Complete trip code directory, alarm causes, and diagnostic troubleshooting steps for Nidec Control Techniques Commander SX IP66 / NEMA 4X washdown AC drives. Search and filter through the complete diagnostic list below.

IP66 / NEMA 4X Washdown Duty Power: 0.37 to 7.5 kW (0.5 to 10 HP) Cabinet-Free Wall Mount Integrated EMC Filter
Power Range 0.37 – 7.5 kW (0.5 – 10 HP)
Supply Voltage 200–240V / 380–480V AC
Control Modes Open Loop Vector & V/Hz Control
Protection Rating IP66 / NEMA 4X Washdown

Complete Commander SX Trip Code Directory

Use the search box in the table below to quickly find your trip code (e.g., type OI.AC, OV, PSU, th, or Overcurrent).

Fault Code and MeaningCause and Remedy
cL1
ADI1 loss

Cause: Loss of the current reference on analog input ADI1.



Remedy:

  • Check that current is > 3 mA.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


cL2
ADI2 loss

Cause: Loss of the current reference on analog input ADI2.



Remedy:

  • Check that current is > 3 mA.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


cL3
ADIO3 loss

Cause: Loss of the current reference on analog input ADIO3.



Remedy:

  • Check that current is > 3 mA.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


EEF
EEPROM fail.

Cause: Drive rating does not match with XPressKey.



Remedy:

  • Return to default factory settings (see 65).

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


enC2
Encoder rot

Cause: The measured position does not vary (the encoder is incorrectly connected or not supplied with power or the shaft is not turning).



Remedy:

  • Check encoder connections.

  • Check the motor rotation is normal.


EnC1
U sign. loss

Cause: Loss of channel U.



Remedy:

  • Check the speed feedback.

  • Replace the encoder.


EnC2
V sign. loss

Cause: Loss of channel V.



Remedy:

  • Check the encoder voltage and connections.


EnC3
W sign. loss

Cause: Loss of channel W.



Remedy:

  • Check the encoder voltage and connections.


Fbus
Fieldbus loss

Cause: Disconnection of the fieldbus.



Remedy:

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.

  • Check fieldbus connections and status.


It.AC
Motor I²t

Cause: Motor overload I x t.



Remedy:

  • Read the battery value in 4.19.

  • Check that the motor is not overloaded.

  • Adjust the rated speed.

  • Check that the motor rated current is correctly set (06).

  • Speed feedback: check the coupling, and check that the signal is not disturbed.

  • Check the number of motor poles in 62.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


It.br
Brak. resist.

Cause: Braking resistor overload I x t.



Remedy:

  • Read the battery value in 10.39.

  • Increase the resistor ohmic value.

  • Check that 10.30 and 10.31 are set correctly (braking cycle too long).

  • Check the resistor wiring.

  • Check the integrated transistor.


Oht1
Dv over heat

Cause: IGBT overheating (sensor).



Remedy:

  • Reduce the motor load, the cycle, the switching frequency and the acceleration and deceleration ramps.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


Oht2
BR over heat

Cause: Internal resistor overheating (sensor).



Remedy:

  • Reduce the switching frequency.

  • Reduce the cycle and the motor load.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


OI.AC
Over current

Cause: Overcurrent at drive output.



Remedy:

  • Check motor insulation and connection.

  • Increase acceleration and deceleration rates.

  • Check feedback devices.

  • Check motor cable length.

  • Reduce the speed controller gains 29 (3.10), 30 (3.11) and 3.12.

  • If not already set, perform an autotune 63 = 2.

  • Reduce current controller gains 31 (4.13) and 32 (4.14).


OIbr
Brak.IGBT

Cause: IGBT braking overcurrent.



Remedy:

  • Check the resistor insulation.

  • Correct the short-circuit at the resistor output.

  • Set a higher resistor ohmic value.


Old1
24V over Id

Cause: Overload on +24V source or logic output.



Remedy:

  • Check the total current consumption.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


OSP
Over speed

Cause: Overspeed.



Remedy:

  • The speed is higher than 1.2 times the value of 02.

  • Check that the load is not driving.

  • Check that the overspeed threshold has been set correctly.

  • Adjust the speed loop gains.

  • Set a longer deceleration time.


OU
DC over volt

Cause: DC bus overvoltage.



Remedy:

  • Provide a braking resistor (optional). If a resistor is already connected, reduce its value (within permitted limits).

  • Check that the mains supply is not disturbed.

  • Check the motor insulation.

  • Set a longer deceleration time in 04.

  • Check the deceleration mode.


ph
In Ph. loss

Cause: Phase loss. Note: The loss of one phase can only be detected if the active current is between 50% and 100% of the rated value.



Remedy:

  • Check the mains supply (3 phases present and balanced).

  • Check the level of supply voltage (at full load).


Ph.AC
Out Ph. loss

Cause: Motor phase loss.



Remedy:

  • Check the connection of phases U, V and W in both the motor and the drive.


rot
A/B reversed

Cause: The a, b, a\, b\ signals are the wrong way round.



Remedy:

  • Reverse 2 motor phases or 2 encoder channels.


rS
Stator res.

Cause: Stator resistance measurement fault.



Remedy:

  • Adapt the drive power to that of the motor.

  • Check the connection of the motor cables.


SCL
COM loss

Cause: Serial link fault.



Remedy:

  • Replace the keypad or the cable.

  • Check the connectors between the keypad and the drive.

  • Check that the cable is not damaged.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


Secd
Sec.disable

Cause: Secure input fault.



Remedy:

  • Give a stop command before enabling the drive.


Th
Motor PTC

Cause: Motor sensor trip.



Remedy:

  • Check the motor load.

  • Reduce the level of overload.

  • Check the motor cooling and the ambient temperature.

  • Check the wiring of the ADI2 terminal on the control terminal block.

  • If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


tr01 - tr10
User 1 - 10

Cause: User fault 1 through 10 via logic input or serial link.



Remedy:

  • Check logic inputs or serial communications.

  • For tr05, tr10: If 10.37 = 1 (Ctld), the drive decelerates the motor without tripping.


tun3
UVW revers.

Cause: The u, v, w switching signals are the wrong way round.



Remedy:

  • Check encoder and motor connections.


tun4
U sign.miss.

Cause: Some signals are present, but U is missing.



Remedy:

  • Check encoder connections.


tun5
V sign.miss.

Cause: Some signals are present, but V is missing.



Remedy:

  • Check encoder connections.


tun6
W sign.miss.

Cause: Some signals are present, but W is missing.



Remedy:

  • Check encoder connections.


tun7
Pole count

Cause: The number of pairs of poles set is incorrect (the revolutions measured mechanically and electrically are inconsistent).



Remedy:

  • Check encoder lines per revolution.

  • Verify 5.11 (62) "number of motor poles" setting.


tunE
Autotun. fail

Cause: Autocalibration error.



Remedy:

  • Drive set to fault mode during the autocalibration phase.

  • The Stop key has been pressed.

  • The SDI2 contact has been opened during the autocalibration phase.


UU
Under volt.

Cause: DC bus undervoltage.



Remedy:

  • Check the mains supply.


How to Clear & Reset Commander SX Drive Trips

  1. Keypad Reset: Press the red Stop / Reset key on the integrated front keypad. If the drive is running in keypad mode, press once to stop and a second time to clear the active trip.
  2. Terminal Input Reset: Remove the drive run signal or toggle an assigned digital input programmed as a trip reset (Parameter 10.38 / User Trip Reset).
  3. SXSoft PC Software: Connect via the serial communications interface using an RS485 converter lead, open SXSoft or CTSoft, and click “Reset Drive” on the live monitor panel.
  4. Serial Fieldbus (Modbus RTU): Send a trip reset command by writing a transition from `0` to `1` on the control word reset bit (Bit 3 in Parameter 06.42) via Modbus RTU communications.
  5. Line Power Cycle: Switch off the main AC line supply to the drive. Wait until all internal LEDs and display characters turn off completely (allow at least 5 minutes for complete discharge of the internal bus capacitors) before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Although the Commander SX features an IP66/NEMA 4X washdown enclosure, dangerous DC bus voltages remain inside after removing main AC supply power. Before opening the housing cover or working on power terminals (+DC, -DC, U, V, W), isolate the AC feed and confirm with a calibrated digital multimeter that intermediate DC bus voltage has discharged below 50VDC.