LS Electric iC5 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iC5 (SV-iC5) compact micro inverter series. Search or filter through the complete fault code directory below.

Compact Micro Inverter Power: 0.4 to 2.2 kW (0.5 to 3.0 HP) Sensorless Vector & V/F Control
Power Range 0.4 – 2.2 kW (0.5 – 3.0 HP)
Supply Voltage 200–230V AC (1-Phase Input)
Control Modes Sensorless Vector & V/F Control
Operator Interface Integrated LED Display & Pot.

Complete LS Electric iC5 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC, OV, OVT, or ETH).

Fault Code and MeaningCause and Remedy
OC
Overcurrent

Cause:


  • Accel/Decel time is too short compared to the GD² of the load.

  • Load is greater than the inverter rating.

  • Inverter output is issued when the motor is free running.

  • Output short circuit or ground fault has occurred.

  • Mechanical brake of the motor is operating too fast.




Remedy:


  • Increase the Accel/Decel time.

  • Replace the inverter with appropriate capacity.

  • Resume operation after stopping the motor or use H22 (Speed search) in Function group 2.

  • Check output wiring.

  • Check the mechanical brake.


GF
Ground fault current

Cause:


  • Ground fault has occurred at the output wiring of the inverter.

  • The insulation of the motor is damaged due to heat.




Remedy:


  • Check the wiring of the output terminal.

  • Replace the motor.


IOL
Inverter Overload

Cause:


  • Load is greater than the inverter rating.

  • Inverter capacity is incorrectly selected.

  • Torque boost scale is set too large.




Remedy:


  • Upgrade the capacity of motor and inverter or reduce the load weight.

  • Select correct inverter capacity.

  • Reduce torque boost scale.


OLT
Overload trip

Cause:

The inverter turns off its output if the output current flows at 150% of rated current for more than the current limit time (1 min).



Remedy:


  • Upgrade the capacity of motor and inverter or reduce the load weight.

  • Select correct inverter capacity.


OHT
Heat sink overheat

Cause:


  • Cooling system has faults.

  • An old cooling fan is not replaced with a new one.

  • Ambient temperature is too high.




Remedy:


  • Check for alien substances clogged in the heat sink.

  • Replace the old cooling fan with a new one.

  • Keep ambient temperature under 40°C.


COL
DC link capacitor overload

Cause:

The inverter has determined it is time to replace the old DC link capacitor.



Remedy:


  • Replace the DC link capacitor with a new one.


POT
Output Phase loss

Cause:


  • Faulty contact of magnetic switch at output.

  • Faulty output wiring.




Remedy:


  • Make connection of magnetic switch at output of the inverter securely.

  • Check output wiring.


OVT
Over voltage

Cause:


  • Decel time is too short compared to the GD² of the load.

  • Regenerative load is at the inverter output.

  • Line voltage is too high.




Remedy:


  • Increase the Decel time.

  • Use Dynamic Brake Unit.

  • Check whether line voltage exceeds its rating.


LVT
Low voltage

Cause:


  • Line voltage is low.

  • Load larger than line capacity is connected to line (ex: welding machine, motor with high starting current).

  • Faulty magnetic switch at the input side of the inverter.




Remedy:


  • Check whether line voltage is below its rating.

  • Check the incoming AC line. Adjust the line capacity corresponding to the load.

  • Change a magnetic switch.


ETH
Electronic Thermal

Cause:


  • Motor has overheated.

  • Load is greater than inverter rating.

  • ETH level is set too low.

  • Inverter capacity is incorrectly selected.

  • Inverter has been operated at low speed for too long.




Remedy:


  • Reduce load weight and operating duty.

  • Change inverter with higher capacity.

  • Adjust ETH level to an appropriate level.

  • Select correct inverter capacity.

  • Install a cooling fan with a separate power supply.


EEP
Parameter save error

Cause:

User-setting parameters failed to be entered into memory.



Remedy:


  • Contact your local LSIS sales representative.


H/W
Inverter hardware fault

Cause:

An error occurred in the control circuitry of the inverter.



Remedy:


  • Contact your local LSIS sales representative.


Err
Communication Error

Cause:

The inverter cannot communicate with the keypad.



Remedy:


  • Contact your local LSIS sales representative.


FAN
Cooling fan fault

Cause:


  • An alien substance is clogged in a ventilating slot.

  • Inverter has been in use without changing a cooling fan.




Remedy:


  • Check the ventilating slot and remove the clogged substances.

  • Replace the cooling fan.


EST
Instant cut off

Cause:

Used for emergency stop. The EST terminal has been turned on.



Remedy:


  • Turn off the EST terminal to return to regular operation.

  • Caution: The inverter starts regular operation if EST is turned off while FX or RX terminal is ON.


EtA
External fault A contact input

Cause:

The terminal set to "18 (External fault-A)" in I20-I24 group is ON.



Remedy:


  • Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input.


EtB
External fault B contact input

Cause:

The terminal set to "19 (External fault-B)" in I20-I24 group is ON.



Remedy:


  • Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input.


--L
Operating method lost

Cause:

No frequency command is applied to V1 and I when operation is set via Analog input.



Remedy:


  • Check the wiring of V1 and I and frequency reference level.


How to Clear & Reset LS Electric iC5 Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the integrated front keypad while the trip error code is displayed.
  2. Multi-Function Terminal Input (P1–P5): If programmed in I/O parameters I17 through I21 with option 3 (Reset), momentarily short the designated terminal (e.g., P3 or P4) to the CM common terminal.
  3. DriveView PC Software: Connect via the RJ45 Modbus-RTU RS485 port, open LS DriveView software, and send a Trip Reset command from the status monitor window.
  4. Modbus RTU Communication: Write a value of `0x0001` to the Reset command control register (`0x0382`) over the RS-485 serial link.
  5. Power Cycle: Turn off the single-phase AC main supply disconnect, wait at least 5 minutes until the 7-segment display and internal charging LED extinguish completely, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 30VDC across terminals [P1 / +] and [N / -] before opening wiring covers, servicing power leads, or touching motor terminals U, V, and W on the LS Electric iC5 drive.