Mitsubishi FR-B3-N(H) 400 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi FR-B3-N(H) 400 explosion-proof motor driving inverter. Search or filter through the complete fault code directory below.
Rated Capacity
0.4 kW / 400W (0.5 HP)
Supply Voltage
380–480V AC (3-Phase, 400V Class)
Control Modes
Advanced Magnetic Flux Vector Control
Operator Interface
FR-DU04 / FR-PU04 Operation Panel
Complete Mitsubishi FR-B3-N(H) 400 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or E.THM).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
E.OC1 Overcurrent shut-off during acceleration | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during acceleration. Check points: Check for sudden acceleration, output short circuit, or if main circuit power (R, S, T) is supplied. Remedy:
|
E.OC2 Overcurrent shut-off during constant speed | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during constant speed. Check points: Check for sudden load change or output short circuit. Remedy:
|
E.OC3 Overcurrent shut-off during deceleration | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during deceleration. Check points: Check for sudden speed reduction, output short circuit, or too fast operation of motor's mechanical brake. Remedy:
|
E.OV1 Regenerative overvoltage shut-off during acceleration | Cause: Regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value. It may also be activated by a surge voltage generated in the power supply system. Check points: Check for too slow acceleration. Remedy:
|
E.OV2 Regenerative overvoltage shut-off during constant speed | Cause: Regenerative energy causes internal main circuit DC voltage to exceed specified value (or surge voltage). Check points: Check for sudden load change. Remedy:
|
E.OV3 Regenerative overvoltage shut-off during deceleration or stop | Cause: Regenerative energy causes internal main circuit DC voltage to exceed specified value (or surge voltage). Check points: Check for sudden speed reduction. Remedy:
|
E.THM Motor overload shut-off (electronic overcurrent protection) | Cause: Motor overheat due to overload or reduced cooling capability during constant-speed operation. (Pre-alarm occurs at 85% of preset value). Check points: Check the motor for use under overload. Remedy:
|
E.THT Inverter overload shut-off (electronic overcurrent protection) | Cause: Current of more than 150% of the rated output current flows. Inverse-time characteristics activate protection to protect output transistors. Check points: Check the motor for use under overload. Remedy:
|
E.IPF Instantaneous power failure protection | Cause: A power failure occurred for longer than 15ms. Check points: Find the cause of instantaneous power failure occurrence. Remedy:
|
| E.UVT Undervoltage protection | Cause: Power supply voltage reduces below 150V (about 300V for the 400V class). Large-capacity motor start causing voltage dip. Jumper not connected across P-P1. Remedy:
|
| E.FIN Fin overheat | Cause: Cooling fin overheats (sensor actuated). Too high ambient temperature or cooling fin clogging. Remedy:
|
| E.GF Output side ground fault overcurrent protection | Cause: Ground fault overcurrent flows due to a ground fault in the inverter's output side (load side). Check for ground fault in motor or connection cable. Remedy:
|
| E.OHT OH Fault (External thermal relay operation) | Cause: External thermal relay or internal motor temperature relay switched on (contacts open). Motor overheating. Incorrect setting of Pr. 180 to Pr. 186. Remedy:
|
| E.BE Br. Cct. Fault (Brake transistor alarm detection) | Cause: Brake circuit fault due to damaged brake transistors. Load GD² is too high or improper braking usage frequency. Remedy:
|
| E.OLT Stall prevention (Still Prev STP) | Cause: Running frequency fell to 0 because stall prevention was activated. Motor used under overload. Remedy:
|
| E.OPT Option Fault | Cause: Dedicated option setting error or connection fault. High power factor converter connection set but AC power supplied to R, S, T. Loose connector. Remedy:
|
| E.OP1 to OP3 Option slot alarm 1 to 3 | Cause: Functional alarm in the plug-in option (e.g. communication alarm). Wrong option function setting or operation. Remedy:
|
| E.PE Corrupt Memory (Parameter storage device alarm) | Cause: Fault in the E²PROM device. Too many parameter write times. Remedy:
|
| E.PUE PU Leave Out (Parameter unit disconnection) | Cause: Communication between inverter and PU suspended/disconnected. Loose fitting of DU or PU. Pr. 75 setting issue. Remedy:
|
| E.RET Retry No Over (Retry count exceeded) | Cause: Operation could not be resumed within the set number of retries. Remedy:
|
| E.LF Output phase failure protection | Cause: One of the three phases (U, V, W) on the output side is open. Rated motor current is extremely lower than rated inverter current. Loose wiring. Remedy:
|
| E.CPU CPU Fault | Cause: Arithmetic operation of the built-in CPU does not end within a predetermined period. Remedy:
|
| E.6 / E.7 Fault 6 / Fault 7 (CPU error) | Cause: Arithmetic operation of peripheral circuit failed or receive data error in built-in CPU. Loose connector. Remedy:
|
| E.P24 24VDC power output short circuit | Cause: Check for a short circuit in the PC terminal output. Remedy: Remedy the short circuit portion. |
| E.CTE Operation panel power supply short circuit | Cause: Check for a short circuit in the PU connector cable. Remedy: Check the PU and cable. |
| E.MB1 to 7 Brake sequence error | Cause: Find the cause of alarm occurrence. Remedy: Perform parameter setting check and wiring properly. |
| FN Fan fault | Cause: Check the cooling fan for a fault. Remedy: Change the fan. |
| OL Stall prevention (Over current) | Cause: Check the motor for use under overload. Remedy: The acceleration time may change. Increase the stall prevention operation level using Pr. 22 "stall prevention operation level" or make the stall prevention inoperative using Pr. 156 "stall prevention operation selection". |
| oL Stall prevention (overvoltage) | Cause: Check for sudden speed reduction. Remedy: The deceleration time may change. Increase the deceleration time using Pr. 8 "deceleration time". |
| PS PU stop | Cause: Check for a stop made by pressing the STOP key of the operation panel. Remedy: Refer to page 98. |
| Err. Operation Error | Cause: This alarm appears if:
Remedy: Perform operation correctly. |
How to Clear & Reset Mitsubishi FR-B3-N(H) 400 Drive Faults
- Keypad Reset: Press the STOP / RESET key on the operation panel (FR-DU04) or parameter unit (FR-PU04). Keypad fault reset is active only while the inverter is in an active trip state.
- Digital Input Reset (RES Terminal): Apply a reset signal across control terminal RES and common terminal SD (for sink logic) or PC (for source logic) for at least 0.1 seconds, then turn it OFF. Note: Resetting while the drive is operating will cause the motor to coast to stop.
- PU / RS-485 Communication: Connect via the RJ-45 PU communication connector on the front unit using a dedicated communication converter cable, and issue an Inverter Reset / Fault Clear command using the Mitsubishi computer link protocol.
- Network Option Cards: Assert the Inverter Reset Bit or write reset command code
H9696via optional fieldbus cards such as CC-Link (FR-A5NC) or Profibus-DP (FR-A5NP). - Power Cycle: Switch OFF the main circuit power supply breaker (terminals R/L1, S/L2, T/L3). Wait until the red CHARGE lamp turns off completely (approx. 10 minutes), then switch power back ON.
⚠️ High-Voltage & Explosion-Proof Safety Warning:
Always verify that the red CHARGE lamp on the unit is completely extinguished, and use a calibrated digital multimeter to confirm that intermediate DC bus voltage across terminals [P/+] and [N/-] is strictly below 30V DC before touching motor cables or wiring terminals U, V, and W. Never bypass motor thermal overload protection parameters (Pr. 9) or offline auto-tuning settings, as doing so may violate explosion-proof operating certifications in hazardous areas.