LS Electric G100 drive

Home / LS Electric / LS Electric G100 drive

LS Electric G100 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric G100 general purpose industrial drive series. Search or filter through the complete fault code directory below.

General Purpose AC Drive Power: 0.4 to 22 kW (0.5 to 30 HP) Sensorless Vector & V/f Control
Power Range 0.4 – 22 kW (0.5 – 30 HP)
Supply Voltage 200–240V / 380–480V AC
Control Modes V/F, Slip Comp, Sensorless Vector
Operator Interface Integrated 7-Segment LED Keypad

Complete LS Electric G100 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCT, OVT, or Overload).

Fault Code and MeaningCause and Remedy
OLT


Over Load

Displayed when the motor overload trip is activated and the actual load level exceeds the set level.

Cause:

  • The load is greater than the motor's rated capacity.

  • The set value for the overload trip level (Pr.21) is too low.




Remedy:

  • Replace the motor and inverter with models that have increased capacity.

  • Increase the set value for the overload trip level.


ULT


Under Load

Displayed when the motor underload trip is activated and the actual load level is less than the set level.

Cause:

  • There is a motor-load connection problem.

  • The set value for underload level (Pr.29, Pr.30) is less than the system's minimum load.




Remedy:

  • Replace the motor and inverter with models with lower capacity.

  • Reduce the set value for the underload level.


OCT


Over Current1

Displayed when inverter output current exceeds 200% of the rated current.

Cause:

  • Acc/Dec time is too short, compared to load inertia (GD2).

  • The inverter load is greater than the rated capacity.

  • The inverter supplied an output while the motor was idling.

  • The mechanical brake of the motor is operating too fast.

  • A ground fault has occurred in the inverter output wiring.

  • The motor insulation is damaged.




Remedy:

  • Increase Acc/Dec time.

  • Replace the inverter with a model that has increased capacity.

  • Operate the inverter after the motor has stopped or use the speed search function (Cn.60).

  • Check the mechanical brake.

  • Check the output wiring.

  • Replace the motor.


OVT


Over Voltage

Displayed when internal DC circuit voltage exceeds the specified value.

Cause:

  • Deceleration time is too short for the load inertia (GD2).

  • A generative load occurs at the inverter output.

  • The input voltage is too high.

  • A ground fault has occurred in the inverter output wiring.

  • The motor insulation is damaged.




Remedy:

  • Increase the deceleration time.

  • Use the braking unit.

  • Determine if the input voltage is above the specified value.

  • Check the output wiring.

  • Replace the motor.


LVT


Low Voltage

Displayed when internal DC circuit voltage is less than the specified value.

Cause:

  • The input voltage is too low.

  • A load greater than the power capacity is connected to the system (e.g., a welder, direct motor connection).

  • The magnetic contactor connected to the power source has a faulty connection.




Remedy:

  • Determine if the input voltage is below the specified value.

  • Increase the power capacity.

  • Replace the magnetic contactor.


LV2


Low Voltage 2

Displayed when internal DC circuit voltage is less than the specified value during inverter operation.

Cause:

  • The input voltage has decreased during operation.

  • An input open-phase has occurred when input voltage is low.

  • The magnetic contactor connected to the power source has a faulty connection.




Remedy:

  • Determine if the input voltage is below the specified value.

  • Check the input wiring.

  • Replace the magnetic contactor.


GFT


Ground Trip

Displayed when a ground fault trip occurs on the output side of the inverter.

Cause:

  • A ground fault has occurred in the inverter output wiring.

  • The motor insulation is damaged.




Remedy:

  • Check the output wiring.

  • Replace the motor.


ETH


E-Thermal

Displayed based on inverse time-limit thermal characteristics to prevent motor overheating.

Cause:

  • The motor has overheated.

  • The inverter load is greater than the rated capacity.

  • The set value for electronic thermal protection is too low.

  • The inverter has been operated at low speed for an extended duration.




Remedy:

  • Reduce the load or operation frequency.

  • Replace the inverter with a model that has increased capacity.

  • Set an appropriate electronic thermal prevention (ETH) level.

  • Replace the motor with a model that supplies extra power to the cooling fan.


POT


Out Phase Open

Displayed when a 3-phase inverter output has one or more phases in an open circuit condition.

Cause:

  • The magnetic contactor on the output side has a connection fault.

  • The output wiring is faulty.




Remedy:

  • Check the magnetic contactor on the output side.

  • Check the output wiring.


IPO


In Phase Open

Displayed when a 3-phase inverter input has one or more phases in an open circuit condition.

Cause:

  • The magnetic contactor on the input side has a connection fault.

  • The input wiring is faulty.

  • The DC link capacitor needs to be replaced.




Remedy:

  • Check the magnetic contactor on the input side.

  • Check the input wiring.

  • Replace the DC link capacitor (Contact retailer/service center).


IOLT


Inverter OLT

Displayed when the inverter has been protected from overload and resultant overheating.

Cause:

  • The load is greater than the rated motor capacity.

  • The torque boost level is too high.




Remedy:

  • Replace the motor and inverter with models that have increased capacity.

  • Reduce the torque boost level.


OHT


Over Heat

Displayed when the temperature of the inverter heat sink exceeds the specified value.

Cause:

  • There is a problem with the cooling system.

  • The inverter cooling fan has been operated for an extended period.

  • The ambient temperature is too high.




Remedy:

  • Determine if a foreign object is obstructing the air inlet, outlet, or vent.

  • Replace the cooling fan.

  • Keep the ambient temperature below 50°C.


OC2


Over Current2

Displayed when the DC circuit in the inverter detects a specified level of excessive, short circuit current.

Cause:

  • Output wiring is short-circuited.

  • There is a fault with the electronic semiconductor (IGBT).

  • A ground fault has occurred in the inverter output wiring.

  • The motor insulation is damaged.




Remedy:

  • Check the output wiring.

  • Do not operate the inverter. Contact the retailer or service center.

  • Check the output wiring.

  • Replace the motor.


NTC


NTC Open

Displayed when an error is detected in the temperature sensor of the Insulated Gate Bipolar Transistor (IGBT).

Cause:

  • The ambient temperature is too low.

  • There is a fault with the internal temperature sensor.




Remedy:

  • Keep the ambient temperature above –10°C.

  • Contact the retailer or the LSIS customer service center.


FAN


Fan Trip

Displayed when an error is detected in the cooling fan.

Cause:

  • A foreign object is obstructing the fan’s air vent.

  • The cooling fan needs to be replaced.




Remedy:

  • Remove the foreign object from the air inlet or outlet.

  • Replace the cooling fan.


How to Clear & Reset LS Electric G100 Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the front keypad when the trip code is flashing on the 7-segment display.
  2. Multi-Function Input Reset (P1–P5): Activate the configured digital terminal defined as “Reset” (configurable via input parameters IN-65 through IN-69 set to 4 / Reset).
  3. DriveView Software: Connect via the RJ45 communication port using an RS-485 to USB converter, launch DriveView 7 / 9 PC software, and click “Fault Reset” in the monitoring status window.
  4. Modbus RTU Communication: Write a reset bit command over RS-485 serial communication across terminals [S+] and [S-] to clear the active inverter trip condition.
  5. Power Cycle: Disconnect primary mains AC power, wait at least 5 minutes until the charge indicator LED turns off completely and internal DC bus capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus intermediate circuit voltage measures strictly below 30VDC across terminals [P1/+] and [N/-] (or motor output terminals U, V, and W) before inspecting wiring, removing terminal covers, or touching terminals on the LS Electric G100 drive.