ABB ACS255 Micro Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, 7-segment LED display trip messages (such as O-I, O-Volt, and I.t-trP), root causes, and step-by-step diagnostic procedures for the ABB ACS255 micro drive series. Search or filter through the complete fault code directory below.
Power Range
0.37 – 15 kW (0.5 – 20 HP)
Supply Voltage
115V / 230V / 480V / 600V
Control Modes
Scalar (V/f) & Vector (SLV)
Operator Interface
Integrated 6-Digit LED Keypad
Complete ABB ACS255 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type O-I, O-Volt, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Stop (0x00) Drive is READY and in a stopped condition. | Cause: The motor is not energized. No enable signal is present to start the drive. Remedy:
|
| P-def (0x0A) Factory Default parameters have been loaded. | Cause: Default parameters loaded. Remedy:
|
| F0001 (0x03) Instantaneous Over current on the drive output. | Cause: Excess load or shock load on the motor. Remedy:
|
| F0009 (0x04) Motor thermal overload protection trip. | Cause: The drive has tripped after delivering >100% of value in 9906 for a period of time to prevent damage. Remedy:
|
| OL-b (0x01) Brake channel over current. | Cause: Excessive current in the brake resistor. Remedy:
|
| OL-br (0x02) Brake resistor thermal overload. | Cause: Internal protection activated (when param 2020 = 1). Remedy:
|
| F0004 (0x05) Hardware Over Current. | Cause: Short circuit or hardware fault. Remedy:
|
| F0002 (0x06) Over voltage on DC bus. | Cause: Supply voltage outside tolerance or regen energy too high. Remedy:
|
| F0006 (0x07) Under voltage on DC bus. | Cause: The incoming supply voltage is too low (or power removed). Remedy:
|
| F0003 (0x08) Heatsink over temperature. | Cause: The drive is too hot. Remedy:
|
| U-t (0x09) Under temperature. | Cause: Ambient temperature is less than -10°C. Remedy:
|
| F0018 (0x10) Faulty thermistor on heatsink. | Cause: Internal component failure. Remedy:
|
| O-heat (0x17) Drive internal temperature too high. | Cause: Drive ambient temperature too high. Remedy:
|
| F0014 (0x0B) External trip (on digital input 3). | Cause: E-trip requested on control terminals (based on param 9902 settings). Remedy:
|
| F0010 (0x0C) Comms loss trip. | Cause: Communication link failure. Remedy:
|
| F0022 (0x0E) Input phase loss trip. | Cause: Drive intended for 3 phase supply has lost one input phase. Remedy:
|
| SPin-F (0x0F) Spin start failed. | Cause: Spin start function failed to detect the motor speed. Remedy:
|
| F0027 (0x11) Internal memory fault. | Cause: Parameters not saved, defaults reloaded. Remedy:
|
| F0007 (0x12) Analog input current out of range. | Cause: 4-20mA signal loss or out of bounds. Remedy:
|
| F0021 Internal drive Fault. | Cause: Internal Error. Remedy:
|
| faulty Internal drive Fault. | Cause: Internal Error. Remedy:
|
| AtF-01 (40) Autotune Fault. | Cause: Measured motor stator resistance varies between phases. Remedy:
|
| AtF-02 (41) Autotune Fault. | Cause: Measured motor stator resistance is too large. Remedy:
|
| AtF-03 (42) Autotune Fault. | Cause: Measured motor inductance is too low. Remedy:
|
| AtF-04 (43) Autotune Fault. | Cause: Measured motor inductance is too large. Remedy:
|
| AtF-05 (44) Autotune Fault. | Cause: Measured motor parameters are not convergent. Remedy:
|
How to Clear & Reset ABB ACS255 Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the integrated front keypad. If the drive is stopped and a trip message is flashing, pressing STOP clears the fault and displays STOP.
- Digital Input Reset: Toggle the enable/run input open or cycle the configured reset terminal (defined by terminal macro parameter P-12 or P-15).
- Modbus RTU Reset: Send a reset command by setting Bit 3 (Fault Reset) in the Control Word via the built-in RJ45 Modbus RTU communication port.
- Automatic Reset: If automatic restart is enabled via parameter P-30, the drive will automatically attempt to clear the trip condition up to the preset number of attempts after a programmed delay.
- Power Cycle: Disconnect AC input mains power completely. Wait at least 5 minutes until the LED display is completely dark and DC bus capacitors have discharged before restoring power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous voltages remain present in internal capacitors after input power is disconnected. Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC / BR] and [-DC] before servicing terminals U, V, W or motor wiring on the ABB ACS255 drive.