INVT GD600 Series Multi-Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive600 (GD600) common DC bus multi-drive inverter system. Search or filter through the complete fault code directory below.

Common DC Bus Multi-Drive Power: 1.5 to 75 kW / Module (to 500 kW System) Embedded Safe Torque Off (STO SIL3)
Power Range 1.5 – 75 kW (Modules up to 500 kW)
Supply Voltage 3PH 380–440V AC / Common DC Bus
Control Modes Closed-Loop Vector (VC), SVC & V/F
Operator Interface Detachable LCD Keypad / Fieldbus Master

Complete INVT GD600 Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OUT1, OC1, OV2, or Overcurrent).

Fault Code and MeaningCause and Remedy
LV1
Input grid undervoltage

Cause: The grid voltage is 20% lower than the general value, or the internal hardware circuit of the rectifier unit is abnormal.



Remedy:

  • Check the grid input power.


OV1
Grid voltage

Cause: The grid voltage is 20% higher than the general value, or the internal hardware circuit of the rectifier unit is abnormal.



Remedy:

  • Check the grid input power.

  • Check the related function code settings.


SPI1
A phase loss on the input side

Cause: A phase on the input side is lost.



Remedy:

  • Check the wiring of A phase and grid voltage.


SPI2
B phase loss on the input side

Cause: B phase on the input side is lost.



Remedy:

  • Check the wiring of B phase and grid voltage.


SPI3
C phase loss on the input side

Cause: C phase on the input side is lost.



Remedy:

  • Check the wiring of C phase and grid voltage.


PLLF
Phase-locked failed

Cause: The grid voltage is abnormal.



Remedy:

  • Check the input wiring and grid voltage.


OH1
Bridge rectifier module overheating

Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


OH2
Heat sink module overheating

Cause: Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


EF
External fault

Cause: SI external fault input terminal acts.



Remedy:

  • Check external device input.


E-485
485 communication fault

Cause: Baud rate is set improperly; Communication line fault; Communication address error; Communication suffers from strong interference.



Remedy:

  • Set proper baud rate.

  • Check the wiring of communication interfaces.

  • Set the proper communication address.

  • Replace or change the wiring to enhance the anti-interference capacity.


LV
Bus undervoltage

Cause: Bus undervoltage occurs during operation; Detect the actual bus voltage.



Remedy:

  • Check the bus voltage.

  • Change the undervoltage threshold parameter.

  • Replace the main control board.


OV
Bus overvoltage

Cause: Bus overvoltage occurs during operation; Detect the actual bus voltage.



Remedy:

  • Check the bus voltage.

  • Change the overvoltage threshold parameter.

  • Replace the main control board.


EEP
EEPROM operation fault

Cause: R/W error occurred to the control parameters; EEPROM is damaged.



Remedy:

  • Press STOP/RST to reset.

  • Replace the main control board.


OL
Rectifier unit overload fault

Cause: The rectifier unit releases overload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


bCE
Braking unit direct connection fault

Cause: Fault occurred to the brake circuit or the braking pipe is damaged.



Remedy:

  • Check the braking unit, and replace with new braking pipe.

  • Increase the brake resistance.


bOL
Braking pipe overload

Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small.



Remedy:

  • Check the braking unit, and replace with new braking pipe.

  • Increase the brake resistance.


bOC
Brake overcurrent

Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small.



Remedy:

  • Check the braking unit, and replace with new braking pipe.

  • Increase the brake resistance.


E-DP
PROFIBUS communication fault

Cause: The communication address is incorrect; The matching resistor is not switched on improperly; The GSD file of the master station is set improperly; The peripheral interference is too large.



Remedy:

  • Check the related settings.

  • Check the surrounding environment, and eliminate interference effects.


E-NET
Ethernet communication fault

Cause: The address of Ethernet is set improperly; Ethernet communication mode is selected improperly; The peripheral interference is too large.



Remedy:

  • Check the related settings.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E-CAN
CANopen communication fault

Cause: Line contact is poor; The matching resistor is not switched on; Communication baud rates do not match; The peripheral interference is too large.



Remedy:

  • Check the line.

  • Switch on the matching resistor.

  • Set the same baud rate.

  • Check the surrounding environment, and eliminate interference effects.


OFFL
Certain slave units offline

Cause: The number of actual slave nodes (P17.15) conflicts with the number of set slave nodes (P21.33); Line contact is poor; Matching resistor not on; Baud rates do not match; Address conflict.



Remedy:

  • Check the values of P17.15 and P21.33.

  • Switch on the matching resistor.

  • Set the same baud rate.

  • Check all master/slave addresses.

  • Check CANopen network parameters.


PCE
PLC card communication fault

Cause: Communication address incorrect; Matching resistor not switched on; GSD file set improperly; Peripheral interference too large.



Remedy:

  • Check the related settings.

  • Check the surrounding environment, and eliminate interference effects.


E-C1
Communication fault occurred to the expansion card slot 1

Cause: The communication state of communication card in the expansion card slot 1 is abnormal; The peripheral interference is too large.



Remedy:

  • Check whether the expansion card in card slot 1 is contacted well.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E-C2
Communication fault occurred to the expansion card slot 2

Cause: The communication state of communication card in the expansion card slot 2 is abnormal; The peripheral interference is too large.



Remedy:

  • Check whether the expansion card in card slot 2 is contacted well.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E-F1
Identification fault occurred to the expansion card slot 1

Cause: The communication card in the expansion card slot 1 failed to be identified normally; The peripheral interference is too large.



Remedy:

  • Check whether the expansion card in card slot 1 is contacted well.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E-F2
Identification fault occurred to the expansion card slot 2

Cause: The communication card in the expansion card slot 2 failed to be identified normally; The peripheral interference is too large.



Remedy:

  • Check whether the expansion card in card slot 2 is contacted well.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E-CP
Expansion card detection abnormation

Cause: The type of the expansion card is wrong; The peripheral interference is too large.



Remedy:

  • Check whether the expansion card is good.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


END
Running time reached

Cause: The actual running time is longer than the set time.



Remedy:

  • Ask the supplier to adjust the preset running time.


OUt1
Inverter unit U-phase protection

Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs.



Remedy:

  • Increase ACC time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OUt2
Inverter unit V-phase protection

Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs.



Remedy:

  • Increase ACC time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OUt3
Inverter unit W-phase protection

Cause: ACC is too fast; IGBT module is damaged; Misacts caused by interference; Drive wires are poorly connected; To-ground short circuit occurs.



Remedy:

  • Increase ACC time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounding the peripheral device.


OV1
Over-voltage during ACC

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power.

  • Check whether load DEC time is too short.

  • Install dynamic brake components.

  • Check the setup of related function codes.


OV2
Over-voltage during DEC

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power.

  • Check whether load DEC time is too short.

  • Install dynamic brake components.

  • Check the setup of related function codes.


OV3
Over-voltage during constant speed running

Cause: Exception occurred to input voltage; Large energy feedback; Lack of braking units; Dynamic brake is not enabled.



Remedy:

  • Check the input power.

  • Install dynamic brake components.

  • Check the setup of related function codes.


OC1
Over-current during ACC

Cause: ACC is too fast; Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference; Overvoltage stall protection not enabled.



Remedy:

  • Increase ACC /DEC time.

  • Check the input power.

  • Select the inverter with larger power.

  • Check if the load is short circuited or rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.

  • Check the setup of related function codes.


OC2
Over-current during DEC

Cause: Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference.



Remedy:

  • Increase ACC /DEC time.

  • Check the input power.

  • Select the inverter with larger power.

  • Check if the load is short circuited.

  • Check the output wiring.

  • Check if there is strong interference.


OC3
Over-current during constant speed running

Cause: Grid voltage is too low; Inverter power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference.



Remedy:

  • Check the input power.

  • Select the inverter with larger power.

  • Check if the load is short circuited.

  • Check the output wiring.

  • Check if there is strong interference.


UV
Bus undervoltage fault

Cause: Grid voltage is too low; Overvoltage stall protection is not enabled.



Remedy:

  • Check the grid input power.

  • Check the setup of related function codes.


OL1
Motor overload

Cause: Grid voltage is too low; Rated current of the motor is set improperly; Motor stall or load jumps violently.



Remedy:

  • Check the grid voltage.

  • Reset the rated current of the motor.

  • Check the load and adjust torque boost.


OL2
Inverter overload

Cause: ACC is too fast; The motor in rotating is restarted; Grid voltage is too low; Load is too large; Power is too small.



Remedy:

  • Increase ACC time.

  • Avoid restart after stop.

  • Check grid voltage.

  • Select the inverter with larger power.

  • Select proper motor.


SECAN
Master/slave synchronous CAN fault

Cause: In master station mode, the communication network has two or more slaves of the same station; Slave count inconsistency.



Remedy:

  • Check whether the slave stations in the communication network are set repeatedly.

  • Check whether the wiring of each slave station and master station is normal.


SPO
Phase loss on output side

Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cable.


OH2
Overheat of inverter module

Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


CE
RS485 communication fault

Cause: Incorrect baud rate; Communication line fault; Incorrect communication address.



Remedy:

  • Set a proper baud rate.

  • Check the communication interface cable.

  • Set the communication address correctly.

  • Replace or change the wiring to enhance the anti-interference capacity.


ItE
Current detection fault

Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the hall component.

  • Replace the main control board.


tE
Motor autotuning fault

Cause: Motor capacity does not match inverter capacity; Difference exceeds five power classes.



Remedy:

  • Change the inverter model, or adopt V/F mode for control.

  • Set proper motor type and nameplate parameters.

  • Empty the motor load and carry out autotuning again.


EEP
EEPROM fault

Cause: R/W error occurred to the control parameters; EEPROM is damaged.



Remedy:

  • Press STOP/RST to reset.

  • Replace the main control board.


PIDE
PID feedback offline fault

Cause: PID feedback offline; PID feedback source disappears.



Remedy:

  • Check PID feedback signal wires.

  • Check PID feedback source.


S-Err
Master/slave synchronous CAN slave fault

Cause: In the master station mode, the master station detects that a fault occurred to the slave.



Remedy:

  • Check the fault occurred to CAN slave station in the communication network.


OL3
Electronic overload fault

Cause: The inverter releases overload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


PCE
Keypad communication fault

Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad or mainboard circuit error.



Remedy:

  • Check the keypad cable.

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.


UPE
Parameter upload error

Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad or mainboard circuit error.



Remedy:

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.


DNE
Parameter download error

Cause: Keypad cable connected improperly/disconnected; Cable too long causing interference; Keypad data storage error.



Remedy:

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.

  • Re-back up the data on the keypad.


ETH1
To-ground short circuit fault 1

Cause: Inverter output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply.



Remedy:

  • Check whether the motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


ETH2
To-ground short circuit fault 2

Cause: Inverter output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply.



Remedy:

  • Check whether the motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


dEu
Speed deviation fault

Cause: Load is too heavy, or stall occurred.



Remedy:

  • Check the load to ensure it is proper, and increase the detection time.

  • Check whether the control parameters are set properly.


STo
Maladjustment fault

Cause: Control parameters of the synchronous motor set improperly; Parameter gained from autotuning is inaccurate; Inverter not connected to motor.



Remedy:

  • Check the load to ensure it is proper.

  • Check whether the control parameters are set correctly.

  • Increase the maladjustment detection time.


LL
Electronic underload fault

Cause: The inverter performs the underload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


ENC1O
Encoder offline fault

Cause: Encoder line sequence is wrong, or signal wires are poorly connected.



Remedy:

  • Check the encoder wiring.


ENC1D
Encoder reversal fault

Cause: The encoder speed signal is contrary to the motor running direction.



Remedy:

  • Reset encoder direction.


ENC1Z
Encoder Z pulse offline fault

Cause: Z signal wires are disconnected.



Remedy:

  • Check the wiring of Z signal.


OT
Motor over-temperature fault

Cause: Motor over-temperature input terminal is valid; Temperature detection resistance is abnormal; Long-time overload.



Remedy:

  • Check the wiring of the motor over-temperature input terminal (function 57).

  • Check whether the temperature sensor is proper.

  • Check the motor, and perform maintenance on the motor.


E-OT2
Overtemperature fault (24V PG card)

Cause: The temperature detected by EC-PG707-24 exceeds the threshold.



Remedy:

  • Check for external overtemperature.

  • Check and maintain related devices.


E-OT3
Overtemperature fault (IO card)

Cause: The temperature detected by EC-IO702 exceeds the threshold.



Remedy:

  • Check for external overtemperature.

  • Check and maintain related devices.


E-OT4
Overtemperature fault (AI/AO detection)

Cause: The temperature detected by AI/AO exceeds the threshold.



Remedy:

  • Check for external overtemperature.

  • Check and maintain related devices.


STO
Safe torque off

Cause: Safe torque off function is enabled by external forces.



Remedy:

  • (No specific remedy listed, check external safety switches).


STL1
Exception occurred to safe circuit of channel H1

Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault.



Remedy:

  • Check whether terminal wiring of STO is proper and firm.

  • Check whether the external switch of STO can work properly.

  • Replace the control board.


STL2
Exception occurred to safe circuit of channel H2

Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault.



Remedy:

  • Check whether terminal wiring of STO is proper and firm.

  • Check whether the external switch of STO can work properly.

  • Replace the control board.


STL3
Exception occurred to channel H1 and channel H2

Cause: Hardware fault occurred to STO circuit.



Remedy:

  • Replace the control board.


CrCE
Safety code FLASH CRC check fault

Cause: Control board is faulty.



Remedy:

  • Replace the control board.


P-E1
PLC card customized fault 1

Cause: Faults defined by the PLC expansion card.



Remedy:

  • View the PLC expansion card application program.


P-E2 to P-E10
PLC card customized faults

Cause: PLC card customized faults (2 through 10).



Remedy:

  • Figure out the cause of the fault (defined by PLC program).


E-Err
Repetitive expansion card type

Cause: The two inserted expansion cards are of the same type.



Remedy:

  • You should not insert two cards with the same type.

  • Check the type of expansion card, and remove one card after power-off.


ENCUV
Encoder UVW loss fault

Cause: No electric level variation occurred to UVW signal.



Remedy:

  • Check the wiring of UVW.

  • Encoder is damaged.


F1-Er
Failed to identify the expansion card in card slot 1

Cause: There is data transmission in interfaces of card slot 1, however, it cannot read the card type.



Remedy:

  • Confirm whether the expansion card inserted can be supported.

  • Stabilize the expansion card interfaces after power-off.

  • Check whether the insertion port is damaged.


F2-Er
Failed to identify the expansion card in card slot 2

Cause: There is data transmission in interfaces of card slot 2, however, it cannot read the card type.



Remedy:

  • Confirm whether the expansion card inserted can be supported.

  • Stabilize the expansion card interfaces after power-off.

  • Check whether the insertion port is damaged.


C1-Er
Communication timeout occurred to the expansion card in card slot 1

Cause: There is no data transmission in interfaces of card slot 1.



Remedy:

  • Confirm whether the expansion card inserted can be supported.

  • Stabilize the expansion card interfaces after power-off.

  • Check whether the insertion port is damaged.


C2-Er
Communication timeout occurred to the expansion card in card slot 2

Cause: There is no data transmission in interfaces of card slot 2.



Remedy:

  • Confirm whether the expansion card inserted can be supported.

  • Stabilize the expansion card interfaces after power-off.

  • Check whether the insertion port is damaged.


PoFF
System power failure

Cause: The system is powered off or the bus voltage is too low.



Remedy:

  • Check the grid conditions.


How to Clear & Reset INVT GD600 Series Drive Faults

  1. Keypad Reset: Press the red STOP/RST key on the local LCD operation panel of the tripped inverter unit or master rectifier module. Ensure running signals from the line controller are disengaged prior to resetting.
  2. Digital Input Reset (DI): If any control terminal (S1–S8 or HDI) on the unit’s I/O terminal board is programmed to function 7 (Fault reset) in parameter group P05.01 to P05.08, pulse the terminal contact to clear the trip.
  3. Industrial Fieldbus / PLC Reset: In automated continuous lines, clear trips through network control words (Profinet, EtherCAT, Modbus TCP/RTU) by sending control command 0007H to communication register address 2000H or pulsing Bit 7 in the fieldbus control word.
  4. Automatic Fault Reset: For transient network dips, configure parameter P08.28 (Fault reset times) and P08.29 (Fault reset interval) to allow the individual drive unit to automatically resume operation.
  5. Common DC Bus System Power Cycle: De-energize the main AC circuit breaker feeding the primary rectifier unit. Wait at least 15 minutes to allow the centralized capacitor banks across the common DC busbar to fully discharge before repowering.
⚠️ Extreme DC Bus Energy Safety Warning: Common DC bus multi-drive architectures interconnect substantial capacitive energy across shared busbars. Always isolate the primary AC input to the rectifier unit, disconnect any regenerative feedback sources, and verify with a calibrated digital multimeter that DC bus voltage across shared [(+)] and [(-)] busbars is strictly below 36VDC before removing book-type drive modules or touching output terminals U, V, and W.