|
| OH1 Bridge rectifier module overheating | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running. Remedy:
|
| OH2 Heat sink module overheating | Cause: Ambient temperature is too high; Long-time overload running. Remedy:
|
| EF External fault | Cause: SI external fault input terminal acts. Remedy:
|
| E-485 485 communication fault | Cause: Baud rate is set improperly; Communication line fault; Communication address error; Communication suffers from strong interference. Remedy:
|
| LV Bus undervoltage | Cause: Bus undervoltage occurs during operation; Detect the actual bus voltage. Remedy:
|
| OV Bus overvoltage | Cause: Bus overvoltage occurs during operation; Detect the actual bus voltage. Remedy:
|
| EEP EEPROM operation fault | Cause: R/W error occurred to the control parameters; EEPROM is damaged. Remedy:
|
| OL Rectifier unit overload fault | Cause: The rectifier unit releases overload pre-alarm based on the set value. Remedy:
|
| bCE Braking unit direct connection fault | Cause: Fault occurred to the brake circuit or the braking pipe is damaged. Remedy:
|
| bOL Braking pipe overload | Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small. Remedy:
|
| bOC Brake overcurrent | Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small. Remedy:
|
| E-DP PROFIBUS communication fault | Cause: The communication address is incorrect; The matching resistor is not switched on improperly; The GSD file of the master station is set improperly; The peripheral interference is too large. Remedy:
|
| E-NET Ethernet communication fault | Cause: The address of Ethernet is set improperly; Ethernet communication mode is selected improperly; The peripheral interference is too large. Remedy:
|
| E-CAN CANopen communication fault | Cause: Line contact is poor; The matching resistor is not switched on; Communication baud rates do not match; The peripheral interference is too large. Remedy:
|
| OFFL Certain slave units offline | Cause: The number of actual slave nodes (P17.15) conflicts with the number of set slave nodes (P21.33); Line contact is poor; Matching resistor not on; Baud rates do not match; Address conflict. Remedy:
|
| PCE PLC card communication fault | Cause: Communication address incorrect; Matching resistor not switched on; GSD file set improperly; Peripheral interference too large. Remedy:
|
| E-C1 Communication fault occurred to the expansion card slot 1 | Cause: The communication state of communication card in the expansion card slot 1 is abnormal; The peripheral interference is too large. Remedy:
|
| E-C2 Communication fault occurred to the expansion card slot 2 | Cause: The communication state of communication card in the expansion card slot 2 is abnormal; The peripheral interference is too large. Remedy:
|
| E-F1 Identification fault occurred to the expansion card slot 1 | Cause: The communication card in the expansion card slot 1 failed to be identified normally; The peripheral interference is too large. Remedy:
|
| E-F2 Identification fault occurred to the expansion card slot 2 | Cause: The communication card in the expansion card slot 2 failed to be identified normally; The peripheral interference is too large. Remedy:
|
| E-CP Expansion card detection abnormation | Cause: The type of the expansion card is wrong; The peripheral interference is too large. Remedy:
|
| END Running time reached | Cause: The actual running time is longer than the set time. Remedy:
|
| OUt1 Inverter unit U-phase protection | Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs. Remedy:
|
| OUt2 Inverter unit V-phase protection | Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs. Remedy:
|
| OUt3 Inverter unit W-phase protection | Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs. Remedy:
|
| OV1 Over-voltage during ACC | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OV2 Over-voltage during DEC | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OV3 Over-voltage during constant speed running | Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled. Remedy:
|
| OC1 Over-current during ACC | Cause: ACC is too fast; Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference; Overvoltage stall protection not enabled. Remedy:
|
| OC2 Over-current during DEC | Cause: Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference. Remedy:
|
| OC3 Over-current during constant speed running | Cause: Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference. Remedy:
|
| UV Bus undervoltage fault | Cause: Grid voltage is too low; Overvoltage stall protection is not enabled. Remedy:
|
| OL1 Motor overload | Cause: Grid voltage is too low; Rated current of the motor is set improperly; Motor stall or load jumps violently. Remedy:
|
| OL2 Inverter overload | Cause: ACC is too fast; The motor in rotating is restarted; Grid voltage is too low; Load is too large; Power is too small. Remedy:
|
| SECAN Master/slave synchronous CAN fault | Cause: In master station mode, the communication network has two or more slaves of the same station; Slave count inconsistency. Remedy:
|
| SPO Phase loss on output side | Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical). Remedy:
|
| OH2 Overheat of inverter module | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running. Remedy:
|
| CE RS485 communication fault | Cause: Incorrect baud rate; Communication line fault; Incorrect communication address. Remedy:
|
| ItE Current detection fault | Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit. Remedy:
|
| tE Motor autotuning fault | Cause: Motor capacity does not match inverter capacity; Difference exceeds five power classes. Remedy:
|
| EEP EEPROM fault | Cause: R/W error occurred to the control parameters; EEPROM is damaged. Remedy:
|
| PIDE PID feedback offline fault | Cause: PID feedback offline; PID feedback source disappears. Remedy:
|
| S-Err Master/slave synchronous CAN slave fault | Cause: In the master station mode, the master station detects that a fault occurred to the slave. Remedy:
|
| OL3 Electronic overload fault | Cause: The inverter releases overload pre-alarm based on the set value. Remedy:
|
| PCE Keypad communication fault | Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad or mainboard circuit error. Remedy:
|
| UPE Parameter upload error | Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad or mainboard circuit error. Remedy:
|
| DNE Parameter download error | Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad data storage error. Remedy:
|
| ETH1 To-ground short circuit fault 1 | Cause: Inverter output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply. Remedy:
|
| ETH2 To-ground short circuit fault 2 | Cause: Inverter output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply. Remedy:
|
| dEu Speed deviation fault | Cause: Load is too heavy, or stall occurred. Remedy:
|
| STo Maladjustment fault | Cause: Control parameters of the synchronous motor set improperly; Parameter gained from autotuning is inaccurate; Inverter not connected to motor. Remedy:
|
| LL Electronic underload fault | Cause: The inverter performs the underload pre-alarm based on the set value. Remedy:
|
| ENC1O Encoder offline fault | Cause: Encoder line sequence is wrong, or signal wires are poorly connected. Remedy:
|
| ENC1D Encoder reversal fault | Cause: The encoder speed signal is contrary to the motor running direction. Remedy:
|
| ENC1Z Encoder Z pulse offline fault | Cause: Z signal wires are disconnected. Remedy:
|
| OT Motor over-temperature fault | Cause: Motor over-temperature input terminal is valid; Temperature detection resistance is abnormal; Long-time overload. Remedy:
|
| E-OT2 Overtemperature fault (24V PG card) | Cause: The temperature detected by EC-PG707-24 exceeds the threshold. Remedy:
|
| E-OT3 Overtemperature fault (IO card) | Cause: The temperature detected by EC-IO702 exceeds the threshold. Remedy:
|
| E-OT4 Overtemperature fault (AI/AO detection) | Cause: The temperature detected by AI/AO exceeds the threshold. Remedy:
|
| STO Safe torque off | Cause: Safe torque off function is enabled by external forces. Remedy:
|
| STL1 Exception occurred to safe circuit of channel H1 | Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault. Remedy:
|
| STL2 Exception occurred to safe circuit of channel H2 | Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault. Remedy:
|
| STL3 Exception occurred to channel H1 and channel H2 | Cause: Hardware fault occurred to STO circuit. Remedy:
|
| CrCE Safety code FLASH CRC check fault | Cause: Control board is faulty. Remedy:
|
| P-E1 PLC card customized fault 1 | Cause: Faults defined by the PLC expansion card. Remedy:
|
| P-E2 to P-E10 PLC card customized faults | Cause: PLC card customized faults (2 through 10). Remedy:
|
| E-Err Repetitive expansion card type | Cause: The two inserted expansion cards are of the same type. Remedy:
|
| ENCUV Encoder UVW loss fault | Cause: No electric level variation occurred to UVW signal. Remedy:
|
| F1-Er Failed to identify the expansion card in card slot 1 | Cause: There is data transmission in interfaces of card slot 1, however, it cannot read the card type. Remedy:
|
| F2-Er Failed to identify the expansion card in card slot 2 | Cause: There is data transmission in interfaces of card slot 2, however, it cannot read the card type. Remedy:
|
| C1-Er Communication timeout occurred to the expansion card in card slot 1 | Cause: There is no data transmission in interfaces of card slot 1. Remedy:
|
| C2-Er Communication timeout occurred to the expansion card in card slot 2 | Cause: There is no data transmission in interfaces of card slot 2. Remedy:
|
| PoFF System power failure | Cause: The system is powered off or the bus voltage is too low. Remedy:
|
How to Clear & Reset INVT GD600 Series Drive Faults
- Keypad Reset: Press the red STOP/RST key on the local LCD operation panel of the tripped inverter unit or master rectifier module. Ensure running signals from the line controller are disengaged prior to resetting.
- Digital Input Reset (DI): If any control terminal (S1–S8 or HDI) on the unit’s I/O terminal board is programmed to function 7 (Fault reset) in parameter group P05.01 to P05.08, pulse the terminal contact to clear the trip.
- Industrial Fieldbus / PLC Reset: In automated continuous lines, clear trips through network control words (Profinet, EtherCAT, Modbus TCP/RTU) by sending control command 0007H to communication register address 2000H or pulsing Bit 7 in the fieldbus control word.
- Automatic Fault Reset: For transient network dips, configure parameter P08.28 (Fault reset times) and P08.29 (Fault reset interval) to allow the individual drive unit to automatically resume operation.
- Common DC Bus System Power Cycle: De-energize the main AC circuit breaker feeding the primary rectifier unit. Wait at least 15 minutes to allow the centralized capacitor banks across the common DC busbar to fully discharge before repowering.
⚠️ Extreme DC Bus Energy Safety Warning:
Common DC bus multi-drive architectures interconnect substantial capacitive energy across shared busbars. Always isolate the primary AC input to the rectifier unit, disconnect any regenerative feedback sources, and verify with a calibrated digital multimeter that DC bus voltage across shared [(+)] and [(-)] busbars is strictly below 36VDC before removing book-type drive modules or touching output terminals U, V, and W.