Nidec Control Techniques NE200 & NE300 drive

Home / Nidec Control Techniques / Nidec Control Techniques NE200 & NE300 drive

Nidec Control Techniques NE200 & NE300 Fault Codes & Diagnostic Guide

Complete trip alarm reference table, root causes, and diagnostic reset procedures for the Nidec Control Techniques NE200 compact and NE300 high-performance vector AC drive family. Search or filter through the complete trip list below.

Universal Vector AC Drives Power: 0.4 to 900 kW (0.5 to 1,200 HP) V/F, Open Loop SVC & Closed Loop VC
Power Range 0.4 – 900 kW (0.5 – 1200 HP)
Supply Voltage 200–240V / 380–440V (1Ø / 3Ø)
Control Modes Sensorless Vector, VC & V/Hz
Operator Interface LED Keypad w/ Digital Potentiometer

Complete Nidec Control Techniques NE200 & NE300 Trip Directory

Use the search box in the table below to quickly find your trip code (e.g., type OC1, OU2, OL2, or Overcurrent).

Fault Code and MeaningCause and Remedy
Uu1
Bus Under voltage during running

Cause:


Power grid low voltage.



Remedy:

  • Check the input power source.


OC1
Over current in Acceleration

Cause:


1. Acceleration time too short.

2. Power grid low voltage.

3. Inverter power rating too small.



Remedy:

  • Increase the acceleration time.

  • Check the input power source.

  • Choose inverter with higher capacity.


OC2
Over current in Deceleration

Cause:


1. Deceleration time too short.

2. Large load inertia.

3. Inverter power rating too small.



Remedy:

  • Increase the deceleration time.

  • Add suitable brake devices.

  • Choose higher capacity drive.


OC3
Over current at constant-speed

Cause:


1. Abnormal Load mutation.

2. Power grid low voltage.

3. Inverter power rating too small.

4. Encoder sudden offline in closed-loop vector control.



Remedy:

  • Check the load.

  • Check the input power source.

  • Choose higher capacity drive.

  • Check the encoder and its wiring.


Ou1
Over Voltage in Acceleration

Cause:


1. Acceleration time too short.

2. Power supply abnormal.



Remedy:

  • Increase the acceleration time.

  • Check the input power source.


Ou2
Over voltage in deceleration

Cause:


1. Deceleration time too short.

2. Large load inertia.



Remedy:

  • Increase the deceleration time.

  • Add suitable brake devices.


Ou3
Over voltage in constant speed

Cause:


1. Power supply abnormal.

2. Large load inertia.



Remedy:

  • Check the input power source.

  • Add suitable braking devices.


GF (NE300 Only)
Ground Fault

Cause:


1. One output phase got short circuit problem.



Remedy:

  • Check whether the electric motor insulation is weakening.

  • Check whether the wiring between the frequency converter and the electric motor is damaged.


SC
Load short-circuit

Cause:


1. Wiring of inverter and motor get phase-to-phase short circuit.

2. Damage of the inverting module IGBT.



Remedy:

  • Check whether the electric motor coil is short circuit.

  • Ask for the services from manufactures.


OH1
Heat-sink over heat

Cause:


1. Ambient temperature too high.

2. Fan is damaged.

3. Fan air duct is blocked.



Remedy:

  • Lower the ambient temperature.

  • Change the fan.

  • Clear the air duct.


OL1
Motor overload

Cause:


1. Power supply abnormal.

2. Motor rated current set wrongly.

3. The Curve of V/F is not fit.

4. Motor always works with heavy load at low speed.

5. Motor blocked to stall or sudden large load change.

6. Motor power too low.



Remedy:

  • Check the input power source.

  • Check whether the motor’s rated current is correctly set up.

  • Adjust the V/F curve and torque boosting performance.

  • Use specialized electric motor.

  • Check whether the motor or the load is blocked to stall or not.

  • Use motor and inverter of suitable power ratings.


OL2
Inverter overload

Cause:


1. Low voltage in power grid.

2. Load too heavy.

3. Acceleration too fast.

4. Restart the motor still in turning.



Remedy:

  • Check the input power source.

  • Select bigger capacity inverter.

  • Increase the acceleration time.

  • Avoid restarting when the motor is in rotation.


EF0
Communication fault

Cause:


1. Baud rate and parity checksum is set incorrect.

2. Communication interrupted for long time.



Remedy:

  • Check communication parameters correct or not.

  • Check the interface wiring.


EF1
External terminal fault

Cause:


1. Faults comes from external control circuit.



Remedy:

  • Check the external input.


SP1
Input phase loss

Cause:


1. Input R,S,T have phase loss or imbalance.



Remedy:

  • Check input voltage.


SPO
Output phase loss

Cause:


1. There is lack of U,V,W when output.

2. There is a serious unbalance in output.



Remedy:

  • Check U-V-W motor wiring.

  • Check the load.


EEP
EEPROM error

Cause:


1. Function code parameter writing error.

2. EEPROM damaged.



Remedy:

  • Recover factory defaults.

  • Ask for service from supplier.


CCF
Keypad & control board communication interrupted

Cause:


1. Connection cable between keyboard and control panel is broken.



Remedy:

  • Check the connection cable between keyboard and control panel.


bCE
Brake unit fault

Cause:


1. The braking line or braking pipe is broken.

2. Brake resistor is too lower.



Remedy:

  • Check the brake unit, change the brake pipe.

  • Choose the suitable braking resistor.


PCE
Parameter copy Error

Cause:


1. Too long connection cable between keypad and control board leads to interference in parameters transmission.

2. The downloading parameters do not match the existed parameters in the inverter.



Remedy:

  • Shorten the cable between Keyboard and control board to reduce interference.

  • Before downloading, make sure the parameters match the inverter.


IDE
IDE Hall current detection fault

Cause:


1. The current sensoring or hall device get damaged.



Remedy:

  • Ask for service from supplier.


ECE (NE300 Only)
Encoder fault

Cause:


1. Encoder signal wires are connected reversely.

2. Encoder signal wires get damaged.

3. Encoder damaged.

4. Dual-way encoder detected motor direction is not match.



Remedy:

  • Check whether the encoder signal is correctly connected.

  • Check whether the encoder wiring is broke.

  • Change the encoder.

  • Change the encoder direction (F3.16) or alter motor wiring sequence.


LC
Fast current limit fault

Cause:


1. Load too large or motor blocked to stall.

2. Inverter power rating too small.

3. Inverter output circuit loop grounded or SC.



Remedy:

  • Decrease the load and check motor and mechanical part status.

  • Choose higher power inverter.

  • Remove the external fault.


EF2
Terminal close fault

Cause:


1. The FWD or REV terminals close and get power on. But inverter is set to not allow the restart after power failure recovery.



Remedy:

  • Disconnect the FWD or REV terminal first and then power on the inverter.

  • Close the fault detection function for closed terminal fault (FC.11=0).


PIDE
PID feedback error

Cause:


1. PID feedback offline.



Remedy:

  • Check PID feedback line.

  • Disable PID feedback detection (F8.24=0.0%).

  • Increase PID feedback offline detection time (F8.25).


OLP2
Overload pre-alarm error

Cause:


1. Frequency inverter output current is higher than set pre-alarm threshold.



Remedy:

  • Disable pre-alarm function (FC.19=0).

  • Increase pre-alarm threshold value (FC.02).

  • Increase pre-alarm detection time (FC.03).


How to Clear & Reset Nidec Control Techniques NE200 & NE300 Faults

  1. Keypad Reset: Press the red STOP / RESET key on the front LED operation panel. Once the underlying fault condition is resolved, the trip indicator will clear and the display will return to normal stop status.
  2. Digital Input Reset (Terminal X1–X6): Configure any multi-function digital input terminal (parameters F1.00 to F1.05) to function code 9 (Fault Reset). Pulse this terminal high relative to COM to clear active alarms remotely.
  3. Diagnostic Parameter Verification: Access parameter group FA (Fault Records) via the keypad. Inspect parameter FA.00 (Most recent fault code), FA.01 (Frequency at trip), and FA.02 (Output current at trip) to confirm root causes before resetting.
  4. Modbus RTU Reset (RS485): Send the fault reset bit command via the integrated RS485 communication port using standard Modbus RTU communication control registers.
  5. AC Mains Power Cycle: Turn off main incoming AC line power. Wait until the LED display and cooling fans turn off completely (approx. 5 minutes for intermediate DC capacitors to safely discharge), then re-apply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [(+)] and [(-)] or [(+)] and [PB] before touching terminals U, V, and W, checking dynamic braking resistors, or servicing motor cabling on the NE200 & NE300 drive.