Nidec Control Techniques Commander SK drive

Home / Nidec Control Techniques / Nidec Control Techniques Commander SK drive

Nidec Control Techniques Commander SK Drive Trip Codes & Diagnostic Guide

Comprehensive trip code reference directory, diagnostic causes, and step-by-step troubleshooting procedures for the Nidec Control Techniques Commander SK AC drive series. Search or filter through the complete diagnostic directory below.

Compact AC Drive Power: 0.25 to 132 kW (0.33 to 200 HP) Open Loop Vector & V/Hz Control
Power Range 0.25 – 132 kW (0.33 – 200 HP)
Supply Voltage 100V / 200V / 400V / 575V / 690V
Control Modes Open Loop Vector & V/Hz
Operator Interface Built-in LED Keypad / CTSoft

Complete Nidec Control Techniques Commander SK Trip & Fault Code Directory

Use the search box in the table below to quickly find your trip code (e.g., type OI.AC, UU, OU, or It.AC).

Fault Code and MeaningCause and Remedy
UV

DC bus under voltage

Cause:


  • Low AC supply voltage.

  • Low DC bus voltage when supplied by an external DC power supply.




Remedy:

Check power supply voltage and connections.
OV

DC bus over voltage

Cause:


  • Deceleration rate set too fast for the inertia of the machine.

  • Mechanical load driving the motor.




Remedy:

Increase deceleration ramp time or install braking resistor.
OI.AC**

Drive output instantaneous over current

Cause:


  • Insufficient ramp times.

  • Phase to phase or phase to ground short circuit on the drives output.

  • Drive requires autotuning to the motor.




Remedy:


  • Check motor and motor cable for insulation resistance.

  • If motor or motor connections changed, re-autotune drive to motor.


OI.br**

Braking resistor instantaneous over current

Cause:


  • Excessive braking current in braking resistor.

  • Braking resistor value too small.




Remedy:

Check braking resistor value and wiring.
O.SPd

Over speed

Cause:

Excessive motor speed (typically caused by mechanical load driving the motor).



Remedy:

Check mechanical load and speed parameters.
tunE

Auto tune stopped before completion

Cause:

Run command removed before autotune complete.



Remedy:

Restart autotune and maintain run command.
It.br

I2t on braking resistor

Cause:

Excessive braking resistor energy.



Remedy:

Check braking cycle and resistor rating.
It.AC

I2t on drive output current

Cause:


  • Excessive mechanical load.

  • High impedance phase to phase or phase to ground short circuit at drive output.

  • Drive requires re-autotuning to motor.




Remedy:

Reduce load or check motor tuning.
O.ht1

IGBT over heat based on drives thermal model

Cause:

Overheat software thermal model.



Remedy:

Check for blocked vents or fan failure.
O.ht2

Over heat based on drives heatsink

Cause:

Heatsink temperature exceeds allowable maximum.



Remedy:

Reduce ambient temperature or check cooling fans.
th

Motor thermistor trip

Cause:

Excessive motor temperature.



Remedy:

Check motor cooling and load.
O.Ld1*

User +24V or digital output overload

Cause:

Excessive load or short circuit on +24 V output.



Remedy:

Check wiring on user I/O terminals.
O.ht3

Drive over-heat based on thermal model

Cause:

Overheat software thermal model.



Remedy:

Check drive mounting and ventilation.
cL1

Analog input 1 current mode, current loss

Cause:

Input current less than 3 mA when 4-20 or 20-4mA modes selected.



Remedy:

Check signal source and wiring.
SCL

Serial communications loss time-out

Cause:

Loss of communication when drive is under remote control.



Remedy:

Check serial communication cables and master controller.
EEF

Internal drive EEPROM trip

Cause:

Possible loss of parameter values.



Remedy:

Set default parameters (see Pr 29).
PH

Input phase imbalance or input phase loss

Cause:

One of the input phases has become disconnected from the drive (applies to 200/400 V three phase drives only, not dual rated drives).



Remedy:

Check input power supply fuses and wiring.
rS

Failure to measure motors stator resistance

Cause:


  • Motor too small for drive.

  • Motor cable disconnected during measurement.




Remedy:

Check motor rating and connections.
CL.bt

Trip initiated from the control word

Cause:

Control word has initiated a trip.



Remedy:

Check remote control logic.
O.ht4

Power module rectifier over temperature

Cause:

Power module rectifier temperature exceeds allowable maximum.



Remedy:

Check airflow and ambient temperature.
C.dAt

SmartStick data does not exist

Cause:

New/empty SmartStick being read.



Remedy:

Program the SmartStick or use one with valid data.
C.Acc

SmartStick read/write fail

Cause:

Bad connection or faulty SmartStick.



Remedy:

Re-seat SmartStick or replace it.
C.rtg

SmartStick/drive rating change

Cause:

Already programmed SmartStick read by a drive of a different rating.



Remedy:

Use SmartStick compatible with drive rating.
O.cL

Overload on current loop input

Cause:

Input current exceeds 25 mA.



Remedy:

Check analog input source.
HFxx trip

Hardware faults

Cause:

Internal drive hardware fault.



Remedy:

See Commander SK Advanced User Guide.
OVL.d

I x t overload (I = current, t = time)

Cause:

Motor current overload detected.



Remedy:

Reduce motor current (Load).
hot

Heatsink/IGBT temperature high

Cause:

Drive thermal model limits approached.



Remedy:

Reduce ambient temperature or reduce motor current.
br.rS

Braking resistor overload

Cause:

Braking resistor thermal limit approached.



Remedy:

See Menu 10 in the Commander SK Advanced User Guide.
AC.Lt

Drive is in current limit

Cause:

Load requires more current than the limit set.



Remedy:

See Menu 10 in the Commander SK Advanced User Guide.
FAIL

Failed attempt to read stick

Cause:

An attempt has been made to read the stick when the drive was not disabled or tripped, or the stick is read-only.



Remedy:

Ensure drive is disabled before reading SmartStick.

How to Clear & Reset Nidec Control Techniques Commander SK Trips

  1. Keypad Reset: Press the red Stop / Reset button on the drive’s integrated keypad. Note that high-current trips (such as OI.AC or OI.br) impose a 10-second lockout before a reset can be accepted.
  2. Terminal Reset (Enable / Reset): Toggle the terminal assigned to Drive Enable / Reset (Terminal B4 on frame sizes A to D, or your assigned digital input terminal) from low (0V) to high (+24V).
  3. Serial Modbus Reset: Over serial communications (RJ45 port using CT Modbus RTU), write a value of 100 to Parameter Pr 10.38 to remotely reset active drive trips.
  4. CTSoft Software Tool: Connect your PC using the CT Comms cable, open the CTSoft diagnostic window, and trigger the software drive reset command.
  5. Mains Power Cycle: Disconnect AC line input power, wait for the display to extinguish completely (allow at least 5 to 10 minutes for the intermediate DC bus capacitors to discharge safely), and then restore AC mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] (or dynamic braking terminals) before opening terminal covers, checking wiring, or touching motor terminals U, V, and W on the Commander SK drive.