Nidec Control Techniques Commander S Fault Codes & Diagnostic Guide

Comprehensive error code directory, trip alarm causes, and step-by-step diagnostic procedures for the Nidec Control Techniques Commander S micro AC drive series. Search or filter through the complete fault code directory below.

General Purpose Micro AC Drive Power: 0.18 to 4.0 kW (up to 11 kW) Marshal App & NFC Interface
Power Range 0.18 – 4.0 kW (0.25 – 5.0 HP)
Supply Voltage 100V / 200V 1Ø, 200V / 400V 3Ø
Control Modes Linear & Square V/F, Resistance Comp.
Operator Interface Integrated Keypad & Marshal App (NFC)

Complete Nidec Control Techniques Commander S Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E001, E006, or Overcurrent).

Fault Code and MeaningCause and Remedy
A0
Motor Overload

Cause: Motor Thermal Percentage (P1.22) is larger than 75 % and the current magnitude is larger than the motor rated value.



Remedy:

  • Reduce the load on the motor.

  • Check for a jammed motor shaft.


A1
Drive Overload

Cause: Drive Thermal Percentage (P1.23) is > 95 %. The alarm will be cleared when Drive Thermal Percentage is < 75 %.



Remedy:

  • Reduce load on motor or ambient temperature of the drive.


A2
Auto-tune Active

Cause: Will be reset when auto-tune complete.



Remedy:

  • Wait for auto-tune to complete.


A3
Limit Switch Active

Cause: A digital input has been configured as a limit switch and is active.



Remedy:

  • Rotate the motor away from the limit switch.

  • See Sequencer Input and Output Indicators (P1.11) and Digital IO Indicators (P1.25).


A4
Supply Phase Loss or Imbalance

Cause: The drive has detected a supply phase loss or a large imbalance between the phases.



Remedy:

  • Check supply fuses to the drive.

  • Check the voltage on each phase is equal.


A5
Analog Input Current Loop Loss

Cause: The input current of an analog input (T2 or T4) has fallen below 3 mA. See Analog Input 1 Type (P6.01).



Remedy:

  • Check current loop master is powered.

  • Check the integrity of the wiring.


A6
Current Limit Active

Cause: The drive is at its current limit.



Remedy:

  • Increase time set in Acceleration Rate 1 (P2.06).

  • Reduce the load on the motor.


A7
I/O Overload

Cause: The current demand on the drive 24 V circuit has exceeded 100 mA.



Remedy:

  • Check 24 V output, digital output and 485 port for a current overload condition or potential short.


E000
None

Cause: No error.



Remedy:

  • No action required.


E001
DC Over Voltage

Cause: The D.C. bus voltage has exceeded the maximum D.C. bus voltage (Instant Threshold or Delay Threshold exceeded).



Remedy:

  • Increase deceleration ramp rate parameter values in Deceleration Rate 1 (P2.07) and Rate 2 (P2.09).

  • Consider enabling S-Ramps (P2.05) if the problem occurs at the start of deceleration.

  • Consider reducing Standard Ramp Voltage (P2.12) if seen during deceleration.

  • Check nominal A.C. supply level.

  • Check for supply disturbances which could cause the D.C. bus level to rise.

  • Check motor insulation using an insulation tester.


E003
Over Current

Cause: The instantaneous drive output current has exceeded the over current threshold of the drive.



Remedy:

  • Increase time taken for the drive to accelerate/decelerate.

  • Check for short circuit on the output cabling.

  • Check integrity of the motor insulation using an insulation tester.

  • Check the motor cable length is within limits of the drive.

  • Reduce the value set in Current Loop Gain (P3.23).


E006
External Error

Cause: An external error has been generated by a digital input when configured as External Error (14).



Remedy:

  • Check the external device/source triggering the digital input.


E007
Motor Over Speed

Cause: Ramp Output (P1.14) has exceeded the threshold defined by 1.2 x Maximum Frequency Limit (P2.02).



Remedy:

  • Check that the motor is not being driven by another part of the system.


E009
Capacitor Failed

Cause: The D.C. bus capacitors have failed.



Remedy:

  • Contact the supplier of the drive.


E018
Tune Interrupted

Cause: The drive was prevented from completing an auto-tune, because either the drive enable or the drive run signals were removed.



Remedy:

  • Ensure the drive enable signal is active for the entire auto-tune.

  • Ensure a run signal (Run Forward, Run Reverse or Run) is active for the entire auto-tune.

  • If these signals are supplied by a digital input, check the states of the IO using Digital IO Indicators (P1.25).


E020
Motor Temp

Cause: The drive has estimated that the motor has become too hot based on the Motor Rated Current (P3.01) and Thermal Protection Action (P3.21).



Remedy:

  • Ensure the load is not jammed / sticking.

  • Check the load on the motor has not changed.

  • Ensure the motor rated current is correct.


E021
Drive Temp 1

Cause: An IGBT junction over-temperature has been detected.



Remedy:

  • Check enclosure temperature.

  • Check enclosure / drive fans are still functioning correctly.

  • Clean the fan filter if being used.

  • Check enclosure ventilation paths.

  • Check enclosure door filters.

  • Increase ventilation.

  • Reduce duty cycle.

  • Increase acceleration / deceleration rate parameter values.

  • Reduce motor load.

  • Ensure all three supply phases are present and balanced.

  • Confirm the drive is correctly sized for the application.

  • Use a drive with larger current / power rating.


E023
Drive Temp 2

Cause: A power stage over-temperature has been detected.



Remedy:

  • See Drive Temp 1.


E027
Drive Temp 3

Cause: A D.C. bus component over temperature has been detected.



Remedy:

  • See Drive Temp 1.


E028
An In 1 Current

Cause: A current loss was detected in T2 analog input 1 and the input type is set to 4-20 mA Error. Loss of input detected if current falls below 3 mA.



Remedy:

  • Check control wiring is correct.

  • Check control wiring is undamaged.

  • Check T2 Analog Input 1 Type (P6.01).

  • Check the current signal is present and greater than 3 mA.


E029
An In 2 Current

Cause: A current loss was detected in T4 analog input 2 and the input type is set to 4-20 mA Error. Loss of input detected if current falls below 3 mA.



Remedy:

  • Check control wiring is correct.

  • Check control wiring is undamaged.

  • Check T4 Analog Input 2 Type (P6.02).

  • Check the current signal is present and greater than 3 mA.


E030
Watchdog Timeout

Cause: Once the control word has been enabled, it must continue to be written to at least once a second to prevent a Watchdog Timeout error.



Remedy:

  • Ensure the control word is being written to cyclically.


E032
Supply Phase

Cause: The drive has detected a supply phase loss or large supply imbalance.



Remedy:

  • Check the A.C. supply voltage balance and level at full load.

  • Check the output current stability.

  • Reduce the duty cycle.

  • Reduce the motor load.


E033
Motor Resistance

Cause: The auto-tune test to measure the motor stator resistance has failed because the output current failed to rise to the correct level.



Remedy:

  • Check the motor cable / connections.

  • Check the integrity of the motor stator windings using an insulation tester.

  • Check the motor phase to phase resistance at the drive terminals.

  • Check the motor phase to phase resistance at the motor terminals.

  • Select Linear V to F (1) in Motor Control Mode (P3.05) and verify output waveforms.

  • Replace the motor.


E034
Remote Keypad

Cause: A remote keypad has been removed whilst the RUN and STOP buttons have been configured to Run/Stop the drive.



Remedy:

  • Check cable connection.


E035
Control Word

Cause: Bit 12 (Control Word Error) in Binary Control Word (P4.18) has been set to 1 whilst the control word is enabled (bit 15 = 1).



Remedy:

  • Check control system logic for Bit 12 activation.


E036
User Save

Cause: The user-save parameters have been corrupted.



Remedy:

  • Restore Factory Defaults (P4.01).


E037
Power Down Save

Cause: The power down save parameters have been corrupted.



Remedy:

  • Restore Factory Defaults (P4.01).


E093
Inter-Processor

Cause: Communication between the control board processor and the power stage processor has been lost (likely noise).



Remedy:

  • Follow guidance in section 4.7 Electromagnetic compatibility (EMC).


E098
Motor Phase

Cause: Motor Phase Loss Detection (P4.15) is enabled and a motor phase loss has been detected.



Remedy:

  • Check motor and drive connections.

  • Check cable integrity.


E099
Save Blocked

Cause: A save has been triggered while Marshal is attempting to communicate with the drive.



Remedy:

  • Save parameter settings using Save Parameters (P4.19).


E172
Fire Mode Error

Cause: Fire mode has been deactivated and errors were suppressed while the drive was in fire mode.



Remedy:

  • See Error History 1 (P1.30) to Error History 3 (P1.32).


E189
An In 1 Overload

Cause: The input current on T2 analog input 1 has exceeded 24 mA.



Remedy:

  • Check control wiring is correct.

  • Check control wiring is undamaged.

  • Check T2 Analog Input 1 Type (P6.01).


E190
An In 2 Overload

Cause: The input current on T4 analog input 2 has exceeded 24 mA.



Remedy:

  • Check control wiring is correct.

  • Check control wiring is undamaged.

  • Check T4 Analog Input 2 Type (P6.02).


E216
Firmware Fault 1

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E220
Firmware Fault 2

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E222
Firmware Fault 3

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E224
Firmware Fault 4

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E228
Ground fault

Cause: The drive has detected a ground (earth) fault on the motor cable/windings.



Remedy:

  • Check for short circuit to ground (earth) on the output cables.

  • Check the integrity of the motor insulation using an insulation tester.


E232
Firmware Fault 5

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E235
Firmware Fault 6

Cause: Hardware fault.



Remedy:

  • Contact the supplier of the drive.


E245
Firmware Fault 7

Cause: A firmware update has been interrupted.



Remedy:

  • Restart the drive.

  • If the firmware was being downloaded, try again.

  • If the issue persists this could indicate a hardware fault – Contact the supplier of the drive.


E251
Saved Corrupted

Cause: This error indicates that parameter data has been corrupted.



Remedy:

  • Restore factory defaults (P4.01).


E252
Database Changed

Cause: A firmware update has been interrupted. The firmware has been changed but the project parameter values have been lost.



Remedy:

  • Restore Factory Defaults (P4.01).


How to Clear & Reset Commander S Drive Faults

  1. Keypad Reset: Press the red Stop / Reset key on the integrated drive front panel to acknowledge and clear active trips after eliminating the root cause.
  2. Marshal Mobile App (NFC): Open the Nidec Marshal App on your smartphone and tap against the NFC symbol on the drive faceplate to read diagnostics and perform a guided fault reset (even when the drive is powered down).
  3. Digital Input Reset (DI): If programmed via parameter configuration, momentarily toggle the assigned reset digital input terminal to clear the trip condition remotely.
  4. Modbus RTU Control Word: Write a logical `1` to the Reset Bit (Bit 3) via serial communications over the built-in RJ45 Modbus RTU communication interface.
  5. Power Cycle: Disconnect incoming AC mains power, allow the display and indicators to extinguish completely (wait at least 5 minutes for bus capacitors to discharge), and reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage has discharged strictly below 50VDC across DC bus terminals (+DC / -DC or motor terminals) before opening terminal covers, checking wiring, or touching terminals U, V, and W on the Commander S drive.