Mitsubishi FR-CS80 drive

Home / Mitsubishi / Mitsubishi FR-CS80 drive

Mitsubishi FR-CS80 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, protective trip explanations, root causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-CS80 compact micro inverter series.

Compact Micro Inverter Power: 0.1 to 15 kW (1/8 to 20 HP) Advanced Magnetic Flux Vector Control
Power Range 0.1 – 15 kW (1/8 – 20 HP)
Supply Voltage 1-Ph 200V / 3-Ph 200–240V / 380–480V
Control Modes V/F & Adv. Magnetic Flux Vector
Operator Interface Integrated 4-Digit Display & M Dial

Complete Mitsubishi FR-CS80 Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).

Fault Code and MeaningCause and Remedy
HOLD
Operation panel lock

Cause: Operation lock is set. Operation other than STOP/RESET is invalid.


Remedy:

  • Press MODE for 2 seconds to release the lock.


LOCD
Parameter locked

Cause: Password function is active. Display and setting of parameters are restricted.


Remedy:

  • Enter the password in Pr.297 (Password lock/unlock) to unlock the password function before the operation.


Er1
Write disable error

Cause:
Parameter setting was attempted while Pr.77 is set to disable write, or overlapping ranges set for frequency jump/adjustable 5 points V/F. The PU and inverter may not be communicating normally.


Remedy:

  • Check the Pr.77 Parameter write selection setting.

  • Check the settings of Pr.31 to Pr.36 (frequency jump).

  • Check the settings of Pr.100 to Pr.105 (adjustable 3 points V/F).

  • Check the connection of the PU and the inverter.


Er2
Write error during operation

Cause: Parameter write was attempted while Pr.77 Parameter write selection = "0".


Remedy:

  • Check that the inverter is stopped.

  • After stopping the operation, make parameter setting.

  • When setting Pr.77 = "2", parameter write is enabled during operation.


Er3
Calibration error

Cause: Analog input bias and gain calibration values are set too close.


Remedy:

  • Check the settings of the calibration parameters C3, C4, C6, and C7 (calibration functions).


Er4
Mode designation error

Cause:
Parameter setting is attempted in the External or NET operation mode when Pr.77 = "1", or when the command source is not at the operation panel.


Remedy:

  • Check that operation mode is PU operation mode.

  • Check that the Pr.551 PU mode operation command source selection setting is correct.

  • After setting the operation mode to the "PU operation mode", set the parameter.

  • When Pr.77 = "2", parameter write is enabled regardless of the operation mode.


Err.
(Error)

Cause: The RES signal is turned ON, or voltage at the input side of the inverter has dropped.


Remedy:

  • Turn OFF the RES signal.

  • Check the voltage on the input side of the inverter.


OLC (FR-LU08: OL)
Stall prevention (overcurrent)

Cause:
When the output current of the inverter increases, the stall prevention function is activated. This stops the increase (during accel) or decreases frequency (during constant speed/decel) to prevent an overcurrent trip.


Remedy:

  • Check that the Pr.0 Torque boost setting is not too large.

  • Check if Pr.7 Acceleration time and Pr.8 Deceleration time settings are too short.

  • Check that the load is not too heavy.

  • Check for any failures in peripheral devices.

  • Check that Pr.13 Starting frequency is not too large.

  • Check that Pr.22 Stall prevention operation level is appropriate.

  • Set a larger value in Pr.7 and Pr.8.

  • Reduce the load or try General-purpose magnetic flux vector control.


OLV (FR-LU08: oL)
Stall prevention (overvoltage)

Cause:
When the output voltage increases, the stall prevention function is activated. The regeneration avoidance function may be activated due to excessive regenerative power.


Remedy:

  • Check for sudden speed reduction.

  • Check if the regeneration avoidance function (Pr.882, Pr.883, etc.) is enabled.

  • Increase the deceleration time using Pr.8 Deceleration time.


TH
Electronic thermal O/L relay pre-alarm

Cause:
Appears if the cumulative value of the electronic thermal O/L relay reaches 85% of the preset level of Pr.9.


Remedy:

  • Check for large load or sudden acceleration.

  • Check that the Pr.9 setting is appropriate.

  • Reduce the load and frequency of operation.

  • Set an appropriate value in Pr.9.


PS
PU stop

Cause:
The motor is stopped using STOP/RESET under a mode other than PU operation mode (if Pr.75 is set to allow this), or by the emergency stop function.


Remedy:

  • Check if the motor is stopped by pressing STOP/RESET on the operation panel.

  • Turn OFF the start signal and switch the operation mode to the PU operation mode to reset.


UV
Undervoltage

Cause:
Power supply voltage of the inverter decreased to about 115 VAC (200V class) or 230 VAC (400V class) or below.


Remedy:

  • Check that the power supply voltage is appropriate.

  • Check if a high-capacity motor is driven.

  • Investigate the devices on the power supply line such as the power supply itself.


IH
Inrush current limit resistor overheat

Cause:
The inrush current limit resistor (PTC thermistor) is overheated due to frequent power ON/OFF cycling.


Remedy:

  • Check that power ON/OFF is not repeated frequently.

  • Check that the inrush current limit circuit is not damaged.

  • Configure a circuit where frequent power ON/OFF is not repeated.

  • If problem persists, contact your sales representative.


ED

Emergency drive in operation

Cause:

Emergency drive operation is performed by turning ON the X84 signal.



Remedy:

The display is cleared when the emergency drive operation ends.
E.OC1

Overcurrent trip during acceleration

Cause:

  • Check for sudden speed acceleration.

  • Check if the downward acceleration time is too long in a lift application.

  • Check for output short-circuit.

  • Check that the Pr.3 Base frequency setting is not 60 Hz when the motor rated frequency is 50 Hz.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.

  • Check that the regenerative driving is not performed frequently.


Remedy:

  • Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)

  • If "E.OC1" always appears at start, disconnect the motor once and restart the inverter. If it still appears, contact your sales representative.

  • Check the wiring to make sure that output short circuit does not occur.

  • Set 50 Hz in Pr.3 Base frequency.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.

  • Set the base voltage in Pr.19 Base frequency voltage.


E.OC2

Overcurrent trip during constant speed

Cause:

  • Check for sudden load change.

  • Check for output short-circuit.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.


Remedy:

  • Keep the load stable.

  • Check the wiring to make sure that output short circuit does not occur.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.


E.OC3

Overcurrent trip during deceleration or stop

Cause:

  • Check for sudden speed reduction.

  • Check for output short-circuit.

  • Check for too fast operation of the motor's mechanical brake.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.


Remedy:

  • Set the deceleration time longer.

  • Check the wiring to make sure that output short circuit does not occur.

  • Check the mechanical brake operation.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.


E.OV1

Regenerative overvoltage trip during acceleration

Cause:

  • Check for too slow acceleration. (e.g. during downward acceleration in vertical lift load)

  • Check that the Pr.22 Stall prevention operation level is not set to the no load current or lower.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.


Remedy:

  • Set the acceleration time shorter.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Set a value larger than the no load current in Pr.22.


E.OV2

Regenerative overvoltage trip during constant speed

Cause:

  • Check for sudden load change.

  • Check that the Pr.22 Stall prevention operation level is not set to the no load current or lower.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.

  • Check that acceleration/deceleration time is not too short.


Remedy:

  • Keep the load stable.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Use a brake unit or the power regeneration common converter (FR-CV) as required.

  • Set a value larger than the no load current in Pr.22.

  • Set the acceleration/deceleration time longer.


E.OV3

Regenerative overvoltage trip during deceleration or stop

Cause:

  • Check for sudden speed reduction.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.


Remedy:

  • Set the deceleration time longer. (Set the deceleration time which matches the moment of inertia of the load.)

  • Make the brake cycle longer.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Use the brake unit or power regeneration common converter (FR-CV) as required.

  • Enable the increased magnetic excitation deceleration.


E.THT

Inverter overload trip (electronic thermal O/L relay function)

Cause:

  • Check that acceleration/deceleration time is not too short.

  • Check that torque boost setting is not too large (small).

  • Check that load pattern selection setting is appropriate for the load pattern of the machine.

  • Check that the motor is not used under overload.


Remedy:

  • Set the acceleration/deceleration time longer.

  • Adjust the torque boost setting.

  • Set the load pattern selection setting according to the load pattern of the using machine.

  • Reduce the load.


E.THM

Motor overload trip (electronic thermal O/L relay function)

Cause:

  • Check if the motor is not used under overload.

  • Check that the setting of Pr.71 Applied motor for motor selection is correct.

  • Check that the stall prevention operation setting is correct.


Remedy:

  • Reduce the load.

  • For a constant-torque motor, set the constant-torque motor in Pr.71 Applied motor.

  • Set the stall prevention operation level accordingly.


E.FIN

Heatsink overheat

Cause:

  • Check for too high surrounding air temperature.

  • Check for heat sink clogging.

  • Check that the cooling system is not stopped.


Remedy:

  • Set the surrounding air temperature to within the specifications.

  • Clean the heatsink.

  • If the problem still persists after taking the above measure, contact your sales representative.


E.UVT

Undervoltage

Cause:

  • Check if a high-capacity motor is driven.


Remedy:

  • Check the devices on the power supply line such as the power supply itself.

  • If the problem still persists after taking the above measure, contact your sales representative.


E.ILF

Input phase loss

Cause:

  • Check if a high-capacity motor is driven.

  • Check that phase-to-phase voltage of the three-phase power input is not largely unbalanced.


Remedy:

  • Wire the cables properly.

  • Check the Pr.872 setting.


E.OLT
Stall prevention stop

Cause: Output frequency has fallen to 1 Hz by stall prevention operation and remains for 3 seconds. Check if the motor is not used under overload.

Remedy:

  • Reduce the load.

  • Change the Pr.22 setting.

  • Check that stall prevention (overcurrent) warning (OLC) or stall prevention (overvoltage) warning (OLV) countermeasure is taken.


E.GF
Output side earth (ground) fault overcurrent

Cause: Earth (ground) fault overcurrent flows due to an earth fault on the inverter's output side. Check for a ground fault in the motor and connection cable.

Remedy:

  • Remedy the earth (ground) fault portion.

  • Check the Pr.249 setting.


E.LF
Output phase loss

Cause: One of the three phases (U, V, W) on the inverter's output side is lost. Check wiring and that motor capacity is not smaller than inverter.

Remedy:

  • Wire the cables properly.

  • Check the Pr.251 setting.


E.OHT
External thermal relay operation

Cause: External or internal thermal relay switches ON (contacts open). Check for motor overheating. Check Pr.178 to Pr.182 settings.

Remedy:

  • Reduce the load and operation duty.

  • Even if relay contacts reset automatically, the inverter will not restart unless reset manually.


E.PE6
Internal storage device fault

Cause: Writing data failed due to power-OFF or data fault during parameter operations. Check if power was turned OFF during operations.

Remedy:

  • Check power supply and devices.

  • If due to power-OFF: Check Pr.890. If "7" or smaller, perform All parameter clear and reset.

  • If due to other reasons: Contact sales representative.


E.PE / E.PE2
Parameter storage device fault (Corrupt Memory)

Cause: A fault occurred in the stored parameters (EEPROM failure). Check for too many parameter write times.

Remedy:

  • Contact your sales representative.

  • If writing frequently for communication, set "1" in Pr.342 to enable RAM write.


E.PUE
PU disconnection

Cause: Communication between inverter and PU is suspended/disconnected. Check that PU is connected properly and Check Pr.75.

Remedy:

  • Connect the PU securely.


E.RET
Retry count excess

Cause: Operation cannot be resumed properly within the number of retries set in Pr.67. Find the cause of the fault occurrence.

Remedy:

  • Eliminate the cause of the fault preceding this fault indication.


E.CPU / E.5
CPU fault

Cause: Communication fault of the built-in CPU. Check for devices producing excess electrical noises around the inverter.

Remedy:

  • Take measures against noises if there are devices producing excess electrical noises.

  • Contact your sales representative.


E.CDO
Abnormal output current detection

Cause: Output current exceeds Pr.150 level. Check settings of Pr.150, Pr.151, and Pr.167.

Remedy:

  • Adjust the parameter settings (Pr.150, Pr.151, Pr.167) or load conditions.


E.IOH
Inrush current limit circuit fault

Cause: Resistor of inrush current limit circuit is overheated or faulty. Check that frequent power ON/OFF is not repeated.

Remedy:

  • Configure a circuit where frequent power ON/OFF is not repeated.

  • If problem persists, contact sales representative.


E.ICF
Input monitoring fault

Cause: Input signal does not turn ON/OFF within time set in Pr.242. Check for input signal loss or device failure.

Remedy:

  • Set the Pr.242 setting larger.

  • Check connection of input devices.


E.LCI
4 mA input fault

Cause: Analog input current is 2 mA or less. Check for break in wiring or Pr.778 setting.

Remedy:

  • Check the wiring for the analog current input.

  • Set the Pr.778 setting larger.


E.E10
Inverter output fault

Cause: Fault on inverter output side while Pr.631 is active. Check for ground fault in motor/cable.

Remedy:

  • Remedy the earth (ground) fault portion.

  • Check the Pr.631 setting.


E.0
No fault history

Cause: Appears when no fault records are stored.

Remedy:

  • None required (System Normal).


How to Clear & Reset Mitsubishi FR-CS80 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key directly on the integrated front operation panel while the drive is faulted. Parameter Pr. 75 (Reset selection / PU stop selection) configures reset permissibility under different control modes.
  2. Terminal Input Reset (RES): Turn ON the external terminal RES by closing contact to terminal SD (Sink logic) for at least 0.1 seconds, then reopen the connection.
  3. FR Configurator2 PC Software: Connect via the RS-485 communication terminal block using an RS-485 to USB converter, launch Mitsubishi FR Configurator2, and trigger the “Fault Reset” instruction.
  4. Serial Communication (Modbus RTU): Write a fault reset bit command (Bit 1 or Bit 7 depending on communication mode settings) across the built-in RS-485 Modbus RTU interface.
  5. Power Cycle: Disconnect AC input mains power, wait until the LED display and internal charge light completely turn off (allow at least 10 minutes for full capacitor discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Lethal residual voltage remains inside intermediate DC bus capacitors after main AC power removal. Wait at least 10 minutes after turning OFF mains supply, verify that the operation panel LED display is completely dark, and measure DC voltage across terminals [P/+] and [N/-] with a multimeter to ensure it reads below 30 VDC before inspecting wiring or touching terminal terminals U, V, and W.