Mitsubishi FR-XC Converter Fault Codes & Diagnostic Guide

Complete fault code reference directory, protective trip causes, and step-by-step troubleshooting procedures for the Mitsubishi FR-XC multifunction regeneration converter series. Search or filter through the complete fault code directory below.

Multifunction Regeneration Converter Capacity: 7.5 to 220 kW (10 to 300 HP) Harmonic Suppression & Power Regeneration
Capacity Range 7.5 – 220 kW (10 – 300 HP)
Supply Voltage 200–240V / 380–500V (3-Phase)
Operating Modes Harmonic Suppression, Common Bus, Reg. Mode 2
Operator Interface Integrated Operation Panel / FR-PU07

Complete Mitsubishi FR-XC Converter Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or E.THT).

Fault Code and MeaningCause and Remedy
HOLD

Operation panel lock

Cause:


Operation lock is set. Operation other than STOP/RESET is invalid.



Remedy:



  • Press MODE for 2 seconds to release the lock.


Er1

Write disable error

Cause:


Parameter setting was attempted while Pr.77 Parameter write selection is set to disable parameter write.



Remedy:



  • Check the Pr.77 setting.


rE1

Parameter read error

Cause:


A failure has occurred at EEPROM in the operation panel during reading of the parameter settings for Parameter copy.



Remedy:



  • Perform Parameter copy again.

  • The operation panel (FR-DU08) may be faulty. Contact your sales representative.


rE2

Parameter write error

Cause:



  • Parameter write from the operation panel to the multifunction regeneration converter was attempted for Parameter copy during operation.

  • A failure has occurred at EEPROM in the operation panel during writing of the parameter settings for Parameter copy.





Remedy:



  • Check that the converter is stopped.

  • After turning ON the SOF signal, perform Parameter copy again.

  • The operation panel (FR-DU08) may be faulty. Contact your sales representative.


rE3

Parameter verification error

Cause:



  • The data in the converter are different from the data in the operation panel.

  • A failure has occurred at EEPROM in the operation panel during parameter verification.





Remedy:



  • Continue the verification by pressing SET.

  • Perform the parameter verification again.

  • The operation panel (FR-DU08) may be faulty. Contact your sales representative.


rE4

Product series error

Cause:



  • The series of the source converter used to copy or verify parameters is not the same as the target converter.

  • The operation panel data was incorrect when attempting to verify parameters or copy parameters from the operation panel to the converter.





Remedy:



  • Check that the source converter being used to verify or copy parameters is the same series as the target converter.

  • Check that the copying of parameters was not interrupted due to a loss of power.

  • Try to copy or verify parameters again.


OL / LB

Overload signal detection

Cause:


Appears when the current limit function of the converter is activated.



Remedy:



  • Set the acceleration/deceleration time longer in the inverter.

  • Reduce the load.

  • Check that the peripheral devices are operating properly.


TH / LC

Electronic thermal relay function pre-alarm

Cause:


Appears if the cumulative value of the electronic thermal relay reaches or exceeds 85% of the preset level.



Remedy:



  • Check for large load or sudden acceleration.

  • Reduce the load and frequency of operation.


PS / LD

PU stop

Cause:


The PU stop (stop of the converter operation by pressing STOP/RESET on the PU) is enabled by the setting of Pr.75.



Remedy:



  • To reset the indication, turn ON the Converter stop (SOF) signal to stop the converter output, and press EXT.


MT / LE

Maintenance signal output

Cause:


Appears when the converter's cumulative energization time reaches or exceeds the parameter set value (Pr.34 > Pr.35).



Remedy:



  • Write "0" in Pr.34 Maintenance timer.


CP

Parameter copy

Cause:


Appears when parameter copy is performed between the FR-XC-(H)55K or lower and the FR-XC-H75K.



Remedy:



  • Pr.52 PU main monitor selection and Pr.57 Restart selection must be set again.

  • Set the initial value in Pr.989 Parameter copy alarm release.


SL / LG

Power supply not detected

Cause:



  • Appears when the power supply detection ends incompletely at a power failure.

  • Appears at the power ON of the control circuit when using separate power supply sources for the control circuit and main circuit.





Remedy:



  • Check that the wiring from proper power source is performed correctly.

  • Correct the wiring.


LH

Converter operation disabled

Cause:


Appears when the regenerative operation is not possible due to data processing in the converter (e.g. triggered by SOF signal).



Remedy:



  • Turn OFF the SOF signal.

  • Check the power supply condition is stable.

  • Check that the multifunction regeneration converter was reset after Parameter copy.


LJ

Box-type reactor overheat pre-alarm

Cause:


Appears when the speed of cooling fan on the box-type reactor decreases.



Remedy:



  • The fan may be faulty. Contact your sales representative.

  • Check the cooling fan for a failure.


FN / LA

Fan alarm

Cause:


Appears when the cooling fan in the converter stops due to a fault or slows down.



Remedy:



  • The fan may be faulty. Contact your sales representative.

  • Check the cooling fan for a failure.


E.OCT / E.A

Overcurrent trip

Cause:


The converter output is shut off if the input current exceeds the specified level during operation.



Remedy:



  • Check for sudden load change.

  • Check for a short-circuit in the output circuit.

  • Check that the wiring is performed correctly.

  • Check that any power supply failure did not occur.

  • Keep the load stable.


E.OVT / E.B

Overvoltage trip

Cause:


If the converter's internal main circuit DC voltage reaches or exceeds the specified value, the protective circuit is activated. Can also be caused by surge voltage.



Remedy:



  • Check for sudden load change and excessive regeneration.

  • Check that any power supply failure did not occur.

  • Keep the load stable.

  • Check the power supply.


E.THT / E.C

Overload trip (electronic thermal relay function)

Cause:


Electronic thermal relay activates in inverse-time characteristics against the converter input to stop the output.



Remedy:



  • Reduce the load.

  • Reconsider the configuration of the inverters for the converter.

  • Make the permissible voltage imbalance ratio within 3%.

  • Check that the total capacity of inverters is not larger than the converter capacity.


E.FIN / E.D

Heat sink overheat

Cause:


When the heat sink overheats, the temperature sensor activates, and the converter output is stopped.



Remedy:



  • Set the surrounding air temperature to within the specifications.

  • Clean the heat sink (check for clogging).

  • Replace the cooling fan if stopped.


E.IPF / E.E

Instantaneous power failure

Cause:


Instantaneous power failure protection function activates to stop the output. (Power failure persists for 100 ms or longer).



Remedy:



  • Remedy the instantaneous power failure.

  • Prepare a backup power supply for instantaneous power failure.

  • Set the function of automatic restart after instantaneous power failure (Pr.57).


E.UVT / E.F

Undervoltage

Cause:


If the power supply voltage drops to about 150 VAC or lower, the output is stopped to prevent control circuit malfunction.



Remedy:



  • Investigate the devices on the power system such as the power supply itself.

  • Check if a high-capacity motor is driven.

  • Check that the wiring is performed correctly.


E.ILF / E.G

Input phase loss

Cause:


This protective function is activated when any of the three phases of power input is lost.



Remedy:



  • Correct the wiring.

  • Repair a broken wire.


E.OHT / E.H

External thermal relay operation

Cause:


If an overheat protection device such as a thermostat activates, the output of the converter is stopped. (Available when "4" is set in Pr.3, Pr.4, or Pr.7).



Remedy:



  • Check for the overheat of a thermostat or other similar peripheral devices.

  • Check for a short circuit between terminals PC and SD.

  • Check the wiring.

  • Reset the thermostat (converter does not restart unless reset).


E.J / PUE / E.PUE

PU disconnection

Cause: Communication between the converter and the PU is suspended (e.g., disconnected parameter unit) while Pr.75 is set to "2, 3, 16 or 17".



Remedy:

  • Check that the PU is connected properly.

  • Check that the Pr.75 setting is correct.

  • Set Pr.75 appropriately.

  • Fit the PU securely.


E.K / RET / E.RET

Retry count excess

Cause: Operation cannot be resumed properly within the set number of retries (enabled when Pr.67 is set).



Remedy:

  • Find the cause of the fault occurrence.

  • Eliminate the cause of the error preceding this error indication.


E.L / CPU / E.CPU

CPU fault

Cause: A communication fault in the built-in CPU has occurred.



Remedy:

  • Check for devices producing excess electrical noises around the converter.

  • Take measures against noises.

  • Contact your sales representative.


E.L / E13 / E.13

Internal circuit fault

Cause: An internal circuit fault has occurred.



Remedy:

  • Contact your sales representative.


E.M / P24 / E.P24

24 VDC power output short circuit

Cause: The 24 VDC power output from terminal PC is shorted.



Remedy:

  • Check for a short circuit in terminal PC.

  • Repair the short-circuited portion.

  • Reset via PU or power cycle (cannot be reset by external RES signal).


E.N / IOH / E.IOH

Inrush overheat

Cause: Inrush current limit contactor does not turn ON, thermostat activates, or the circuit is damaged due to frequent power ON/OFF.



Remedy:

  • Check that frequent power ON/OFF is not repeated.

  • Configure a circuit where frequent power ON/OFF is not repeated.

  • If situation persists, contact your sales representative.


E.P / PE / E.PE

Corrupt Memory (Control circuit board)

Cause: Parameter storage device fault (EEPROM failure) or too many parameter write times.



Remedy:

  • Set "1" in Pr.342 (write to RAM) for operations requiring frequent parameter writing.

  • If situation persists, contact your sales representative.


E.P / PE2 / E.PE2

PR storage alarm (Main circuit board)

Cause: Parameter storage device fault (EEPROM failure) on the main circuit board.



Remedy:

  • Contact your sales representative.


E.Q / OP1 / E.OP1

Communication option fault

Cause: Communication line error, wrong option setting, loose connector, cable break, or terminating resistor issue.



Remedy:

  • Check the option function setting.

  • Connect the communication option securely.

  • Check the connection of communication cables.


E.T / ERR / E.MF1

Connection mode fault

Cause: Connection mode selection switch does not match the actual wiring of main circuit terminals.



Remedy:

  • Check that the setting of Pr.415 SW2 setting status is correct.

  • Check the wiring.

  • Set Pr.415 appropriately.


E.U / ERR / E.MF2

Unsupported control selection

Cause: Unsupported function is set to be enabled by using Pr.416.



Remedy:

  • Check the setting of Pr.416.

  • Set Pr.416 correctly.


E.V / ERR / E.FT1

Box-type reactor overheat protection

Cause: Reactor overheat (LOH) signal detected, Pr.416 setting mismatch, installation error, or cooling fan failure.



Remedy:

  • Remove foreign matter from cooling fan.

  • Set Pr.416 correctly (match reactor model).

  • Check the wiring.

  • Contact sales representative if needed.


E.W / ERR / E.FT2

Box-type reactor cooling fan power short

Cause: Power supply for the cooling fan on the box-type reactor is shorted.



Remedy:

  • Check for a short circuit in power supply for the cooling fan.

  • Correct the wiring.


E.1 / E.1

Option fault

Cause: Contact failure between converter and option, switch setting changed, or excess electrical noise.



Remedy:

  • Connect the communication option securely.

  • Take measures against noises.

  • Set the switch for manufacturer setting back to initial position.

  • Contact sales representative if unresolved.


E.6 / E.16

Main circuit power supply detection fault

Cause: Power supply to the main circuit is not detected.



Remedy:

  • Contact your sales representative.


E.8 / E.8

Input power supply fault 1

Cause: Power supply frequency fault, phase detection failure, overvoltage, sudden amplitude change, or wiring error (R, S, T).



Remedy:

  • Check that the wiring from proper power source is performed correctly.

  • Correct the wiring.


How to Clear & Reset Mitsubishi FR-XC Converter Faults

  1. Keypad Reset: Press the STOP / RESET key on the integrated operation panel. Keypad reset is active only while the converter is in a fault trip status.
  2. Digital Input Reset (RES Terminal): Turn ON the reset signal between terminal RES and terminal SD (for sink logic) or terminal PC (for source logic) for at least 0.1 seconds, then turn it OFF.
  3. FR Configurator2 PC Software: Connect a PC to the RS-485 / PU interface connector on the unit, launch FR Configurator2, open the Diagnostics/Monitor window, and execute “Fault Clear” or “Inverter/Converter Reset”.
  4. RS-485 / Network Communication: Write a reset command code (such as writing H9696 to clear parameter or asserting the reset bit) via the built-in RS-485 communication link using Modbus RTU or Mitsubishi dedicated inverter protocol.
  5. Power Cycle: Switch OFF the main circuit breaker (terminals R/L1, S/L2, T/L3). Wait until the red CHARGE lamp turns off completely (approx. 10 minutes), then switch power back ON.
⚠️ High-Voltage Electrical Safety Warning: Always verify that the red CHARGE lamp on the front unit is completely extinguished, and use a calibrated digital multimeter to confirm that the intermediate DC bus voltage measured across terminals [P/+] and [N/-] is strictly below 30V DC before touching busbars, terminal screws, or wiring terminals.