LS Electric iS7 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iS7 (Starvert SV-iS7) high-performance drive series. Search or filter through the complete fault code directory below.

High Performance Industrial VFD Power: 0.75 to 375 kW (1.0 to 500 HP) Sensored & Sensorless Vector Control
Power Range 0.75 – 375 kW (1.0 – 500 HP)
Supply Voltage 200–230V / 380–480V (3-Phase)
Control Modes V/F, Sensorless & Sensored Vector, PM
Operator Interface Graphic LCD Keypad / 7-Segment

Complete LS Electric iS7 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Over Current1, Over Voltage, or Ground Trip).

Fault Code and MeaningCause and Remedy
Over Load

Warning Message

Cause: Motor is overloaded (Operates when PRT-17 is set to "1").


Remedy:

  • Select "4 (Over Load)" to operate.

  • Set the digital output terminal or relay (OUT31-33) to "4 (Over Load)" to receive overload warning output signals.


Under Load

Warning Message

Cause: Motor is underloaded (Operates when PRT-25 is set to "1").


Remedy:

  • Set the digital output terminal or relay (OUT31-33) to "6 (Under Load)" to receive underload warning output signals.


Inv Over Load

Warning Message

Cause: Accumulated overload time is equivalent to 60% of the inverter overheat protection (inverter IOLT) level.


Remedy:

  • Set the digital output terminal or relay (OUT31-33) to "5 (IOL)" to receive inverter overload warning output signals.


Lost Command

Warning Message

Cause: Lost Command warning alarm occurred based on condition set at PRT-13-15 (occurs even when PRT-12 is "0").


Remedy:

  • Set the digital output terminal or relay (OUT31-33) to "12 (Lost Command)" to receive lost command warning output signals.


Fan Warning

Warning Message

Cause: Error detected from the cooling fan while PRT-79 is set to "1".


Remedy:

  • Set the digital output terminal or relay (OUT31-33) to "8 (Fan Warning)" to receive fan warning output signals.


DB Warn %ED

Warning Message

Cause: DB resistor usage rate exceeds the set value.


Remedy:

  • Set the detection level at PRT-66.


Enc Conn Check

Warning Message

Cause: "3 (Enc Test)" is set at BAS-20 (Auto Tuning) and no signal is input during the encoder test.


Remedy:

  • Set the ENC Tune at OUT31–33 to release a signal.


Enc Dir Check

Warning Message

Cause: "3 (Enc Test)" is set at BAS-20 and settings for A and B encoder phases are changed or opposite during test.


Remedy:

  • Set the ENC Dir at OUT31-33 to release a signal.


Lost Keypad

Warning Message

Cause: Operating commands come from keypad or communication problem in Keypad JOG mode after setting PRT-11 to "0".


Remedy:

  • Set the Lost Keypad (29) at OUT31-33.


Check Line PLZ

Warning Message

Cause: Problem with communication between the keypad and the iS7 Control CPU (control connection cables).


Remedy:

  • Check control connection cables.


Fire Mode

Warning Message

Cause: Fire function is activated.


Remedy:

  • If a contact signal output is required, set the Fire Mode (37) at OUT31-33.


PID Sleep

Warning Message

Cause: Displayed in PID Sleep mode to distinguish from a stopped state.


Remedy:

  • Information only (Warning status).


AUX Power On

Warning Message

Cause: Control power is supplied with the auxiliary power module (replaces Low Voltage trip when main power is off).


Remedy:

  • Information only.


Over Load

Fault Trip


Cause: The load is greater than the motor's rated capacity.


Remedy:

  • Ensure that the motor and inverter have appropriate capacity ratings.




Cause: The set value for the overload trip level (PRT-21) is too low.


Remedy:

  • Increase the set value for the overload trip level.



Under Load

Fault Trip


Cause: There is a motor-load connection problem.


Remedy:

  • Replace the motor and inverter with lower capacity models.




Cause: The set value for the underload level (PRT-29 and PRT-30) is less than the system's minimum load.


Remedy:

  • Increase the set value for the underload level.



Over Current1

Fault Trip


Cause: Acc/dec time is too short compared to load inertia (GD2).


Remedy:
  • Increase acc/dec time.



Cause: The inverter load is greater than the rated capacity.


Remedy:
  • Replace the inverter with a model that has increased capacity.



Cause: The inverter supplied an output while the motor was idling.


Remedy:
  • Operate the inverter after the motor has stopped or use the speed search function (CON-60).



Cause: The mechanical brake of the motor is operating too fast.


Remedy:
  • Check the mechanical brake.


Over Voltage

Fault Trip


Cause: The deceleration time is too short for the load inertia (GD2).


Remedy:
  • Increase the deceleration time.



Cause: A generative load occurs at the inverter output.


Remedy:
  • Use the braking unit.



Cause: The input voltage is too high.


Remedy:
  • Check if the input voltage is above the specified value.


Low Voltage / Low Voltage2

Fault Trip


Cause: The input voltage is too low.


Remedy:
  • Check if the input voltage is below the specified value.



Cause: A load greater than the power capacity is connected to the system (e.g. a welder, direct motor connection).


Remedy:
  • Increase the power capacity.



Cause: The magnetic contactor connected to the power source has a faulty connection.


Remedy:
  • Replace the magnetic contactor.


Ground Trip

Fault Trip

Cause: A ground fault has occurred in the inverter output wiring.


Remedy:

  • Check the output wiring.


E-Thermal

Fault Trip


Cause: The set value for electronic thermal protection is too low.


Remedy:
  • Set an appropriate electronic thermal level.



Cause: The inverter has been operated at a low speed for an extended period.


Remedy:
  • Replace the motor with a model that supplies extra power to the cooling fan.



Cause: The motor insulation is damaged.


Remedy:
  • Replace the motor.



Cause: The motor has overheated.


Remedy:
  • Reduce the load or operation frequency.



Cause: The inverter load is greater than the rated capacity.


Remedy:
  • Replace the inverter with a model that has increased capacity.


Out Phase Open

Fault Trip


Cause: The magnetic contactor on the output side has a connection fault.


Remedy:
  • Check the magnetic contactor on the output side.



Cause: The output wiring is faulty.


Remedy:
  • Check the output wiring.


In Phase Open

Fault Trip


Cause: The magnetic contactor on the input side has a connection fault.


Remedy:
  • Check the magnetic contactor on the input side.



Cause: The input wiring is faulty.


Remedy:
  • Check the input wiring.



Cause: The DC link capacitor needs to be replaced.


Remedy:
  • Replace the DC link capacitor. Contact the retailer or LS ELECTRIC Customer Support.


Inverter OLT

Fault Trip


Cause: The load is greater than the rated motor capacity.


Remedy:
  • Replace the motor and inverter with models that have increased capacity.



Cause: The torque boost level is too high.


Remedy:
  • Reduce the torque boost level.


Over Heat

Fault Trip


Cause: There is a problem with the cooling system.


Remedy:
  • Check if a foreign object is obstructing the air inlet, outlet, or vent.



Cause: The inverter cooling fan has been operating for an extended period.


Remedy:
  • Replace the cooling fan.



Cause: The ambient temperature is too high.


Remedy:
  • Keep the ambient temperature below 50°C.


Over Current2

Fault Trip


Cause: The output wiring has short-circuited.


Remedy:
  • Check the output wiring.



Cause: There is a fault with the electronic semiconductor (IGBT).


Remedy:
  • Do not operate the inverter. Contact the retailer or LS ELECTRIC Customer Support.


NTC Open

Fault Trip


Cause: The ambient temperature is too low.


Remedy:
  • Keep the ambient temperature above 10°C.



Cause: There is a fault with the internal temperature sensor.


Remedy:
  • Contact the retailer or LS ELECTRIC Customer Support.


FAN Trip

Fault Trip


Cause: There is a foreign object in the inverter vent where the fan is located.


Remedy:
  • Remove the foreign object from the air inlet or outlet.



Cause: The cooling fan needs to be replaced.


Remedy:
  • Replace the cooling fan.


IP54 FAN Trip

Fault Trip


Cause: The fan connector is not connected.


Remedy:
  • Connect the fan connector.



Cause: The power connector for the internal fan PCB board is not connected.


Remedy:
  • Connect the power connector for the internal fan PCB board.



Cause: The cooling fan needs to be replaced.


Remedy:
  • Replace the cooling fan.


No Motor Trip

Fault Trip


Cause: The motor is not connected to the inverter output.


Remedy:
  • Check the wiring connections.



Cause: The current level for trip detection is not set properly.


Remedy:
  • Check the values of both BAS-13 (Rated current) and PRT-32 (No Motor Level).


How to Clear & Reset LS Electric iS7 Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the graphic LCD keypad or standard console display while the active fault information is shown.
  2. Multi-Function Input Reset (P1–P8): Trigger the terminal assigned to the “Reset” function (programmable via input parameters IN-65 through IN-72 set to 4 / Reset).
  3. DriveView Software: Connect your PC via the RS-485 Modbus terminal or loader interface, launch DriveView 7 / 9, and click “Fault Reset” in the main monitor window.
  4. Fieldbus / Network Reset: Write a reset command bit across your network protocol (Profibus-DP, Ethernet/IP, Modbus-TCP, or CANopen) via the communication control word.
  5. Power Cycle: Disconnect the incoming 3-phase AC supply line, wait at least 10 minutes until the charging indicator lamp turns off completely and the internal DC bus discharges, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus intermediate circuit voltage measures strictly below 30VDC across terminals [P1/+] and [N/-] (or motor output terminals U, V, and W) before inspecting motor leads, opening terminal covers, or touching wiring terminals on the LS Electric iS7 drive.