Mitsubishi FR-V220E Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi FR-V220E closed-loop vector control inverter series. Search or filter through the complete fault code directory below.

Closed-Loop Vector Inverter Power: 1.5 to 45 kW (2 to 60 HP) Zero-Speed Full Torque Control
Power Range 1.5 – 45 kW (2 – 60 HP)
Supply Voltage 3-Phase 200–230V AC (50/60 Hz)
Control Modes Closed-Loop Vector & Torque Control
Operator Interface FR-PU03V / FR-PU04V Parameter Unit

Complete Mitsubishi FR-V220E Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).

Fault Code and MeaningCause and Remedy

OC During Acc

E.OC1



Overcurrent during acceleration

Cause:

Overcurrent. Main circuit device overheat.



Remedy:

  • Check if acceleration is too fast.

  • Check for output short circuit or ground fault.

  • Check for cooling fan stop.

  • Increase acceleration time.

  • Change fan. Remove obstacle to cooling fan.



Stedy Spd Oc

E.OC2



Overcurrent during constant speed

Cause:

Overcurrent. Main circuit device overheat.



Remedy:

  • Check for sudden load change.

  • Check for output short circuit or ground fault.

  • Check for cooling fan stop.

  • Keep load stable.

  • Change fan. Remove obstacle to cooling fan.



OC During Dec

E.OC3



Overcurrent during deceleration

Cause:

Overcurrent. Main circuit device overheat.



Remedy:

  • Check if deceleration is too fast.

  • Check for output short circuit or ground fault.

  • Check for cooling fan stop.

  • Check if mechanical brake operates too fast.

  • Increase deceleration time.

  • Check brake operation.



Ov During Acc

E.OV1



Overvoltage during acceleration

Cause:

Overvoltage on DC bus (terminals P (+) and N (-)).



Remedy:

  • Check if acceleration is too fast.

  • Increase acceleration time.



Stedy Spd Ov

E.OV2



Overvoltage during constant speed

Cause:

Overvoltage on DC bus (terminals P (+) and N (-)).



Remedy:

  • Check for sudden load change.

  • Keep load stable.



Ov During Dec

E.OV3



Overvoltage during deceleration

Cause:

Overvoltage on DC bus (terminals P (+) and N (-)).



Remedy:

  • Check if deceleration is too fast.

  • Increase deceleration time (Set deceleration time which matches load GD²).

  • Reduce braking duty.



Motor Overload

THM



Overload alarm (Thermal relay for motor)

Cause:

Motor used under overload.



Remedy:

  • Reduce load.

  • Increase motor and inverter capacities.



Inv. Overload

THT



Overload alarm (Thermal relay for inverter)

Cause:

Motor used under overload.



Remedy:

  • Reduce load.

  • Increase motor and inverter capacities.



Inst. Pwr. Loss

IPF



Instantaneous power failure

Cause:

Instantaneous power failure.



Remedy:

  • Check the cause of instantaneous power failure.

  • Investigate power supply system.



Under Voltage

UVT



Undervoltage

Cause:

Drop of power supply voltage. No jumper across terminals P (+) - P1.



Remedy:

  • Large-capacity motor started?

  • Check for jumper across terminals P (+) - P1.

  • Check power system equipment such as power supply capacity.

  • Install jumper if disconnected.



Br. Cct. Fault

BE



Brake transistor alarm

Cause:

Brake transistor fault (only 5.5K or less).



Remedy:

  • Check if braking duty is proper.

  • Reduce load GD².

  • Reduce braking duty.



Overspeed occurrence

OS



Overspeed occurrence

Cause:

The motor speed exceeded the set overspeed level.



Remedy:

  • Check Pr. 69 "number of PLG pulses" setting correctness.

  • Set Pr. 69 "number of PLG pulses" value correctly.



OH Fault

OHT



External thermal relay operation

Cause:

Temperature detector in motor operated.



Remedy:

  • Check motor for overheat.

  • Reduce load and frequency of operation.



Stll Prev STP

OLT



Stall prevention

Cause:

Stall prevention or current limit function activated too long.



Remedy:

  • Check if motor is used under overload.

  • Reduce load.

  • Increase motor and inverter capacities.



Option Fault

OPT



Inboard option connection alarm

Cause:

Option and inverter connected improperly.



Remedy:

  • Check for loose connector.

  • Securely connect.



Corrupt Memry

PE



Parameter storage device alarm

Cause:

Storage device (E²PROM) fault.



Remedy:

  • Number of parameter write times too many?

  • Change inverter.



Excessive speed deflection

OSD



Excessive speed deflection

Cause:

The deflection between the speed setting and motor speed exceeded the deflection level.



Remedy:

  • Is the load too large?

  • Check Pr. 69 "number of PLG pulses" setting correctness.

  • Lighten the load.

  • Set Pr. 69 "number of PLG pulses" value correctly.



PU Leave Out

PUE



PU disconnected

Cause:

PU disconnected from connector.



Remedy:

  • Check for loose PU fitting.

  • Fit PU securely.



CPU Fault

CPU



CPU error

Cause:

Internal CPU malfunction.



Remedy:

  • Check for loose connector.

  • Change inverter.



No encoder signal

ECT



No encoder signal

Cause:

The PLG pulse is not being input.



Remedy:

  • Check for loose connector.

  • Check for wire breakage in cable.

  • Securely connect.

  • Replace cable.



PU to Inverter comms. Error

0.00 (LED display proper)



Inv. Reset ON

Cause:

Reset signal ON. Loose connection between PU and inverter. Communication circuit fault.



Remedy:

  • Check for miswiring to reset terminal.

  • Check for loose connector.

  • Turn the reset signal off.

  • Securely connect.

  • Change inverter.



Excessive position error

OD



Position error large

Cause:

Difference between position command and position feedback exceeded detection level.



Remedy:

  • Check that the installation direction of the encoder for position detection and parameters match.

  • Is the load too large?

  • Check Pr. 69 "number of PLG pulses" setting correctness.

  • Check the parameters.

  • Lighten the load.

  • Set Pr. 69 "number of PLG pulses" value correctly.



No encoder A signal

ECA



No encoder signal

Cause:

The PLG pulse for the FR-VPA is not being input.



Remedy:

  • FR-VPA connected properly?

  • Check for loose connector.

  • Check for wire breakage in cable.

  • Check for detector fault.

  • Securely connect.

  • Replace cable.

  • Replace the detector.


How to Clear & Reset Mitsubishi FR-V220E Drive Faults

  1. Keypad Reset: Press the STOP / RESET key on the attached FR-PU03V or FR-PU04V parameter unit while the drive is in a tripped state.
  2. External Reset Terminal (RES): Bridge control terminal RES to terminal SD for at least 0.1 seconds, then release. Note that holding RES closed continuously prevents drive start-up.
  3. Parameter Unit Reset Command: Use the parameter clear or fault reset function menu accessible directly on the FR-PU parameter keypad interface.
  4. Option Communication Board: If fitted with an optional communication interface (such as CC-Link or RS-485 board), set the reset bit in the network control word register to clear active trips.
  5. Power Cycle: Switch OFF the main power circuit breaker (MCCB). Wait until the internal intermediate circuit CHARGE lamp is completely off (approx. 10 minutes), then restore AC mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [P/+] and [N/-] and confirm the CHARGE lamp is completely extinguished before opening terminal covers or touching main circuit terminals (R, S, T, U, V, W) on the Mitsubishi FR-V220E inverter.