LS Electric iV5 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iV5 high-precision vector control and elevator drive series. Search or filter through the complete fault code directory below.
Power Range
2.2 – 500 kW (3 – 670 HP)
Supply Voltage
3-Phase 200–230V / 380–480V
Control Modes
Sensored Vector, Sensorless, V/f
Operator Interface
32-Character LCD Loader Keypad
Complete LS Electric iV5 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Over Current, Speed Dev Trip, or Enc Trip).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Over Current Over Current Protection | Cause: The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter rated current. Remedy: Check for short circuits, excessive load, or motor insulation failure. |
| Ground Fault Ground Fault Protection | Cause: A ground fault occurred and the current exceeded the internal setting value. This can occur due to low ground fault resistance. Remedy: Check output cabling and motor insulation for ground faults. |
| Over Voltage Over voltage protection | Cause: DC voltage of the main circuit increased higher than the rated value (200V class: 400V DC, 400V class: 820 V DC). This often happens when the motor decelerates (regenerative energy) or due to a surge voltage in the power supply. Remedy: Check input power for surges; consider increasing deceleration time or using a braking resistor. |
| Low Voltage Low Voltage Protection | Cause: DC voltage dropped below the detection level (200V class: 180Vdc, 400V class: 360Vdc). Insufficient torque or motor overheating can occur if input voltage drops. Remedy: Check input power supply voltage and wiring connections. |
| Over Load Overload Protection | Cause: The output current flowed at 180% of the inverter rated current for more than the current limit time (S/W). Remedy: Reduce load; check motor capacity matches inverter capacity. |
| Inv OLT Inverter Overload | Cause: The rated current of the inverter flowed more than regulation level (150% for 1 minute; inversely proportional to time). Remedy: Check load rating and duty cycle. |
| InvOver Heat Heat Sink Over Heat | Cause: The heat sink overheated due to a damaged cooling fan or foreign substance in the cooling fan (detected by heat sink temperature). Remedy: Check cooling fan for damage or blockages; clean heat sink. |
| OHD Open Heat Sink Over Heat (OHD) | Cause: OHD is opened and the heat sink is overheated. (Note: Only applies to SV2800 ~ 3750iV5). Remedy: Check thermal sensor continuity and cooling system. |
| InvThem OP Inverter NTC Thermistor Open | Cause: The inverter NTC Thermistor is open. Remedy: Contact service/support; internal hardware check required. |
| MotOver Heat Motor overheat | Cause: Motor temperature exceeded 150°C. Output stopped to protect motor. Remedy: Check motor cooling, load factor, and operating environment. |
| MotThem Err Motor Thermistor Error | Cause: Error in the Thermistor that measures motor temperature (e.g., NTC open). Remedy: Check motor thermistor wiring and sensor health. |
| E-Thermal Electronic Thermal | Cause: Internal electronic thermal calculation determined motor overheating. Overload capacity: 150% for 1 min. Note: Inverter cannot protect multi-pole or multiple motors effectively with this function alone. Remedy: If driving multiple motors, consider installing external thermal relays for each motor. |
| External-B External fault B | Cause: User triggered the external fault signal to turn off output. Remedy: Check external input source/switch assigned to External Fault B. |
| Arm Short / Arm Short-DB IGBT Short | Cause: Inverter output stopped because IGBT Arm short or output short occurred. (Arm Short-DB applies to SV110~220iV5). Remedy: Check output wiring for shorts; internal IGBT may be damaged. |
| Fuse Open Fuse Open | Cause: Fuse opened to protect wiring from short currents (usually implies main circuit IGBT issue). Remedy: Do not replace fuse immediately; check main circuit IGBT and wiring for shorts. |
| Encoder Err Encoder Error | Cause: 1) Encoder signal fault occurred (Hardware). 2) Discord of detection time standard of motor error of PAR-14 (Software). Remedy: Check encoder wiring, power, and PAR-14 settings. |
| BX BX protection (Instant Cut Off) | Cause: Used for emergency stop. Output turns off instantly when BX terminal is ON. Returns to operation when BX is OFF. Remedy: Check status of the BX terminal input. Take caution when using this function. |
| Over Speed Motor overspeed | Cause: Motor is rotating over 120% of its rated speed. Remedy: Check load inertia, brake settings, and speed command parameters. |
| COM Error / CPU Error Communication Error | Cause: Inverter cannot communicate with the keypad. Remedy: Check keypad connection cable and seating. |
| HW- Diag H/W Error | Cause: CPU has a problem; inverter blocks IGBT gating signals. Remedy: Cycle power. If fault persists, contact service (CPU/Control board failure). |
| FAN Lock FAN Lock | Cause: The inverter detected a Fan Lock condition. (Only comes under SV2800~3750iV5). Remedy: Inspect cooling fans for debris or mechanical failure. |
| Enc Power Encoder PowerError | Cause: Error in Encoder power source. (Only comes under SV2800~3750iV5). Remedy: Check encoder power supply voltage and wiring. |
| Input PO Input Phase-open | Cause: Power from one phase among the 3-phase input is discontinued at normal load state. Remedy: Check input power lines, fuses, and circuit breakers. |
| Output PO Output Phase-open | Cause: Inverter detected no-output current (open phase on output). Remedy: Check motor wiring and motor windings for continuity. |
| FAN/MC PWR AC FAN and M/C Power Error | Cause: AC220V is not supplied to AC FAN and M/C. (Applicable to 30 ~ 160 kW). Remedy: Check auxiliary AC220V power supply to fans and magnetic contactors. |
| FAN PWR AC FAN Power Error | Cause: AC220V is not supplied to AC FAN and M/C. Remedy: Check auxiliary AC power supply. |
How to Clear & Reset LS Electric iV5 Drive Faults
- Keypad Reset: Press the red [STOP/RESET] key on the 32-character LCD loader keypad once the root cause of the trip is investigated and resolved.
- Multi-Function Input Reset: Apply a momentary signal to any assigned digital input terminal (e.g., P1 to P6 / M1 to M8 depending on the installed I/O board) programmed to RST (Fault Reset).
- DriveView Software: Connect via RS-485 serial communication using LS Electric DriveView PC software, navigate to the diagnostic/monitor page, and click Fault Reset.
- Fieldbus Control Word: Set the fault reset bit in the control word via optional communication modules (Profibus-DP, DeviceNet, Modbus-RTU, or CANopen).
- Power Cycle: Disconnect main 3-phase AC power lines, wait until the LCD loader and internal DC charging lamp are completely extinguished (approx. 5–10 minutes), then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning:
Extremely dangerous residual voltages remain stored in the DC bus capacitors after power disconnection. Always wait at least 5 to 10 minutes and verify using a calibrated digital multimeter that the DC bus voltage measures strictly below 30VDC across terminals [P+] and [N-] before servicing terminal connections, encoder boards, or motor wiring U, V, and W on the LS Electric iV5 drive.