Mitsubishi MD-CX520 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi MD-CX520 MELIPM permanent magnet motor drive series. Search or filter through the complete fault code directory below.
Power Range
0.5 – 7.0 kW (0.75 – 10 HP)
Supply Voltage
3-Phase 200–240V AC (50/60 Hz)
Control Modes
Permanent Magnet Motor Vector Control
Operator Interface
FR-PU04 Parameter Unit / Integrated Panel
Complete Mitsubishi MD-CX520 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E.OC1 Acceleration-time overcurrent | Cause: The acceleration torque is beyond the drive unit capability. Outputs U, V and W are in a short circuit or ground fault. The motor restarted during coasting. Remedy:
|
| E.OC2 Constant speed-time overcurrent | Cause: Excessive load was applied instantaneously. Outputs U, V and W resulted in a short circuit or ground fault during constant-speed operation. Remedy:
|
| E.OC3 Deceleration-time overcurrent | Cause: The deceleration torque is beyond the drive unit capability. Outputs U, V and W resulted in a short circuit or ground fault during deceleration operation. The mechanical brake of the motor operates too early. Remedy:
|
| E.OV1 Acceleration time overvoltage | Cause: Surge compounded with power during acceleration operation. The regenerative energy handling capability is insufficient. Remedy:
|
| E.OV2 Constant speed-time overvoltage | Cause: Surge compounded with power during constant speed operation. Load increased suddenly, activating the stall prevention function. The regenerative energy handling capability is insufficient. Remedy:
|
| E.OV3 Deceleration time overvoltage | Cause: The deceleration torque is beyond the drive unit capability. The regenerative energy handling capability is insufficient. Surge compounded with power during deceleration operation or stop. Remedy:
|
| E.THT / E.THM Electronic thermal O/L relay | Cause: The motor and drive unit are operated under overload. Remedy:
|
| E.UVT Undervoltage | Cause: An instantaneous voltage drop in the AC input power supply. The AC input power supply voltage is insufficient. Remedy:
|
| E.FIN Fin overheat | Cause: Heatsink temperature is higher than the permissible value. The surrounding air temperature exceeded permissible limits. The cooling fan failed. Remedy:
|
| E.OHT External failure | Cause: An external relay or another relay, which is connected to the terminal where the OH signal is assigned, turned ON. Remedy:
|
| E.PUE PU disconnection | Cause: A connection fault of the operation panel or the parameter unit occurred. RS-485 communication was interrupted. Remedy:
|
| E.OLT Stall prevention stop | Cause: Motor overload activated the stall prevention function consecutively, stopping the motor. Remedy:
|
| E.LF Open loss | Cause: One of the output phases U, V, or W was lost. Remedy:
|
| E.CPU CPU fault | Cause: Malfunction of CPU. Remedy:
|
| E.PE Storage device fault | Cause: The storage device failed. Remedy:
|
| E.BE Brake circuit fault | Cause: The regenerative brake circuit failed. Remedy:
|
| OL Overload 1 / Overload 2 | Cause: Overcurrent or Main circuit DC voltage too high. (Stall prevention activated). Remedy:
|
| FN Fan failure | Cause: Cooling fan fault. Remedy:
|
| Err Operation error | Cause: Parameter changed during External operation. Value outside range. RES signal remains ON. Connection fault. Remedy:
|
| PS Emergency stop | Cause: The STOP/RESET key was pressed to make a stop during External operation. Remedy:
|
How to Clear & Reset Mitsubishi MD-CX520 Drive Faults
- Keypad Reset: Press the STOP / RESET key directly on the operation panel or attached FR-PU04 parameter unit when the drive trip protection is activated.
- External Reset Terminal (RES): Bridge control terminal RES to terminal SD (sink logic) for at least 0.1 seconds, then disconnect. Keep the RES signal OFF during normal operation.
- Parameter Unit Clear: Use the FR-PU04 parameter unit interface to access the alarm clear menu to reset the active fault state and historical trip records.
- Serial Communication Command: If controlled over RS-485 serial communication, transmit a software reset command via the communication control register.
- Power Cycle: Disconnect the incoming line breaker (MCCB/contactor). Wait at least 10 minutes until the CHARGE lamp is completely extinguished and the display turns off, then power the unit back ON.
⚠️ High-Voltage & Permanent Magnet Safety Warning:
Because the MD-CX520 drives permanent magnet (MELIPM) motors, high terminal voltage is generated across terminals U, V, and W whenever the motor shaft is turned by external force—even when main power is disconnected. Always lock the motor rotor against rotation, verify with a calibrated multimeter that intermediate DC bus voltage is strictly below 30VDC across terminals [P/+] and [N/-], and ensure the CHARGE lamp is completely extinguished before touching any power connections.