Panasonic MINAS A5 Servo Drive Fault Codes & Diagnostic Guide
Complete error code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Panasonic MINAS A5 AC servo driver series. Search or filter through the complete error code directory below.
Power Range
50 W – 15.0 kW
Supply Voltage
100V / 200V / 400V AC
Control Modes
Position, Speed, Torque & Full-Closed
Operator Interface
5-Digit 7-Segment LED / PANATERM
Complete Panasonic MINAS A5 Servo Drive Fault Code Directory
Use the search box in the table below to quickly find your error code (e.g., type Err 12.0, Err 14.0, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Err11.0 Control power supply under-voltage protection | Cause: Voltage between P and N of the converter portion of the control power supply has fallen below the specified value.
Remedy: Measure the voltage between lines of connector and terminal block (100V/200V: L1C-L2C; 400V: 24V-0V).
|
| Err12.0 Over-voltage protection | Cause: Voltage between P and N of the converter portion of the control power supply has exceeded the specified value.
Remedy: Measure the voltage between lines of connector (L1, L2 and L3).
|
| Err13.0 Main power supply under-voltage protection (PN) | Cause: Instantaneous power failure occurred between L1 and L3 for longer than preset time, or voltage between P and N fell below specified value during Servo-ON.
Remedy: Measure voltage between L1, L2 and L3.
|
| Err13.1 Main power supply under-voltage protection (AC) | Cause: AC power supply issues similar to PN under-voltage.
Remedy: Refer to measures for Code 13.0.
|
| Err14.0 Over-current protection | Cause: Current through the converter portion has exceeded the specified value.
Remedy:
|
| Err14.1 IPM error protection (Intelligent Power Module) | Cause: IPM has detected an error (Over-current, Over-heat, or Control supply under-voltage). Remedy: Refer to remedies for Over-current (14.0) or Over-heat (15.0).
|
| Err15.0 Over-heat protection | Cause: Temperature of the heat sink or power device has risen over the specified temperature.
Remedy:
|
| Err16.0 Over-load protection | Cause: Torque command value exceeded over-load level set with Pr5.12.
Remedy: Note: Cannot be cleared for at least 10 sec.
|
| Err16.1 Torque saturation anomaly protection | Cause: Torque saturation has continued for the time set in Pr6.57. Remedy:
|
| Err18.0 Over-regeneration load protection | Cause: Regenerative energy has exceeded the capacity of regenerative resistor.
Remedy: Check load factor of regenerative resistor via front panel or communication.
|
| Err18.1 Regenerative transistor error protection | Cause: Regenerative driver transistor on the servo driver is defective. Remedy:
|
| Err21.0 Encoder communication disconnection error protection | Cause: Communication between encoder and driver interrupted; disconnection detected. Remedy:
|
| Err21.1 Encoder communication error protection | Cause: Communication error occurred in data from encoder. Mainly data error due to noise. Remedy:
|
| Err23.0 Encoder communication data error protection | Cause: Data communication is normal, but contents of data are not correct. Mainly due to noise. Remedy:
|
| Err24.0 Position deviation excess protection | Cause: Deviation pulses have exceeded the setup of Pr0.14.
Remedy:
|
| Err24.1 Velocity deviation excess protection | Cause: Difference between internal positional command speed and actual speed exceeds setup of Pr6.02. Remedy:
|
| Err25.0 Hybrid deviation excess error protection | Cause: Position of load (external scale) and position of motor (encoder) slips larger than setup pulses (Pr3.28).
Remedy:
|
| Err26.0 Over-speed protection | Cause: The motor rotational speed has exceeded the setup value of Pr5.13. Remedy:
|
| Err26.1 2nd Over-speed protection | Cause: The motor rotational speed has exceeded the setup value of Pr6.15. Remedy:
|
| Err27.0 Command pulse input frequency error protection | Cause: The frequency of command pulse input is more than 1.2 times the setting in Pr5.32. Remedy:
|
| Err27.2 Electronic gear error protection | Cause: Division and multiplication ratio set with command pulse counts per single turn are not appropriate.
Remedy:
|
| Err28.0 Pulse regeneration limit protection | Cause: The output frequency of pulse regeneration has exceeded the limit. Remedy:
|
| Err 29.0 Deviation counter overflow protection | Cause: Positional deviation of encoder pulse reference has exceeded 2^29 (536870912). Remedy:
|
| Err 30.0 Safety input protection | Cause: Input photocoupler of both or one of safety input 1 and 2 is OFF. Remedy: Check wiring of safety input 1 and 2. |
| Err 33.0 I/F input duplicated allocation error 1 protection | Cause: Input signals (SI1, SI2, SI3, SI4, SI5) are assigned with two functions. Remedy: Allocate correct function to each connector pin. |
| Err 33.1 I/F input duplicated allocation error 2 protection | Cause: Input signals (SI6, SI7, SI8, SI9, SI10) are assigned with two functions. Remedy: Allocate correct function to each connector pin. |
| Err 33.2 I/F input function number error 1 protection | Cause: Input signals (SI1, SI2, SI3, SI4, SI5) are assigned with undefined number. Remedy: Allocate correct function to each connector pin. |
| Err 33.3 I/F input function number error 2 protection | Cause: Input signals (SI6, SI7, SI8, SI9, SI10) are assigned with undefined number. Remedy: Allocate correct function to each connector pin. |
| Err 33.4 I/F output function number error 1 protection | Cause: Output signals (SO1, SO2, SO3) are assigned with undefined number. Remedy: Allocate correct function to each connector pin. |
| Err 33.5 I/F output function number error 2 protection | Cause: Output signals (SO4, SO5, SO6) are assigned with undefined number. Remedy: Allocate correct function to each connector pin. |
| Err 33.6 CL assignment error | Cause: Counter clear function is assigned to a signal number other than SI7. Remedy: Allocate correct function to each connector pin. |
| Err 33.7 INH assignment error | Cause: Command pulse inhibit input function is assigned to a signal number other than SI10. Remedy: Allocate correct function to each connector pin. |
| Err 34.0 Software limit protection | Cause: When a position command within the specified input range is given, the motor operates outside its working range specified in Pr5.14. 1) Gain is not appropriate. 2) Pr5.14 setup value is low. Remedy:
|
| Err 36.0 / 36.1 / 36.2 EEPROM parameter error protection | Cause: Data in parameter storage area has been damaged when reading the data from EEPROM at power-on. Remedy:
|
| Err 37.0 / 37.1 / 37.2 EEPROM check code error protection | Cause: Data for writing confirmation to EEPROM has been damaged when reading the data from EEPROM at power-on. Remedy: Replace the driver. (it may be a failure). Return the product to a dealer or manufacturer. |
| Err 38.0 Over-travel inhibit input protection | Cause: With Pr5.04, over-travel inhibit input setup = 0, both positive and negative over-travel inhibit inputs (POT/NOT) have been ON. With Pr5.04 = 2, positive or negative over-travel inhibit input has turned ON. Remedy: Check that there are not any errors in switches, wires or power supply which are connected to positive direction/ negative direction over-travel inhibit input. Check that the rising time of the control power supply (DC12 V to 24 V) is not slow. |
| Err 39.0 Analog input 1 (AI1) excess protection | Cause: Higher voltage has been applied to the analog input 1 than the value that has been set by Pr4.24. Remedy:
|
| Err 39.1 Analog input 2 (AI2) excess protection | Cause: Higher voltage has been applied to the analog input 2 than the value that has been set by Pr4.27. Remedy:
|
| Err 39.2 Analog input 3 (AI3) excess protection | Cause: Higher voltage has been applied to the analog input 3 than the value that has been set by Pr4.30. Remedy:
|
| Err 40.0 Absolute system down error protection | Cause: Voltage of the built-in capacitor has fallen below the specified value because the power supply or battery for the absolute encoder has been down. Remedy: After connecting the power supply for the battery, clear the absolute encoder. (Note: Once this error occurs, the alarm cannot be cleared until the absolute encoder is reset). |
| Err 41.0 Absolute counter over error protection | Cause: Multi-turn counter of the absolute encoder has exceeded the specified value. Remedy:
|
| Err 42.0 Absolute over-speed error protection | Cause: The motor speed has exceeded the specified value when only the supply from the battery has been supplied to 17-bit encoder during the power failure. Remedy:
(Note: Once this error occurs, the alarm cannot be cleared until the absolute encoder is reset). |
| Err 43.0 Encoder initialization error protection | Cause: Encoder initialization error was detected. Remedy: Replace the motor. |
| Err 44.0 Absolute single turn counter error protection | Cause: Absolut: single turn counter error protection. Incremental: single turn counter error protection. Remedy: Replace the motor. |
| Err 45.0 Absolute multi-turn counter error protection | Cause: Absolut: multi-turn counter error protection. Incremental: single turn counter error protection. Remedy: Replace the motor. |
| Err 47.0 Absolute status error protection | Cause: Encoder has been running at faster speed than the specified value at power-on. Remedy: Arrange so as the motor does not run at power-on. |
| Err 48.0 Encoder Z-phase error protection | Cause: Missing pulse of Z-phase of serial incremental encoder has been detected. The encoder might be a failure. Remedy: Replace the motor. |
| Err 49.0 Encoder CS signal error protection | Cause: CS signal logic error of serial incremental encoder has been detected. The encoder might be a failure. Remedy: Replace the motor. |
| Err 50.0 Feedback scale wiring error protection | Cause: Communication between the external scale and the driver has been interrupted in certain times, and disconnection detecting function has been triggered. Remedy:
|
| Err 50.1 External communication data error protection | Cause: Communication error has occurred in data from the external scale. Mainly data error due to noise. External scale cables are connected, but communication date has some error. Remedy:
|
| Err 51.0 External scale status 0 error protection | Cause: Bit 0 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 51.1 External scale status 1 error protection | Cause: Bit 1 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 51.2 External scale status 2 error protection | Cause: Bit 2 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 51.3 External scale status 3 error protection | Cause: Bit 3 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 51.4 External scale status 4 error protection | Cause: Bit 4 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 51.5 External scale status 5 error protection | Cause: Bit 5 of the external scale error code (ALMC) has been turned to 1. Check the specifications of the external scale. Remedy: Remove the causes of the error, then clear the external scale error from the front panel. And then, shut off the power to reset. |
| Err 55.0 A-phase wiring error protection | Cause: A-phase wiring in the external scale is defective, e.g. discontinued. Remedy: Check the A-phase wiring connection. |
| Err 55.1 B-phase wiring error protection | Cause: B-phase wiring in the external scale is defective, e.g. discontinued. Remedy: Check the B-phase wiring connection. |
| Err 55.2 Z-phase wiring error protection | Cause: Z-phase wiring in the external scale is defective, e.g. discontinued. Remedy: Check the Z-phase wiring connection. |
| Err 87.0 Forced alarm input protection | Cause: Forced alarm input (E-STOP) is applied. Remedy: Check the wiring of forced alarm input (E-STOP). |
| Err 95.0 to 95.4 Motor automatic recognition error protection | Cause: The motor and the driver has not been matched. Remedy: Replace the motor which matches to the driver. |
| Err 99.0 Other error | Cause: Excessive noise or the like is detected as an abnormal signal. This type of error will occur if the alarm clear is attempted while the safety input 1/safety input 2 is not in normal state (input photocoupler is ON). Remedy:
|
| Other No. Control circuit malfunction | Cause: Control circuit has malfunctioned due to excess noise or other causes. Some error has occurred inside of the driver while triggering self-diagnosis function of the driver. Remedy:
|
How to Clear & Reset Panasonic MINAS A5 Servo Drive Faults
- Front Panel Clear (Auxiliary Mode): Press the MODE button on the front console until auxiliary function mode (
AF_ACL) appears. Press the SET button to enter the alarm clear screen, then press and hold the ▲ (UP) button for approximately 5 seconds until the display showsStOPorCLEAr. - Digital Input Reset (A-CLR): Trigger the Alarm Clear input signal (A-CLR) allocated on control connector X4 (Pin 31 by default). Maintain the signal input for at least 120 ms after eliminating the root cause. (Note: Critical alarms such as Err 14.0 Overcurrent or Err 15.0 Overload cannot be cleared via A-CLR and require a power cycle).
- PANATERM PC Software: Connect a PC via USB (connector X1 mini-B), open Panasonic PANATERM software, navigate to the Monitor & Diagnostics window, and select “Alarm Clear”.
- Network / Fieldbus Control: On network communication models (e.g., MINAS A5B EtherCAT or MINAS A5N MECHATROLINK), write a transition from `0` to `1` on Bit 7 (Fault Reset) of the CiA402 Controlword.
- Control & Main Power Cycle: For non-resettable protective functions, turn off both the main line power supply (L1, L2, L3) and control power supply (L1C, L2C). Wait until the front panel CHARGE LED turns off completely (approx. 10 to 15 minutes), rectify the fault condition, and restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify that the red CHARGE LED located on the driver front panel is fully extinguished, and use a calibrated digital multimeter to confirm that the DC bus voltage across terminals [P] and [N] is safely below 50VDC before inspecting motor terminals (U, V, W), internal braking resistors, or main power input lines.