INVT SPC Series Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT SPC Series solar pumping drive and MPPT controller. Search or filter through the complete fault code directory below.
Power Range
0.75 – 7.5 kW (1 – 10 HP)
Supply Voltage
PV DC (to 800V) / 220–440V AC
Control Modes
SVPWM & Sensorless Vector (SVC)
Operator Interface
LED Keypad / Optional GPRS & App
Complete INVT SPC Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OV1, A-nL, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OV1 Overvoltage during ACC | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OV2 Overvoltage during DEC | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OV3 Overvoltage during constant speed running | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OC1 Overcurrent during ACC | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| OC2 Overcurrent during DEC | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| OC3 Overcurrent during constant speed running | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| UV Bus undervoltage fault | Cause: The voltage of the grid is too low; The overvoltage stall protection is not enabled. Remedy:
|
| OL1 Motor overload | Cause: The grid voltage is too low; The motor rated current is set incorrectly; The motor stall occurs or the load transient is too large. Remedy:
|
| OL2 Inverter overload | Cause: The ACC is too fast; The rotating motor is reset; The grid voltage is too low; The load is too heavy; The motor power is too small. Remedy:
|
| SPO Phase loss on output side | Cause: Phase loss output occurs to U, V, W (or the three phases of the load are seriously asymmetrical). Remedy:
|
| OH2 Inverter module overheat | Cause: Air duct jam or fan damage occurs; Ambient temperature is too high; The time of overload running is too long. Remedy:
|
| EF External fault | Cause: SI external faulty input terminal action. Remedy:
|
| CE RS485 communication fault | Cause: The baud rate setting is incorrect; A fault occurs to the communication wiring; The communication address is incorrect; There is strong interference to the communication. Remedy:
|
| ItE Current detection fault | Cause: The control board connector is in poor contact; Hall device is damaged; An exception occurs on the magnifying circuit. Remedy:
|
| tE Motor autotuning fault | Cause: The motor capacity does not match the inverter capacity; Motor parameters are not set correctly; The difference between the parameters obtained from autotuning and the standard ones is great; Autotuning timed out. Remedy:
|
| EEP EEPROM operation error | Cause: Error in reading or writing control parameters; The EEPROM is damaged. Remedy:
|
| END Running time reached | Cause: The actual running time of the inverter is longer than the internal set running time. Remedy:
|
| OL3 Electronic overload fault | Cause: The inverter reports overload pre-alarm according to the setting. Remedy:
|
| ETH1 To-ground short-circuit fault 1 | Cause: The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit. Remedy:
|
| ETH2 To-ground short-circuit fault 2 | Cause: The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit. Remedy:
|
| dEu Speed deviation fault | Cause: The load is too heavy or stalled. Remedy:
|
| STo Mal-adjustment fault | Cause: SM control parameters are set incorrectly; Autotuned parameters are not accurate; The inverter is not connected to the motor. Remedy:
|
| LL Electronic underload fault | Cause: The inverter reports underload pre-alarm according to the setting. Remedy:
|
| A-LS Weak-light pre-alarm | Cause: The sunlight is weak or the PV module configuration is insufficient. Remedy:
|
| A-LL Underload pre-alarm | Cause: The pumping pool has no water. Remedy:
|
| A-tF Full-water pre-alarm | Cause: The pumping pool is full. Remedy:
|
| A-tL Empty-water pre-alarm | Cause: The pumping pool has no water. Remedy:
|
How to Clear & Reset INVT SPC Series Drive Faults
- Keypad Reset: Press the red STOP/RST key on the integrated front-panel keypad. In a fault state, this key directly clears active trip codes and resets the drive to ready status.
- Digital Input Reset (DI): If programmed in parameter group P05 (set to Function 4: Fault Reset), momentarily close the assigned digital input terminal (S1–S4 to COM) to clear the fault.
- Automatic Solar & Level Recovery: Operational warnings such as weak sunlight (A-nL) or water tank full / dry well protection automatically clear and self-recover once solar irradiance or water levels return to normal thresholds.
- Remote GPRS / Modbus Reset: If equipped with the optional GPRS module or connected via RS-485 Modbus RTU, send a reset control command to communication address 2000H.
- Power Cycle: Turn off both the DC solar isolator switch and the AC grid supply switch. Wait at least 5 minutes until the internal DC bus capacitors discharge completely and the LED display turns off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning:
Photovoltaic (PV) arrays generate hazardous DC voltages whenever exposed to sunlight. Always open the external DC disconnect switch and disconnect any AC mains supplies before opening covers or servicing wiring. Verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across main terminals (+) and (-) before touching PV input or motor output (U, V, W) terminals. Wait at least 5 minutes after disconnection for capacitors to discharge.