ABB ACH480 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the ABB ACH480 dedicated HVAC and building automation drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 22 kW (1 – 30 HP)
Supply Voltage
380–480V AC (3-Phase)
Control Modes
Scalar & Vector Control
Operator Interface
HVAC Control Panel (ACH-AP-H)
Complete ABB ACH480 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type 2310, 3210, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| A2B1 Overcurrent | Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this warning may also be caused by an earth fault or supply phase loss. Remedy:
|
| A2B3 Earth leakage | Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable. Remedy:
|
| A2B4 Short circuit | Cause: Short-circuit in motor cable(s) or motor. Remedy:
|
| A2BA IGBT overload | Cause: Excessive IGBT junction to case temperature. This warning protects the IGBT(s) and can be activated by a short circuit in the motor cable. See also aux codes: 0001 (U-phase upper), 0002 (U-phase lower), 0004 (V-phase upper), etc. Remedy:
|
| A3A1 DC link overvoltage | Cause: Intermediate circuit DC voltage too high (when the drive is stopped). Remedy:
|
| A3A2 DC link undervoltage | Cause: Intermediate circuit DC voltage too low (when the drive is stopped). Remedy:
|
| A3AA DC not charged | Cause: The voltage of the intermediate DC circuit has not yet risen to operating level. Remedy:
|
| A490 Incorrect temperature sensor setup | Cause: Temperature cannot be supervised due to incorrect adapter setup. Remedy:
|
| A491 External temperature 1 (Editable message text) | Cause: Measured temperature 1 has exceeded warning limit. Remedy:
|
| A492 External temperature 2 (Editable message text) | Cause: Measured temperature 2 has exceeded warning limit. Remedy:
|
| A4A0 Control board temperature | Cause: Control board temperature is too high. Aux codes: - (none): Temperature above warning limit - 0001: Thermistor broken Remedy:
|
| A4A1 IGBT overtemperature | Cause: Estimated drive IGBT temperature is excessive. Remedy:
|
| A4A9 Cooling | Cause: Drive module temperature is excessive. Remedy:
|
| A4B0 Excess temperature | Cause: Power unit module temperature is excessive. Remedy:
|
| A4B1 Excess temperature difference | Cause: High temperature difference between the IGBTs of different phases. Remedy:
|
| A4F6 IGBT temperature | Cause: Drive IGBT temperature is excessive. Remedy:
|
| A581 Fan | Cause: Cooling fan feedback missing. Remedy:
|
| A5A0 Safe torque off (Programmable warning 31.22) | Cause: Safe torque off function is active, i.e., safety circuit signal(s) connected to connector STO is lost. Remedy:
|
| A5EA Measurement circuit temperature | Cause: Problem with internal temperature measurement of the drive. Remedy:
|
| A5EB PU board powerfail | Cause: Power unit power supply failure. Remedy:
|
| A5ED Measurement circuit ADC | Cause: Measurement circuit fault. Remedy:
|
| A5EE Measurement circuit DFF | Cause: Measurement circuit fault. Remedy:
|
| A5EF PU state feedback | Cause: State feedback from output phases does not match control signals. Remedy:
|
| A5F0 Charging feedback | Cause: Charging feedback signal missing. Remedy:
|
| A682 Flash erase speed exceeded | Cause: The flash memory (in the memory unit) has been erased too frequently, compromising the lifetime of the memory. Remedy:
|
| A686 Checksum mismatch | Cause: The calculated parameter checksum does not match any enabled reference checksum. Programmable warning: 96.54 Checksum action. Remedy:
|
| A687 Checksum configuration | Cause: An action has been defined for a parameter checksum mismatch but the feature has not been configured. Remedy:
|
| A6A4 Motor nominal value | Cause: The motor parameters are set incorrectly. The drive is not dimensioned correctly. Aux codes: 0001: Slip frequency is too small. 0002: Synchronous and nominal speeds differ too much. 0003: Nominal speed is higher than synchronous speed with 1 pole pair. 0004: Nominal current is outside limits. 0005: Nominal voltage is outside limits. 0006: Nominal power is higher than apparent power. 0007: Nominal power not consistent with nominal speed and torque. 0008: Motor nominal power factor is not within limits [0.5...0.97]. Remedy:
|
| A6A5 No motor data | Cause: Parameters in group 99 have not been set. Remedy:
|
| A6A6 Voltage category unselected | Cause: The voltage category has not been defined. Remedy:
|
| A6A7 System time not set | Cause: System time is not set. Timed functions cannot be used and fault log dates are not correct. Remedy:
|
| A6B0 User lock is open | Cause: The user lock is open, ie, user lock configuration parameters 96.100…96.102 are visible. Remedy:
|
| A6B1 User pass code not confirmed | Cause: A new user pass code has been entered in parameter 96.100 but not confirmed in 96.101. Remedy:
|
| A6D1 FBA A parameter conflict | Cause: The drive does not have a functionality requested by a PLC, or requested functionality has not been activated. Remedy:
|
| A6E5 AI parametrization | Cause: The current/voltage hardware setting of an analog input does not correspond to parameter settings. Remedy:
|
| A6E6 ULC configuration | Cause: User load curve configuration error. Aux codes: 0000: Speed points inconsistent. 0001: Frequency points inconsistent. 0002: Underload point above overload point. 0003: Overload point below underload point. Remedy:
|
| A6E7 IPC configuration warning | Cause: IPC configuration error. Aux codes: 0001: IPC incorrectly configured for EFB. 0002: IPC incorrectly configured for FBA. Remedy:
|
| A6E8 IPC version mismatch | Cause: The master and follower(s) do not have the same IPC version and will not run in IPC mode. Remedy:
|
| A780 Motor stall | Cause: Motor is operating in stall region because of, for example, excessive load or insufficient motor power. Programmable warning: 31.24 Stall function. Remedy:
|
| A783 Motor overload | Cause: Motor current is too high. Remedy:
|
| A784 Motor disconnect | Cause: All three output phases are disconnected from motor. Remedy:
|
| A793 BR excess temperature | Cause: Brake resistor temperature has exceeded warning limit defined by parameter 43.12 Brake resistor warning limit. Remedy:
|
| A794 BR data | Cause: Brake resistor data has not been given. Aux codes: 0000 0001: Resistance value too low. 0000 0002: Thermal time constant not given. 0000 0003: Maximum continuous power not given. Remedy:
|
| A79C BC IGBT excess temperature | Cause: Brake chopper IGBT temperature has exceeded internal warning limit. Remedy:
|
| A7AB Extension I/O configuration failure | Cause: Installed extension module is not the same as configured. Remedy:
|
| A7C1 FBA A communication | Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost. Programmable warning: 50.02. Remedy:
|
| A7CE EFB comm loss | Cause: Communication break in embedded fieldbus (EFB) communication. Programmable warning: 58.14. Remedy:
|
| A7EE Panel loss | Cause: Control panel or PC tool selected as active control location for drive has ceased communicating. Programmable warning: 49.05. Remedy:
|
| A88F Cooling fan | Cause: Maintenance timer limit exceeded. Remedy:
|
| A8A0 AI supervision | Cause: An analog signal is outside the limits specified for the analog input. Programmable warning: 12.03. Remedy:
|
| A8A1 RO life warning | Cause: The relay has changed states more than the recommended number of times. Aux code 0001: Relay output 1 Aux code 0002: Relay output 2 Aux code 0003: Relay output 3 Remedy:
|
| A8A2 RO toggle warning | Cause: The relay output is changing states faster than recommended. Remedy:
|
| A8B0 ABB Signal supervision 1 (Programmable warning: 32.06) | Cause: Warning generated by the signal supervision function 1. Remedy:
|
| A8B1 ABB Signal supervision 2 (Programmable warning: 32.16) | Cause: Warning generated by the signal supervision function 2. Remedy:
|
| A8B2 ABB Signal supervision 3 (Programmable warning: 32.26) | Cause: Warning generated by the signal supervision function 3. Remedy:
|
| A8B3 ABB Signal supervision 4 (Programmable warning: 32.36) | Cause: Warning generated by the signal supervision function 4. Remedy:
|
| A8B4 ABB Signal supervision 5 (Programmable warning: 32.46) | Cause: Warning generated by the signal supervision function 5. Remedy:
|
| A8B5 ABB Signal supervision 6 (Programmable warning: 32.56) | Cause: Warning generated by the signal supervision function 6. Remedy:
|
| A8BE ULC overload warning (Programmable fault: 37.03) | Cause: Selected signal has exceeded the user overload curve. Remedy:
|
| A8BF ULC underload warning (Programmable fault: 37.04) | Cause: Selected signal has fallen below the user underload curve. Remedy:
|
| A981 External warning 1 (Programmable warning: 31.01) | Cause: Fault in external device 1. Remedy:
|
| A982 External warning 2 (Programmable warning: 31.03) | Cause: Fault in external device 2. Remedy:
|
| A983 External warning 3 (Programmable warning: 31.05) | Cause: Fault in external device 3. Remedy:
|
| A984 External warning 4 (Programmable warning: 31.07) | Cause: Fault in external device 4. Remedy:
|
| A985 External warning 5 (Programmable warning: 31.09) | Cause: Fault in external device 5. Remedy:
|
| AF88 Season configuration warning | Cause: You have configured a season which starts before the previous season. Remedy:
|
| AFAA Autoreset | Cause: A fault is about to be autoreset. Remedy:
|
| AFE1 Emergency stop (off2) | Cause: Drive has received an emergency stop (mode selection off2) command. Remedy:
|
| AFE2 Emergency stop (off1 or off3) | Cause: Drive has received an emergency stop (mode selection off1 or off3) command. Remedy:
|
| AFE9 Start delay | Cause: The start delay is active and the drive will start the motor after a predefined delay. Remedy:
|
| AFED Run permissive | Cause: Run permissive is keeping the drive from running the motor. Remedy:
|
| AFEE Start interlock 1 | Cause: Start interlock 1 is keeping the drive from starting. Remedy:
|
| AFEF Start interlock 2 | Cause: Start interlock 2 is keeping the drive from starting. Remedy:
|
| AFF0 Start interlock 3 | Cause: Start interlock 3 is keeping the drive from starting. Remedy:
|
| AFF1 Start interlock 4 | Cause: Start interlock 4 is keeping the drive from starting. Remedy:
|
| AFF2 Run permissive forced warning | Cause: A forced DI is used as a source for parameter 20.40 Run permissive. Remedy:
|
| AFF3 Start interlock forced warning | Cause: One or more forced DIs is used as a source for one or more of parameters 20.41 Start interlock 1 … 20.44 Start interlock 4. Remedy:
|
| AFF5 Override new start required | Cause: The Safe torque off function was active and has been reset while in Override. Remedy:
|
| AFF6 Identification run | Cause: Motor ID run will occur at next start. Remedy:
|
| AFF8 Motor heating active | Cause: Pre-heating is being performed. Remedy:
|
| AFFE Override active | Cause: Drive is in Override mode. Remedy:
|
| B5A0 STO event (Programmable event: 31.22) | Cause: Safe torque off function is active, ie, safety circuit signal(s) connected to connector STO is lost. Remedy:
|
| B5A2 Power applied | Cause: The drive was powered up or the control board was rebooted successfully. Remedy:
|
| B681 Hand mode selected | Cause: The drive was placed in Hand mode. Remedy:
|
| B682 Off mode selected | Cause: The drive was placed in Off mode. Remedy:
|
| B683 Auto mode selected | Cause: The drive was placed in Auto mode. Remedy:
|
| B686 Checksum mismatch (Programmable event: 96.54) | Cause: The calculated parameter checksum does not match any enabled reference checksum. Remedy:
|
| B687 Auto start command | Cause: The drive received a start command while in Auto mode. Remedy:
|
| B688 Auto stop command | Cause: The drive received a stop command while in Auto mode. Remedy:
|
| B689 Modulating started | Cause: The drive started modulating. Remedy:
|
| B68A Modulating stopped | Cause: The drive stopped modulating. Remedy:
|
| D501 No more available PFC motors | Cause: No more PFC motors can be started because they can be interlocked or in the Hand mode. Remedy:
|
| D502 All motors interlocked | Cause: All the motors in the PFC system are interlocked. Remedy:
|
| D503 VSD controlled PFC motor interlocked | Cause: The motor connected to the drive is interlocked (unavailable). Remedy:
|
| D504 Damper timeout | Cause: Discharge air or outside air damper has timed out. Remedy:
|
| D504 (Aux: 0001) Damper timeout | Cause: Discharge air damper was commanded to open and it timed out while opening. Remedy:
|
| D504 (Aux: 0002) Damper timeout | Cause: Discharge air damper was commanded to close and it timed out while closing. Remedy:
|
| D504 (Aux: 0003) Damper timeout | Cause: Outside air damper was commanded to open and it timed out while opening. Remedy:
|
| D504 (Aux: 0004) Damper timeout | Cause: Outside air damper was commanded to close and it timed out while closing. Remedy:
|
| D50A Running dry (Programmable warning: 82.20) | Cause: Dry run protection is activated. Remedy:
|
| D50B Pipe fill-timeout (Programmable warning: 82.25) | Cause: Soft pipe fill is reached the timeout limit. The PID output is not reached the setpoint after reference ramping is ended and timeout limit is elapsed. Remedy:
|
| D50C Maximum flow protection (Programmable warning: 80.17) | Cause: Actual flow is exceeded the defined warning level. Remedy:
|
| D50D Minimum flow protection (Programmable warning: 80.18) | Cause: Actual flow is below the defined warning level. Remedy:
|
| D50E Outlet minimum pressure (Programmable warning: 82.30) | Cause: Measured outlet pressure is below the defined warning limit. Remedy:
|
| D50F Outlet maximum pressure (Programmable warning: 82.35) | Cause: Measured outlet pressure is above the defined warning limit. Remedy:
|
| D510 Inlet minimum pressure (Programmable warning: 82.40) | Cause: Measured inlet pressure is below the defined warning level. Remedy:
|
| D590 Restart delay | Cause: The restart delay is active. Remedy:
|
| D590 (Aux: 0000) Restart delay | Cause: Contact your local ABB representative. Remedy:
|
| D590 (Aux: 0002) Restart delay | Cause: Pump short cycle protection. Remedy:
|
| 1080 Backup/Restore timeout | Cause: Control panel or PC tool has failed to communicate with the drive when backup was being made or restored. Remedy:
|
| 1081 Rating ID fault | Cause: Drive software has not been able to read the rating ID of the drive. Remedy:
|
| 2310 Overcurrent | Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this fault may also be caused by an earth fault or supply phase loss. Remedy:
|
| 2330 Earth leakage | Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable. Remedy:
|
| 2340 Short circuit | Cause: Short-circuit in motor cable(s) or motor. Auxiliary codes: 0001: Short U-phase upper (R6-R11) 0002: Short U-phase lower (R6-R11) 0004: Short V-phase upper (R6-R11) 0008: Short V-phase lower (R6-R11) 0010: Short W-phase upper (R6-R11) 0020: Short W-phase lower (R6-R11) 0040: DC capacitor short circuit (R6-R11) 0080: State feedback mismatch (R6-R7) Remedy:
|
| 2381 IGBT overload | Cause: Excessive IGBT junction to case temperature. This fault protects the IGBT(s) and can be activated by a short circuit in the motor cable. Remedy:
|
| 3130 Input phase loss | Cause: Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. (Programmable fault 31.21). Remedy:
|
| 3181 Wiring or earth fault | Cause: Incorrect input power and motor cable connection (i.e. input power cable is connected to drive motor connection). (Programmable fault 31.23). Remedy:
|
| 3210 DC link overvoltage | Cause: Excessive intermediate circuit DC voltage. Remedy:
|
| 3220 DC link undervoltage | Cause: Intermediate circuit DC voltage is not sufficient because of a missing supply phase, blown fuse or fault in the rectifier bridge. Remedy:
|
| 3381 Output phase loss | Cause: Motor circuit fault due to missing motor connection (all three phases are not connected). (Programmable fault 31.19). Remedy:
|
| 4110 Control board temperature | Cause: Control board temperature is too high. Remedy:
|
| 4210 IGBT overtemperature | Cause: Estimated drive IGBT temperature is excessive. Remedy:
|
| 4290 Cooling | Cause: Drive module temperature is excessive. Remedy:
|
| 42F1 IGBT temperature | Cause: Drive IGBT temperature is excessive. Remedy:
|
| 4310 Excess temperature | Cause: Power unit module temperature is excessive. Remedy:
|
| 4380 Excess temperature difference | Cause: High temperature difference between the IGBTs of different phases. Remedy:
|
| 4981 External temperature 1 | Cause: Measured temperature 1 has exceeded fault limit. (Editable message text). Remedy:
|
| 4982 External temperature 2 | Cause: Measured temperature 2 has exceeded fault limit. (Editable message text). Remedy:
|
| 5080 Fan | Cause: Cooling fan feedback missing. Remedy:
|
| 5090 STO hardware failure | Cause: STO hardware diagnostics has detected hardware failure. Remedy:
|
| 5091 Safe torque off | Cause: Safe torque off function is active, i.e., safety circuit signal(s) connected to connector STO is broken during start or run. (Programmable fault 31.22). Remedy:
|
| 5092 PU logic error | Cause: Power unit memory has cleared. Remedy:
|
| 5093 Rating ID mismatch | Cause: The hardware of the drive does not match the information stored in the memory. This may occur, for example, after a firmware update. Remedy:
|
| 5094 Measurement circuit temperature | Cause: Problem with internal temperature measurement of the drive. Remedy:
|
| 5098 I/O communication loss | Cause: Internal standard I/O communication failure. Remedy:
|
| 50A0 Fan | Cause: Cooling fan stuck or disconnected. Remedy:
|
| 5681 PU communication | Cause: Communication errors detected between the drive control unit and the power unit. Remedy:
|
| 5682 Power unit lost | Cause: Connection between the drive control unit and the power unit is lost. Remedy:
|
| 5691 Measurement circuit ADC | Cause: Measurement circuit fault. Remedy:
|
| 5692 PU board powerfail | Cause: Power unit power supply failure. Remedy:
|
| 5693 Measurement circuit DFF | Cause: Measurement circuit fault. Remedy:
|
| 5697 Charging feedback | Cause: Charging feedback signal missing. Remedy:
|
| 5698 Unknown PU fault | Cause: The power unit logic has generated a fault which is not known by the software. Remedy:
|
| 6181 FPGA version incompatible | Cause: Firmware and FPGA versions are incompatible. Remedy:
|
| 6200 Checksum mismatch | Cause: The calculated parameter checksum does not match any enabled reference checksum. Remedy:
|
| 6306 FBA A mapping file | Cause: Fieldbus adapter A mapping file read error. Remedy:
|
| 6481 Task overload | Cause: Internal fault. Remedy:
|
| 6487 Stack overflow | Cause: Internal fault. Remedy:
|
| 64A1 Internal file load | Cause: File read error. Remedy:
|
| 64A4 Rating ID fault | Cause: Rating ID load error. Remedy:
|
| 64A6 Adaptive program | Cause: Error running the adaptive program. Check the auxiliary code (format XXYY ZZZZ). Remedy:
|
| 64B1 Internal SSW fault | Cause: Internal fault. Remedy:
|
| 64B2 User set fault | Cause: Loading of user parameter set failed because:
Remedy:
|
| 64B3 Macro parameterization error | Cause: Loading of macro parameter set failed. Remedy:
|
| 64E1 Kernel overload | Cause: Operating system error. Remedy:
|
| 64FF Fault reset | Cause: A fault has been reset from the control panel, Drive composer PC tool, fieldbus or I/O. Remedy:
|
| 6581 Parameter system | Cause: Parameter load or save failed. Remedy:
|
| 6591 Backup/Restore timeout | Cause: During backup creating or restoring operation a control panel or PC tool has failed to communicate with the drive. Remedy:
|
| 65A1 FBA A parameter conflict | Cause: The drive does not have a functionality requested by PLC, or requested functionality has not been activated. Remedy:
|
| 6681 EFB comm loss | Cause: Communication break in embedded fieldbus (EFB) communication. Remedy:
|
| 6682 EFB config file | Cause: Embedded fieldbus (EFB) configuration file could not be read. Remedy:
|
| 6683 EFB invalid parameterization | Cause: Embedded fieldbus (EFB) parameter settings inconsistent or not compatible with selected protocol. Remedy:
|
| 6684 EFB load fault | Cause: Embedded fieldbus (EFB) protocol firmware could not be loaded. Version mismatch between EFB protocol firmware and drive firmware. Remedy:
|
| 6685 EFB fault 2 | Cause: Fault reserved for the EFB protocol application. Remedy:
|
| 6686 EFB fault 3 | Cause: Fault reserved for the EFB protocol application. Remedy:
|
| 6882 Text 32-bit table overflow | Cause: Internal fault. Remedy:
|
| 6885 Text file overflow | Cause: Internal fault. Remedy:
|
| 7081 Control panel loss | Cause: Control panel or PC tool selected as active control location for drive has ceased communicating. Remedy:
|
| 7082 I/O module comm loss | Cause: Communication between IO module and drive is not working properly. Remedy:
|
| 7085 Incompatible option module | Cause: Fieldbus option module not supported. Remedy:
|
| 7086 AI Overvoltage | Cause: An overvoltage has been detected on an analog input. Remedy:
|
| 7087 I/O module configuration fault | Cause: I/O module configuration not supported or illegal. Remedy:
|
| 7100 Excitation current | Cause: Excitation current feedback low or missing. Remedy:
|
| 7121 Motor stall | Cause: Motor is operating in stall region (e.g. excessive load or insufficient motor power). Remedy:
|
| 7122 Motor overload | Cause: Motor current is too high. Remedy:
|
| 7181 Brake resistor | Cause: Brake resistor broken or not connected. Remedy:
|
| 7183 BR excess temperature | Cause: Brake resistor temperature has exceeded fault limit defined by parameter 43.11. Remedy:
|
| 7184 Brake resistor wiring | Cause: Brake resistor short circuit or brake chopper control fault. Remedy:
|
| 7191 BC short circuit | Cause: Short circuit in brake chopper IGBT. Remedy:
|
| 7192 BC IGBT excess temperature | Cause: Brake chopper IGBT temperature has exceeded internal fault limit. Remedy:
|
| 7310 Overspeed | Cause: Motor is turning faster than highest allowed speed. Remedy:
|
| 73B0 Emergency ramp failed | Cause: Emergency stop did not finish within expected time. Remedy:
|
| 73F0 Overfrequency | Cause: Maximum allowed output frequency exceeded. Remedy:
|
| 7510 FBA A communication | Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost. Remedy:
|
| 8001 ULC underload fault | Cause: User load curve: Signal has been too long under the underload curve. Remedy:
|
| 8002 ULC overload fault | Cause: User load curve: Signal has been too long over the overload curve. Remedy:
|
| 80A0 AI supervision | Cause: An analog signal is outside the limits specified for the analog input. Remedy:
|
| 80B0 Signal supervision 1 | Cause: Fault generated by the signal supervision function 1. Remedy:
|
| 80B1 Signal supervision 2 | Cause: Fault generated by the signal supervision function 2. Remedy:
|
| 80B2 Signal supervision 3 | Cause: Fault generated by the signal supervision function 3. Remedy:
|
| 80B3 Signal supervision 4 | Cause: Fault generated by the signal supervision function 4. Remedy:
|
| 80B4 Signal supervision 5 | Cause: Fault generated by the signal supervision function 5. Remedy:
|
| 80B5 Signal supervision 6 | Cause: Fault generated by the signal supervision function 6. Remedy:
|
| 9081 External fault 1 | Cause: Fault in external device 1. Remedy:
|
| 9082 External fault 2 | Cause: Fault in external device 2. Remedy:
|
| 9083 External fault 3 | Cause: Fault in external device 3. Remedy:
|
| 9084 External fault 4 | Cause: Fault in external device 4. Remedy:
|
| 9085 External fault 5 | Cause: Fault in external device 5. Remedy:
|
| D404 Running dry | Cause: Dry run protection is activated. Remedy:
|
| D405 Pipe fill-timeout | Cause: Soft pipe fill has reached timeout limit. The PID output has not reached the setpoint after reference ramping ended. Remedy:
|
| D406 Maximum flow protection | Cause: Actual flow is exceeded the defined fault level. Remedy:
|
| D407 Minimum flow protection | Cause: Actual flow is below the defined fault level. Remedy:
|
| D408 Outlet minimum pressure | Cause: The measured outlet pressure is below the defined fault limit. Remedy:
|
| D409 Outlet maximum pressure | Cause: The measured outlet pressure is above the defined fault limit. Remedy:
|
| D40A Inlet minimum pressure | Cause: The measured inlet pressure is below the defined fault level. Remedy:
|
| D40B Damper timeout | Cause: Discharge air or outside air damper has timed out. Remedy:
|
| D40C Multipump run permissive timeout | Cause: The run permissive setting (20.40) was not satisfied within the time set in parameter 20.40 or 76.64. Remedy:
|
| FA81 Safe torque off 1 | Cause: Safe torque off function is active, that is, STO circuit 1 is broken. Remedy:
|
| FA82 Safe torque off 2 | Cause: Safe torque off function is active, that is, STO circuit 2 is broken. Remedy:
|
| FF61 ID run | Cause: Motor ID run was not completed successfully. Remedy:
|
| FF63 STO diagnostics failure | Cause: SW internal malfunction. Remedy:
|
| FF81 FB A force trip | Cause: A fault trip command has been received through fieldbus adapter A. Remedy:
|
| FF8E EFB force trip | Cause: A fault trip command has been received through the embedded fieldbus interface. Remedy:
|
How to Clear & Reset ABB ACH480 Drive Faults
- Keypad Reset: Press the red Reset softkey on the ACH-AP-H HVAC control panel. If the drive is under BMS remote control (REM), press the Loc/Rem key to toggle to local mode (LOC) first before resetting.
- Digital Input Reset (DI): If configured in parameter 31.11 (Fault reset selection), pulse the assigned digital input terminal (DI1 to DI6) with an active high 24V signal.
- BMS / Fieldbus Network: If controlled over BACnet MS/TP, Modbus RTU, or N2 via the embedded EIA-485 interface, write a reset command or toggle Bit 7 (Fault Reset) in the Control Word from `0` to `1`.
- Drive Composer PC Tool: Connect your PC via the USB mini-B port on the ACH-AP-H keypad, open Drive Composer, and click the “Reset” button in the top drive status bar.
- Power Cycle: Disconnect incoming AC line power, wait at least 5 minutes for the intermediate DC bus capacitors to discharge completely until the keypad display shuts off, and then restore line power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [UDC+] and [UDC-] before inspecting motor leads, opening terminal covers, or touching terminals U2, V2, and W2 on the ABB ACH480 drive.