Mitsubishi FR-S500 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-S500 compact micro inverter series. Search or filter through the complete fault code directory below.

Compact Micro Inverter Power: 0.1 to 3.7 kW (0.125 to 5 HP) Simple Dial Operation
Power Range 0.1 – 3.7 kW (0.125 – 5 HP)
Supply Voltage 100–120V / 200–240V / 380–480V (1/3-Phase)
Control Modes Soft-PWM / V/F & Flux Vector Control
Operator Interface Integrated Setting Dial Panel / FR-PU04

Complete Mitsubishi FR-S500 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).

Fault Code and MeaningCause and Remedy

OC1

(FR-PU04: OC During Acc)



Overcurrent cut-off during acceleration

Cause:

When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during acceleration, the protective circuit is activated to stop the inverter output.


Check points: Check for sudden acceleration. Check for output short-circuit/ground fault.



Remedy:

  • Increase the acceleration time.



OC2

(FR-PU04: Stedy Spd OC)



Overcurrent cut-off during constant speed

Cause:

When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during constant-speed operation, the protective circuit is activated to stop the inverter output.


Check points: Check for sudden load change. Check for output short-circuit/ground fault.



Remedy:

  • Keep load stable.



OC3

(FR-PU04: OC During Dec)



Overcurrent cut-off during deceleration

Cause:

When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during deceleration (other than acceleration or constant speed), the protective circuit is activated to stop the inverter output.


Check points: Check for sudden speed reduction. Check for output short-circuit/ground fault. Check for too fast operation of motor's mechanical brake.



Remedy:

  • Increase the deceleration time.

  • Adjust brake operation.



OV1

(FR-PU04: OV During Acc)



Regenerative overvoltage cut-off during acceleration

Cause:

When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during acceleration. May also be activated by surge voltage in power supply.


Check points: Check for too slow acceleration.



Remedy:

  • Decrease the acceleration time.

  • Install a power factor improving reactor.



OV2

(FR-PU04: Stedy Spd OV)



Regenerative overvoltage cut-off during constant speed

Cause:

When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during constant speed. May also be activated by surge voltage in power supply.


Check points: Check for sudden load change.



Remedy:

  • Keep load stable.

  • Install a power factor improving reactor.



OV3

(FR-PU04: OV During Dec)



Regenerative overvoltage cut-off during deceleration or stop

Cause:

When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during deceleration or stop. May also be activated by surge voltage in power supply.


Check points: Check for sudden speed reduction.



Remedy:

  • Increase the deceleration time. (Set the deceleration time which matches the inertia moment of the load).

  • Decrease the braking duty.

  • Install a power factor improving reactor.



THM

(FR-PU04: Motor Overload)



Motor overload cut-off (electronic thermal overcurrent protection)

Cause:

The electronic overcurrent protection detects motor overheat due to overload or reduced cooling capability during low-speed operation.


Check points: Check the motor for use under overload.



Remedy:

  • Reduce the load weight.

  • For the constant-torque motor, change the Pr. 71 setting to the constant-torque motor setting.



THT

(FR-PU04: Inv. Overload)



Inverter overload cut-off (electronic thermal overcurrent protection)

Cause:

If a current of more than 150% of the rated output current flows and overcurrent shut-off does not occur (200% or less), inverse-time characteristics activate protection to stop the inverter output to protect output transistors.


Check points: Check the motor for use under overload.



Remedy:

  • Reduce the load weight.



FIN

(FR-PU04: H/Sink O/Temp)



Fin overheat

Cause:

If the cooling fin overheats, the overheat sensor is actuated to stop the inverter output.


Check points: Check for too high ambient temperature. Check for cooling fin clogging.



Remedy:

  • Set the ambient temperature to within the specifications.

  • Clean the cooling fins.



GF

(FR-PU04: Ground Fault)



Start-time output side ground fault overcurrent protection

Cause:

A ground fault overcurrent flowed due to a ground fault which occurred in the inverter's output (load) side. (Valid when Pr. 40 = "1").


Check points: Check for a ground fault in the motor and connection cable.



Remedy:

  • Remedy the ground fault portion.



OHT

(FR-PU04: OH Fault)



External thermal relay

Cause:

The external thermal relay (motor overheat protection) or internally mounted temperature relay in the motor switched on (contacts open).


Check points: Check for motor overheating. Check that value of 7 (OH signal) is set correctly in Pr. 60 to Pr. 63.



Remedy:

  • Reduce the load and operating duty.



OLT

(FR-PU04: Stll Prev STP)



Stall prevention (overload)

Cause:

The running frequency has fallen to 0 by stall prevention operation activated. OL appears while stall prevention is being activated.


Check points: Check the motor for use under overload.



Remedy:

  • Reduce the load weight.



OPT

(FR-PU04: Option Fault)



Communication error

Cause:

A setting error or connection (connector) fault occurred during use of the RS-485 communication function.


Check points: Check that the connector is plugged securely.



Remedy:

  • Make connection securely.

  • Please contact your sales representative.



PE

(FR-PU04: Corrupt Memory)



Parameter error

Cause:

A fault occurred in parameters stored (example: E2PROM fault).


Check points: Check for too many number of parameter write times.



Remedy:

  • Please contact your sales representative.


PUE

PU disconnected

Cause: Communication between inverter and PU is suspended (e.g., if the PU is disconnected with "1" set in parameter n17).



Remedy:

  • Fit the FR-PU04 securely.


RET

Retry count

Cause: If operation cannot be resumed properly within the number of retries set, this function stops the inverter output.



Remedy:

  • Eliminate the cause of the error preceding this error indication.


CPU

CPU error

Cause: If the arithmetic operation of the built-in CPU does not end within a predetermined period, the inverter self-determines it as an alarm.



Remedy:

  • Please contact your sales representative.


FN

Fan trouble

Cause: The cooling fan stops due to a fault or operates differently from the setting of Pr. 76 "cooling fan operation selection".



Remedy:

  • Change the fan.


OL

Stall prevention (overcurrent)

Cause: Current of more than 150% of the rated inverter current flows in the motor during acceleration, constant speed, or deceleration. The function stops frequency change to prevent overcurrent shut-off.



Remedy:

  • The acceleration/deceleration time may change.

  • Increase the stall prevention operation level with Pr. 22.

  • Disable stall prevention with Pr. 21.

  • Check that the torque boost (Pr. 0) setting is not higher than required.


oL

Stall prevention (overvoltage)

Cause: During deceleration, if regenerative energy increases too much to exceed brake capability, this function stops the decrease in frequency to prevent overvoltage shut-off.



Remedy:

  • Increase the deceleration time using Pr. 8 "deceleration time".


PS

PU stop (Stopped with PU STOP key)

Cause: Pr. 75 "reset selection/PU stop selection" had been set and a stop was made by pressing the STOP/RESET key during external operation mode.



Remedy:

  • Refer to page 94 (Check for a stop made by pressing the STOP/RESET key).


UV

Undervoltage

Cause: Power supply voltage reduced below about 115VAC (230VAC for 400V series) resulting in control circuit issues.



Remedy:

  • Check the power supply system equipment.

  • Check for a start of large-capacity motor.


Er1

Write disable error

Cause:

  • Write performed with "1" (write disable) set in Pr. 77.

  • Frequency jump setting range overlapped.

  • Parameter write performed without write precedence (only for RS-485 types).





Remedy:

  • Check the setting of Pr. 77 "parameter write disable selection".

  • Check the settings of Pr. 31 to 36 (frequency jump).

  • Check communication operation settings.


Er2

Write-while-running / mode designation error

Cause:

  • Write was performed during operation.

  • Attempt made to change Pr. 79 setting while operation command input.

  • Write performed in external operation mode.





Remedy:

  • After stopping operation, make parameter setting.

  • After setting the operation mode to "PU operation mode", make parameter setting.


Er3

Calibration error

Cause: Analog input bias and gain calibration values are too close.



Remedy:

  • Check the settings of C3, C4, C6, and C7 (calibration functions).


How to Clear & Reset Mitsubishi FR-S500 Drive Faults

  1. Keypad Reset: Press the STOP / RESET key on the integrated operation panel while the fault code is indicated on the display. Important: Turn off all forward/reverse run commands (STF / STR) prior to resetting to prevent an unexpected motor restart.
  2. Control Terminal Reset (RES): Short the Reset input terminal (RES) to the common terminal (SD in sink logic) for at least 0.1 seconds, then release it. Terminal RES is mapped via multi-function input parameters Pr. 180 to Pr. 183.
  3. FR Configurator Software (Communication models): On FR-S500E models equipped with the RS-485 communication port, connect a PC with a converter cable and select “Inverter Reset / Clear Fault” in FR Configurator.
  4. Serial Network Reset: Write an Inverter Reset instruction command (HFD00) over the RS-485 serial communication bus to clear active trip faults.
  5. Main Power Cycle: Switch OFF the incoming AC mains power, wait until the LED display and red CHARGE LED turn completely off (wait at least 10 minutes for DC bus capacitor discharge), then turn main power back ON.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [P/+] and [N/-] (and confirm the internal red CHARGE indicator lamp is completely unlit) before opening terminal covers, servicing motor wiring, or touching terminals U, V, and W on the Mitsubishi FR-S500 inverter.