LS Electric H100 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric H100 (LSLV-H100) HVAC, fan, and pump drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 500 kW (1 – 650 HP)
Supply Voltage
200–240V / 380–480V AC (3-Phase)
Control Modes
V/F Control (IM/PM) & Slip Comp.
Operator Interface
Hand-Off-Auto (HOA) LCD Keypad
Complete LS Electric H100 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Over Current, Over Voltage, or Inverter OLT).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
Over Load Displayed when the motor overload trip is activated and the actual load level exceeds the set level. Operates when PRT-20 is set to a value other than ‘0’. | Cause:
Remedy:
|
Under Load Displayed when the motor underload trip is activated and the actual load level is less than the set level. Operates when PRT-27 is set to a value other than ‘0’. | Cause:
Remedy:
|
Over Current1 Displayed when inverter output current exceeds 180% of the rated current. | Cause:
Remedy:
|
Over Voltage Displayed when internal DC circuit voltage exceeds the specified value. | Cause:
Remedy:
|
Low Voltage Displayed when internal DC circuit voltage is less than the specified value. | Cause:
Remedy:
|
Low Voltage2 Displayed when internal DC circuit voltage is less than the specified value during inverter operation. | Cause:
Remedy:
|
Ground Trip Displayed when a ground fault trip occurs on the output side of the inverter and causes the current to exceed the specified value. | Cause:
Remedy:
|
E-Thermal Displayed based on inverse time-limit thermal characteristics to prevent motor overheating. Operates when PRT-40 is set to a value other than ‘0’. | Cause:
Remedy:
|
Out Phase Open Displayed when a 3-phase inverter output has one or more phases in an open circuit condition. | Cause:
Remedy:
|
In Phase Open Displayed when a 3-phase inverter input has one or more phases in an open circuit condition. | Cause:
Remedy:
|
Inverter OLT Displayed when the inverter has been protected from overload and resultant overheating. (120% for 1 min, 140% for 5 sec). | Cause:
Remedy:
|
Over Heat Displayed when the temperature of the inverter heat sink exceeds the specified value. | Cause:
Remedy:
|
Over Current2 Displayed when the DC circuit in the inverter detects a specified level of excessive, short circuit current. | Cause:
Remedy:
|
NTC Open Displayed when an error is detected in the temperature sensor of the Insulated Gate Bipolar Transistor (IGBT). | Cause:
Remedy:
|
Fan Lock / In Fan Displayed when an error is detected in the cooling fan or an internal fan abnormality occurs (110kW-500kW). | Cause:
Remedy:
|
How to Clear & Reset LS Electric H100 Drive Faults
- Keypad Reset: Press the [STOP/RESET] or [OFF] button on the Hand-Off-Auto (HOA) keypad while viewing the fault screen to clear latching trips.
- Multi-Function Digital Input (DI): If configured in parameters IN-65 to IN-71 (terminals P1–P7) with option 17 (RST / Trip Reset), pulse the terminal closed with 24V common.
- DriveView 7 PC Tool: Connect your PC via the USB or RJ45 port, open LS DriveView software, and click the “Fault Reset” button in the live monitoring dashboard.
- Fieldbus / Building Network: Write a Fault Reset command bit over the embedded RS-485 Modbus-RTU, Metasys N2, or BACnet MS/TP automation network.
- Power Cycle: Disconnect the primary 3-phase AC input power, wait until the keypad LCD display and internal charge LED turn off completely (approx. 5–10 minutes for capacitor discharge), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [+DC / P] and [-DC / N] before inspecting motor cables, opening terminal covers, or touching terminals U, V, and W on the LS Electric H100 drive.