Omron Drives Fault Codes & Troubleshooting

Complete diagnostic database for 5 Omron inverter & servo drive series. Browse fault codes, trip errors, causes, and step-by-step fixes for industrial AC variable speed inverters and high-precision servo motion systems. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

3 Inverter Series 2 Servo Motion Drives 5 Total Series

Omron AC Variable Frequency Inverters

3 Models

Omron AC Servo Drives & Motion Systems

2 Models

Most Common Omron Drive Fault Codes

Diagnostic Quick Reference
Inverter Code Servo Alarm Fault Name Common Root Cause
E01 – E04 Err 12.0 Overcurrent Protection Instantaneous peak current exceeded rated limit; output motor phase short circuit, rapid acceleration ramp, or locked rotor.
E07 Err 18.0 Overvoltage Protection DC link voltage exceeded upper threshold; high regenerative energy during motor deceleration, or dynamic brake resistor circuit open.
E09 Err 13.1 Undervoltage Protection DC link voltage dropped below allowable limit; utility power line dip, loose incoming line terminals (R/L1, S/L2, T/L3), or blown input fuse.
E05 Err 16.0 Overload Protection Drive or motor electronic thermal overload tripped; mechanical friction overload or improper motor nameplate parameter configuration.
E14 Err 14.0 Ground Fault Protection Ground leakage current detected at inverter output; cracked motor cable insulation or moisture in motor terminal housing.
E21 Err 15.0 Inverter Heatsink Overheat Internal temperature exceeded safety threshold; defective cooling fan, clogged heat sink fins, or cabinet ambient temperature exceeding 50°C.

How to Clear & Reset Omron Faults

  1. Keypad Reset: Press the red STOP/RESET key on the front digital operator keypad once the underlying abnormal condition is cleared.
  2. Multi-Function Reset Input (RS): Send a 24VDC pulse to the multi-function terminal configured for Reset (default multi-function input terminal configured to parameter C001–C007 set to option 18: RS (Reset)).
  3. Sysmac Studio / CX-Drive Software: Connect via USB or EtherCAT, open the diagnostic status window inside Sysmac Studio or CX-Drive, and click “Fault Reset”.
  4. Mains Power Cycle: Turn off main 3-phase AC power, wait 5 minutes until the charge indicator LED completely extinguishes, and restore power.
⚠️ High-Voltage Safety Warning: High voltage remains stored in the intermediate circuit DC bus capacitors even after incoming AC power is turned off. Always wait until the red CHARGE indicator LED is completely unlit, and verify with a calibrated digital multimeter that the voltage across terminals (+1/+) and (-) is strictly below 50VDC before inspecting internal connections or motor terminals.