Nidec Control Techniques Digitax SF Fault Codes & Diagnostic Guide
Complete numeric alarm code directory, diagnostic causes, pulse/analog error troubleshooting, and step-by-step reset procedures for the Nidec Control Techniques Digitax SF servo drive series. Search or filter through the complete fault code database below.
Power Range
50 W – 2 kW (0.05 – 2 kW)
Supply Voltage
200 – 240V AC (1Ø / 3Ø)
Control Modes
Position, Velocity & Torque
Operator Interface
Built-in LED Panel / Digitax SF Connect
Complete Nidec Control Techniques Digitax SF Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type AL.01, AL.07, AL.20, or Overload).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 900 Encoder overheat detection | Cause: The temperature inside the absolute encoder has exceeded the temperature value specified by Encoder: Overheat detection - Value (267.0). An alarm can be output in place of the warning. Remedy: Reduce the ambient temperature and improve thermal radiation conditions. Check the setting of Encoder: Overheat detection - Value (267.0). Reset Method: After eliminating the cause, then input RESET signal to the RESET terminal on the connector CN1. |
| 901 Encoder battery voltage drop error detection | Cause: The battery voltage of the absolute encoder has dropped below the voltage set by Encoder: Battery voltage drop detection - Value (268.0). Remedy: Replace the battery in the absolute encoder. Check the Encoder: Battery voltage drop detection - Value (268.0). Reset Method: After eliminating the cause, then input RESET signal to the RESET terminal on the connector CN1. |
| 902 Emergency stop | Cause: The E-STOP control terminal digital input is open. Remedy: Close the E-STOP control terminal digital input. Check for proper I/O connections. Reset Method: After eliminating the cause, then input RESET signal to the RESET terminal on the connector CN1. |
| 903 Encoder communication warning | Cause: Failed to obtain ABS encoder temperature and battery voltage data. Remedy:
Reset Method: After eliminating the cause, then input RESET signal to the RESET terminal on the connector CN1. |
| 904 Excessive position error | Cause: The position error consecutively exceeded the setting of Position error warning detection: Value (363.0) and the setting of Position error warning detection: Delay time (365.0). Remedy:
Reset Method: After eliminating the cause, then input RESET signal to the RESET terminal on the connector CN1. |
| Alarm No. 0 System | Cause: Error in the control circuit. The control circuit CPU is not operating normally. Remedy: Please contact the supplier of the drive. |
| Alarm No. 1 EEPROM data | Cause: Error during writing of Parameters. Remedy: Check the interface cable and re-write the parameters. |
| Alarm No. 2 Product code | Cause:
Remedy: Check the motor-drive pairing. Check the encoder cable connections. |
| Alarm No. 4 Overspeed | Cause:
Remedy:
|
| Alarm No. 5 Speed | Cause: Position control/Speed control error.
Remedy:
|
| Alarm No. 6 Position | Cause: Position Control Error.
Remedy:
|
| Alarm No. 7 Overload | Cause:
Remedy: Executing overloaded motion continuously may burnout the motor.
|
| Alarm No. 8 Command overspeed | Cause:
Remedy: Check the Pulse train command: Ratio (34.0 and 36.0). Check the commands from the host controller. |
| Alarm No. 9 Encoder pulse - Output frequency error | Cause: The frequency of the encoder pulse output exceeded 4 Mpps. Remedy:
|
| Alarm No. 10 Positioning command overflow /Homing failure | Cause:
Remedy:
|
| Alarm No. 11 Encoder (multi-turn counter overflow) | Cause: Multi-turn data of the encoder has exceeded the ±32,767 range. Remedy: Check the setting of Absolute system (257.0). Verify that the multi-turn motion amount is within the ±32,767 range. |
| Alarm No. 12 Overheat | Cause: The control circuit temperature has exceeded the upper limit. Remedy: Check the drive's installation method and environment. Lower the ambient temperature to below the rating. |
| Alarm No. 14 Overvoltage | Cause: The power supply to the control components has exceeded the drive circuit limits. Remedy:
|
| Alarm No. 15 Power supply (AC Supply) | Cause:
Remedy:
|
| Alarm No. 16 Encoder (received data) | Cause: Encoder data changed rapidly for a short period of time. Remedy:
|
| Alarm No. 17 Encoder (no response) | Cause: Encoder communications were disconnected. Remedy: See remedy for Alarm No. 16 (Check wiring, noise, grounding, cable length). |
| Alarm No. 18 Encoder (circuit) | Cause:
Remedy:
|
| Alarm No. 19 Encoder (communication) | Cause: The initial communication with the encoder failed. Remedy: See remedy for Alarm No. 16 (Check wiring, noise, grounding, cable length). |
| Alarm No. 20 Encoder (multi-turn data) | Cause: Absolute encoder data changed rapidly. At startup, failed to receive multi-turn data internally. Remedy: See remedy for Alarm No. 16 (Check wiring, noise, grounding, cable length). |
| Alarm No. 21 Encoder (voltage drop) | Cause: The battery voltage dropped or became disconnected. It was the first start-up after battery connection. Remedy: Check for low battery voltage. Check for loose battery cable. Initialize the encoder. |
| Alarm No. 22 Voltage (control power) | Cause: The control power supply dropped. Remedy:
|
| Alarm No. 23 Switch circuit | Cause: Control circuit has failed. Remedy: Please contact the supplier of the drive. |
| Alarm No. 24 Overcurrent | Cause: Anomaly of motor control current inside of the drive has been detected. Remedy:
|
| Alarm No. 25 Inverter 1 | Cause: Anomaly in the control circuit has been detected. Remedy:
|
| Alarm No. 26 Inverter 2 | Cause: Anomaly in the control circuit has been detected. SERVO ON timed out. Remedy:
|
| Alarm No. 27 Current sensor | Cause: The ambient temperature of the current sensor was high. Anomaly of the current sensor has been detected. Remedy: Check the installation method and environment. If unresolved, contact supplier. |
| Alarm No. 28 Encoder (overheat) | Cause: The encoder PCB temperature has reached the upper limit. Remedy: Check the installation method and environment of the motor. Decrease the ambient temperature of the motor below the specification. |
| Alarm No. 29 Voltage drop (inside the drive) | Cause: The control power voltage (5 VDC) inside the drive has dropped. Remedy: Verify that there is no short-circuit in encoder cable connections. If the above didn't resolve the issue, please contact the supplier of the drive. |
How to Clear & Reset Digitax SF Servo Drive Faults
- CN1 User I/O Reset (ALM-RST): Assert the assigned Alarm Reset digital input pin on the CN1 control connector to clear latching drive alarms once the root cause has been addressed.
- Setup Panel Keypad Reset: Navigate through the front 6-digit LED display panel buttons to acknowledge and clear recoverable alarms.
- Digitax SF Connect PC Tool: Connect your PC via the USB/RS-485 interface, open Digitax SF Connect software, and execute an Alarm Reset in the Status Monitor window.
- Encoder Clear Auxiliary Function: For absolute multi-turn encoder alarms (e.g., battery low or position data errors), execute the Encoder Clear command under the software’s Auxiliary Functions tab, then cycle control power.
- Power Cycle: Disconnect both the main 200V AC power and 24V DC control power, wait for the LED display to turn off completely (allow at least 5 minutes for bus discharge), and reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage has discharged strictly below 50VDC across main power and motor terminals before disconnecting cables, checking wiring, or touching motor terminals U, V, and W on the Digitax SF drive.