LS Electric S100 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric S100 high-performance standard drive series. Search or filter through the complete fault code directory below.

Standard High-Performance AC Drive Power: 0.4 to 75 kW (0.5 to 100 HP) Built-in Safe Torque Off (STO SIL2 / PL d)
Power Range 0.4 – 75 kW (0.5 – 100 HP)
Supply Voltage 1-Phase 200V / 3-Phase 200–480V
Control Modes V/f, Slip Comp., Sensorless Vector
Operator Interface 7-Segment LED / Optional LCD Loader

Complete LS Electric S100 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCT, OVT, or Ground Fault).

Fault Code and MeaningCause and Remedy
OLt

Over Load (Latch)

Cause:

Displayed when the motor overload trip is activated and the actual load level exceeds the set level.



Remedy:

Check motor load and capacity. Operates when Pr.20 is set to a value other than 0.
ULt

Under Load (Latch)

Cause:

Displayed when the motor underload trip is activated and the actual load level is less than the set level.



Remedy:

Check for broken belts or pump dry run. Operates when Pr.27 is set to a value other than 0.
OCt

Over Current1 (Latch)

Cause:

Displayed when inverter output current exceeds 200% of the rated current.



Remedy:

Check for short circuits or motor insulation failure.
OVt

Over Voltage (Latch)

Cause:

Displayed when internal DC circuit voltage exceeds the specified value.



Remedy:

Check input voltage and deceleration time.
LVt

Low Voltage (Level)

Cause:

Displayed when internal DC circuit voltage is less than the specified value.



Remedy:

Check input power supply voltage.
LV2

Low Voltage2 (Latch)

Cause:

Displayed when internal DC circuit voltage is less than the specified value during inverter operation.



Remedy:

Check for power fluctuations during operation.
GFt

Ground Trip (Latch)

Cause:

Displayed when a ground fault trip occurs on the output side of the inverter and causes the current to exceed the specified value.



Remedy:

Check motor and cabling for ground faults. (Note: S100 inverters 4.0kW or less do not support GFT; they may show OCT or OVT instead).
EtH

E-Thermal (Latch)

Cause:

Displayed based on inverse time-limit thermal characteristics to prevent motor overheating.



Remedy:

Check motor load and cooling. Operates when Pr.40 is set to a value other than 0.
POt

Out Phase Open (Latch)

Cause:

Displayed when a 3-phase inverter output has one or more phases in an open circuit condition.



Remedy:

Check output wiring. Operates when bit 1 of Pr.05 is set to 1.
IPO

In Phase Open (Latch)

Cause:

Displayed when a 3-phase inverter input has one or more phases in an open circuit condition.



Remedy:

Check input wiring and fuses. Operates only when bit 2 of Pr.05 is set to 1.
IOL

Inverter OLT (Latch)

Cause:

Displayed when the inverter has been protected from overload and resultant overheating (150% for 1 min, 200% for 4 sec).



Remedy:

Check load duty cycle and inverter capacity.
ntH

No Motor Trip (Latch)

Cause:

Displayed when the motor is not connected during inverter operation.



Remedy:

Check motor connection. Operates when Pr.31 is set to 1.
OHt

Over Heat (Latch)

Cause:

Displayed when the temperature of the inverter heat sink exceeds the specified value.



Remedy:

Check cooling fan and ambient temperature.
OC2

Over Current2 (Latch)

Cause:

Displayed when the DC circuit in the inverter detects a specified level of excessive, short circuit current.



Remedy:

Check for short circuit in the motor or internal DC circuit issues.
EHt

External Trip (Latch)

Cause:

Displayed when an external fault signal is provided by the multi-function terminal.



Remedy:

Check external device status. Requires multi-function input terminals at In.65-71 set to 4.
bX

BX (Level)

Cause:

Displayed when the inverter output is blocked by a signal provided from the multi-function terminal.



Remedy:

Check input signal status. Requires multi-function input terminals at In.65-71 set to 5.
HWt

H/W-Diag (Fatal)

Cause:

Displayed when an error is detected in memory (EEPROM), ADC Offset, or CPU watchdog.



Remedy:

Fatal Error. Power cycle the unit. If error persists, contact LS ELECTRIC customer service.
ntC

NTC Open (Latch)

Cause:

Displayed when an error is detected in the temperature sensor of the Insulated Gate Bipolar Transistor (IGBT).



Remedy:

Contact service center.
FAn

Fan Trip (Latch)

Cause:

Displayed when an error is detected in the cooling fan.



Remedy:

Check or replace cooling fan. (Set Pr.79 to 0 to activate fan trip for models below 22kW).
PId

Pre-PID Fail (Latch)

Cause:

PID feedback is below set value and low feedback continues (treated as load fault).



Remedy:

Check PID feedback loop and system pressure/flow. Operates with functions set at AP.34–AP.36.
Hbr

Ext-Brake (Latch)

Cause:

Occurs when the inverter output starting current remains below the set value at Ad.41.



Remedy:

Check external brake settings. Set either OU.31 or OU.32 to 35 (BR Control).
SFA / SFb

Safety A(B) Err (Latch)

Cause:

Displayed when at least one of the two safety input signals is off.



Remedy:

Check safety input wiring and switches.
PtCt

PTC Trip (Latch)

Cause:

Displayed when a PTC error is detected, PTC value is exceeded, or a fault occurs.



Remedy:

Check motor PTC sensor and wiring.
LOr

Lost Command (Level)

Cause:

Frequency or operation command error detected during remote operation (not keypad).



Remedy:

Check communication lines. Activate by setting Pr.12 to any value other than 0.
IOt

IO Board Trip (Latch)

Cause:

I/O board or external communication card is not connected or has a bad connection.



Remedy:

Check connection of the option card.
ErrC

Error Code

Cause:

Displayed when an error code continues for more than 5 seconds.



Remedy:

Check specific error sequence displayed.
PAr

ParaWrite Trip (Latch)

Cause:

Communication fails during parameter writing (LCD keypad usage).



Remedy:

Check control cable connection between keypad and inverter.
OPt

Option Trip-1 (Latch)

Cause:

Communication error detected between the inverter and the communication board.



Remedy:

Check installation of communication option card.
OLW

Over Load Warning

Cause:

Displayed when the motor is overloaded.



Remedy:

Operates when Pr.17 is set to 1. Output available via terminal (OU.31/OU.33 set to 5).
ULW

Under Load Warning

Cause:

Displayed when the motor is underloaded.



Remedy:

Operates when Pr.25 is set to 1. Output available via terminal (OU.31/OU.33 set to 7).
IOLW

INV Over Load Warning

Cause:

Displayed when overload time equivalent to 60% of inverter overheat protection level is accumulated.



Remedy:

Reduce load. Output available via terminal (OU.31/OU.33 set to 6).
LCW

Lost Command Warning

Cause:

Lost command warning alarm occurs based on condition set at Pr.13-15.



Remedy:

Check comms. Even if Pr.12 is 0, this warning can occur via digital output (OU.31/OU.33 set to 13).
FAnW

Fan Warning

Cause:

Displayed when an error is detected from the cooling fan while Pr.79 is set to 1.



Remedy:

Check fan. Warning signal available via digital output (OU.31/OU.33 set to 8).
EFAn

Fan Exchange

Cause:

Alarm occurs when the fan life value (Pr.86) is less than the value set at Pr.87.



Remedy:

Replace fan. Warning signal available via digital output (OU.31/OU.33 set to 37).
dbW

DB Warn %ED

Cause:

Displayed when the DB resistor usage rate exceeds the set value.



Remedy:

Check DB resistor sizing. Set detection level at Pr.66.
trEr

Retry Tr Tune

Cause:

Tr tune error warning alarm is activated when motor's rotor time constant (Tr) is too low or high.



Remedy:

Check motor parameters. Activated when dr.9 is set to 4.
SLP

PID Sleep

Cause:

When the PID operation enters sleep mode, a warning occurs.



Remedy:

Normal operation status during PID sleep.

How to Clear & Reset LS Electric S100 Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the integrated 7-segment LED keypad or optional LCD loader once the underlying fault cause has been removed.
  2. Terminal Reset (Multi-Function Input): Apply a momentary signal to any multi-function digital input terminal (P1 to P7) assigned to code 17 (RST / Fault Reset) in parameter group In.65–In.71.
  3. DriveView Software: Connect a PC to the drive RJ45 / USB port using LS Electric DriveView 7 / DriveView 9 software, open the monitoring window, and execute a Fault Reset command.
  4. Communication Control (Modbus RTU / Fieldbus): Write the reset command bit to the drive communication control word via RS-485 terminals (S+, S-) or optional fieldbus boards (Profibus-DP, Ethernet/IP, CANopen).
  5. Power Cycle: Disconnect the incoming 3-phase/1-phase AC power lines, wait until the keypad display and internal charge LED turn completely off (at least 5–10 minutes), then reapply mains power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous DC link residual voltage remains present after power disconnect. Wait a minimum of 5 to 10 minutes and verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [P1 / P+] and [N / N-] before inspecting terminal connections or motor leads U, V, and W on the LS Electric S100 drive.