INVT SPC Series Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT SPC Series solar pumping drive and MPPT controller. Search or filter through the complete fault code directory below.

Dedicated Solar Pumping VFD Power: 0.75 to 7.5 kW (1.0 to 10 HP) Advanced MPPT & Dual AC/DC Input
Power Range 0.75 – 7.5 kW (1 – 10 HP)
Supply Voltage PV DC (to 800V) / 220–440V AC
Control Modes SVPWM & Sensorless Vector (SVC)
Operator Interface LED Keypad / Optional GPRS & App

Complete INVT SPC Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OV1, A-nL, or Overcurrent).

Fault Code and MeaningCause and Remedy
OV1
Overvoltage during ACC

Cause:
The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled.



Remedy:

  • Check the input power.

  • Check whether the loaded DEC time is too short or the inverter starts when the motor is rotating.

  • Install the braking components.

  • Check the setting of related function codes.


OV2
Overvoltage during DEC

Cause:
The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled.



Remedy:

  • Check the input power.

  • Check whether the loaded DEC time is too short or the inverter starts when the motor is rotating.

  • Install the braking components.

  • Check the setting of related function codes.


OV3
Overvoltage during constant speed running

Cause:
The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled.



Remedy:

  • Check the input power.

  • Check whether the loaded DEC time is too short or the inverter starts when the motor is rotating.

  • Install the braking components.

  • Check the setting of related function codes.


OC1
Overcurrent during ACC

Cause:
The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled.



Remedy:

  • Increase the ACC time.

  • Check the input power.

  • Select the inverter with larger power.

  • Check whether there is short circuit (to-ground or inter-wire) in the load or the rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.

  • Check the setting of related function codes.


OC2
Overcurrent during DEC

Cause:
The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled.



Remedy:

  • Increase the ACC time.

  • Check the input power.

  • Select the inverter with larger power.

  • Check whether there is short circuit (to-ground or inter-wire) in the load or the rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.

  • Check the setting of related function codes.


OC3
Overcurrent during constant speed running

Cause:
The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled.



Remedy:

  • Increase the ACC time.

  • Check the input power.

  • Select the inverter with larger power.

  • Check whether there is short circuit (to-ground or inter-wire) in the load or the rotation is not smooth.

  • Check the output wiring.

  • Check whether there is strong interference.

  • Check the setting of related function codes.


UV
Bus undervoltage fault

Cause:
The voltage of the grid is too low; The overvoltage stall protection is not enabled.



Remedy:

  • Check the grid input power supply.

  • Check the setting of related function codes.


OL1
Motor overload

Cause:
The grid voltage is too low; The motor rated current is set incorrectly; The motor stall occurs or the load transient is too large.



Remedy:

  • Check the grid voltage.

  • Reset the motor rated current.

  • Check the load and adjust the torque boost quantity.


OL2
Inverter overload

Cause:
The ACC is too fast; The rotating motor is reset; The grid voltage is too low; The load is too heavy; The motor power is too small.



Remedy:

  • Increase the ACC time.

  • Avoid the restarting after stop.

  • Check the grid voltage.

  • Select an inverter with larger power.

  • Select a proper motor.


SPO
Phase loss on output side

Cause:
Phase loss output occurs to U, V, W (or the three phases of the load are seriously asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cables.


OH2
Inverter module overheat

Cause:
Air duct jam or fan damage occurs; Ambient temperature is too high; The time of overload running is too long.



Remedy:

  • Dredge the vent duct or replace the fan.

  • Lower the ambient temperature.


EF
External fault

Cause:
SI external faulty input terminal action.



Remedy:

  • Check external device input.


CE
RS485 communication fault

Cause:
The baud rate setting is incorrect; A fault occurs to the communication wiring; The communication address is incorrect; There is strong interference to the communication.



Remedy:

  • Set a proper baud rate.

  • Check the communication interface wiring.

  • Set a proper communication address.

  • Change or replace the wire or improve the anti-interference capability.


ItE
Current detection fault

Cause:
The control board connector is in poor contact; Hall device is damaged; An exception occurs on the magnifying circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the Hall device.

  • Change the main control board.


tE
Motor autotuning fault

Cause:
The motor capacity does not match the inverter capacity; Motor parameters are not set correctly; The difference between the parameters obtained from autotuning and the standard ones is great; Autotuning timed out.



Remedy:

  • Change the inverter model.

  • Set the motor type and nameplate parameters correctly.

  • Empty the motor load.

  • Check the motor wiring and parameter settings.

  • Check whether the upper limit frequency is higher than 2/3 of the rated frequency.


EEP
EEPROM operation error

Cause:
Error in reading or writing control parameters; The EEPROM is damaged.



Remedy:

  • Press STOP/RST for reset.

  • Change the main control board.


END
Running time reached

Cause:
The actual running time of the inverter is longer than the internal set running time.



Remedy:

  • Ask for the supplier and adjust the set running time.


OL3
Electronic overload fault

Cause:
The inverter reports overload pre-alarm according to the setting.



Remedy:

  • Check the load and the overload pre-alarm points.


ETH1
To-ground short-circuit fault 1

Cause:
The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit.



Remedy:

  • Check whether the motor wiring is normal.

  • Replace the Hall device.

  • Change the main control board.


ETH2
To-ground short-circuit fault 2

Cause:
The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit.



Remedy:

  • Check whether the motor wiring is normal.

  • Replace the Hall device.

  • Change the main control board.


dEu
Speed deviation fault

Cause:
The load is too heavy or stalled.



Remedy:

  • Check the load and increase the detection time if the load is normal.

  • Check whether control parameters are set correctly.


STo
Mal-adjustment fault

Cause:
SM control parameters are set incorrectly; Autotuned parameters are not accurate; The inverter is not connected to the motor.



Remedy:

  • Check the load and ensure the load is normal.

  • Check whether control parameters are set correctly.

  • Increase the mal-adjustment detection time.


LL
Electronic underload fault

Cause:
The inverter reports underload pre-alarm according to the setting.



Remedy:

  • Check the load and the underload pre-alarm points.


A-LS
Weak-light pre-alarm

Cause:
The sunlight is weak or the PV module configuration is insufficient.



Remedy:

  • The device will automatically run when the light is sufficient.

  • Check whether the PV module configuration is sufficient.


A-LL
Underload pre-alarm

Cause:
The pumping pool has no water.



Remedy:

  • Check the pumping pool.


A-tF
Full-water pre-alarm

Cause:
The pumping pool is full.



Remedy:

  • If you have configured the full-water pre-alarm function, the device automatically stops when the pre-alarm elapsed a period of time.

  • Otherwise, check whether terminals are wired correctly.


A-tL
Empty-water pre-alarm

Cause:
The pumping pool has no water.



Remedy:

  • If you have configured the empty-water pre-alarm function, the device automatically stops when the pre-alarm elapsed a period of time.

  • Otherwise, check whether terminals are wired correctly.


How to Clear & Reset INVT SPC Series Drive Faults

  1. Keypad Reset: Press the red STOP/RST key on the integrated front-panel keypad. In a fault state, this key directly clears active trip codes and resets the drive to ready status.
  2. Digital Input Reset (DI): If programmed in parameter group P05 (set to Function 4: Fault Reset), momentarily close the assigned digital input terminal (S1–S4 to COM) to clear the fault.
  3. Automatic Solar & Level Recovery: Operational warnings such as weak sunlight (A-nL) or water tank full / dry well protection automatically clear and self-recover once solar irradiance or water levels return to normal thresholds.
  4. Remote GPRS / Modbus Reset: If equipped with the optional GPRS module or connected via RS-485 Modbus RTU, send a reset control command to communication address 2000H.
  5. Power Cycle: Turn off both the DC solar isolator switch and the AC grid supply switch. Wait at least 5 minutes until the internal DC bus capacitors discharge completely and the LED display turns off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Photovoltaic (PV) arrays generate hazardous DC voltages whenever exposed to sunlight. Always open the external DC disconnect switch and disconnect any AC mains supplies before opening covers or servicing wiring. Verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across main terminals (+) and (-) before touching PV input or motor output (U, V, W) terminals. Wait at least 5 minutes after disconnection for capacitors to discharge.