Nidec Control Techniques Commander SE drive

Home / Nidec Control Techniques / Nidec Control Techniques Commander SE drive

Nidec Control Techniques Commander SE Fault Codes & Troubleshooting Guide

Complete trip code diagnostic directory, root cause analysis, and step-by-step troubleshooting procedures for the Nidec Control Techniques Commander SE AC drive series. Search or filter through the complete fault code list below.

Open Loop Vector AC Drive Power: 0.25 to 37 kW (0.33 to 50 HP) Intelligent Thermal Management (ITM)
Power Range 0.25 – 37 kW (0.33 – 50 HP)
Supply Voltage 200–240V / 380–480V (1Ø / 3Ø)
Control Modes Open Loop Vector & V/Hz Control
Operator Interface Integrated LED Keypad & Display

Complete Nidec Control Techniques Commander SE Trip Directory

Use the search box in the table below to quickly find your trip code (e.g., type OI.AC, OV, th, or Overcurrent).

Fault Code and MeaningCause and Remedy
UU (1)
DC link under voltage

Cause:

Low AC supply voltage.

Low DC link voltage when supplied by external DC power supply.



Remedy:

Check power supply voltage.
OU (2)
DC link over voltage

Cause:

Excessive inertia in the machine during deceleration.

Deceleration rate set too fast for inertia of machine.



Remedy:

Adjust deceleration ramp times.

Check for overvoltage trip levels (200V units: 420VDC, 400V units: 830VDC).
OI.AC** (3)
AC instantaneous over current trip

Cause:

Insufficient ramp times.

Phase to phase or phase to earth short-circuit at the Drive output.



Remedy:

Drive requires autotuning to motor (see parameter 38).

Note: These trips cannot be reset for 10 seconds.
OI.br** (4)
Overcurrent on braking IGBT

Cause:

Excessive current in braking resistor.

Braking resistor value too small (Does not apply to Size 1 units).



Remedy:

Check braking resistor values.

Note: These trips cannot be reset for 10 seconds.
Et (6)
External trip

Cause:

External trip terminal opened (when programmed).



Remedy:

Check external circuit connected to trip terminal.
O.SP (7)
Over speed

Cause:

Excessive motor speed (typically caused by the mechanical load driving the motor).



Remedy:

Check mechanical load conditions.
tunE (18)
Auto-tune failure

Cause:

Motor loaded or no motor connected.



Remedy:

Ensure motor is connected and free to rotate if necessary.
It.br (19)
I x t on braking resistor

Cause:

Excessive braking resistor energy (Does not apply to Size 1 units).



Remedy:

Check braking cycles and resistor sizing.
It.AC (20)
Motor overload on current x time

Cause:

Too much mechanical load.



Remedy:

Reduce mechanical load or check motor sizing.
Oht1 (21)
Overheat

Cause:

Overheat thermal model.



Remedy:

Check drive ventilation and ambient temperature.
Oht2 (22)
Overheat (heatsink thermistor)

Cause:

Temperature exceeds 95°C (203°F).



Remedy:

Check heatsink cooling and fans.
th (24)
Over temperature (Motor thermistor)

Cause:

Excessive motor temperature.



Remedy:

Check motor cooling and load.
O.Ld1* (26)
+24V or digital output overload

Cause:

Excessive load or short circuit on +24V output.



Remedy:

Check wiring on +24V output.

The Enable/Reset terminal will not reset an O.Ld1 trip. Use the Stop/Reset key.
cL (28)
Current loop loss on terminal 5

Cause:

Input current less than 3mA when 4-20 or 20-4 modes used.



Remedy:

Check current loop signal source and wiring.
SCL (30)
User serial communications watchdog failure

Cause:

Failure of serial communications between Drive and master.



Remedy:

Check serial communication cables and master status.
EEF (31)
Failure of internal EEPROM

Cause:

Possible loss of parameter values.

Corruption due to severe electrical noise.



Remedy:

Set default parameters (see parameter 29).
PH (32)
Phase loss

Cause:

One of the input phases has become disconnected from the Drive. (This applies to 200V/400V three phase units only, not dual rated units).



Remedy:

Check input supply fuses and wiring.
rS (33)
Stator resistance measurement failure

Cause:

Motor cable disconnected during measurement.

Motor too small for Drive.



Remedy:

See parameter 38 for more details.
trxx (40-99)
User trips

Cause:

User trips where xx is the user trip number.



Remedy:

Check user program or PLC logic generating the trip.
F.bus (180)
Field bus disconnection

Cause:

Field bus disconnection whilst in use.



Remedy:

Check field bus cables and connections.
C.Err (182)
Quickey memory corrupt

Cause:

Bad connection or memory corrupt.



Remedy:

Check Quickey insertion or replace Quickey.
C.dat (183)
Quickey with no data

Cause:

New / empty Quickey being read.



Remedy:

Program Quickey before reading.
C.Acc (185)
Quickey write fail

Cause:

Bad connection or faulty Quickey.



Remedy:

Re-insert or replace Quickey.
C.rtg (186)
Quickey voltage rating change

Cause:

Already programmed Quickey read by Drive of different rating.



Remedy:

Use Quickey compatible with drive rating.
O.Ld2 (188)
+28V serial communications power supply overload

Cause:

Overload of more than 110 mA or short circuit on +28V serial communications power supply.



Remedy:

Check serial comms wiring for shorts or excessive load.
O.cL (189)
Current loop input overload

Cause:

Input current exceeded 25mA.



Remedy:

Check current source signal level.
(No Code)
Motor runs unstable

Cause:

Motor or motor connections changed.



Remedy:

Check motor connections.

Re-autotune Drive to motor (see parameter 38).

How to Clear & Reset Nidec Control Techniques Commander SE Faults

  1. Keypad Reset: Press the red Stop / Reset (O) push button on the front control panel. Once the condition is rectified, the drive trip will clear and the display will show InH (Inhibit) or rdy (Ready).
  2. Digital Input Reset (Terminal 11): The default factory configuration assigns Terminal 11 as the Drive Enable / Reset input. Open and close the connection between Terminal 11 and +24V (Terminal 7/8) to clear active trips.
  3. SE Soft / CTSoft PC Tool: Connect your PC via the EIA-485 RJ45 communications port using the SE71 serial lead, open SE Soft / CTSoft, and click “Drive Reset” from the diagnostic toolbar.
  4. Serial / Fieldbus Communication: Toggle the trip reset bit in the serial control word (Pr 06.43 or assigned fieldbus control register via optional Profibus DP SE73, DeviceNet SE77, or Interbus SE74 modules).
  5. Mains Power Cycle: Switch off AC line supply power to the drive. Wait until the 7-segment LED display goes completely dark (minimum 5 minutes for internal DC link capacitors to discharge), then restore AC mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] before opening terminal covers, checking dynamic braking resistors, or touching motor terminals U, V, and W on the Commander SE drive.