ABB ACS480 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the ABB ACS480 general purpose compact drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 22 kW (1 – 30 HP)
Supply Voltage
380–480V AC (3-Phase)
Control Modes
Scalar & Vector Control
Operator Interface
Assistant Control Panel (ACS-AP-S)
Complete ABB ACS480 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type 2310, 3210, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 64FF Fault reset | Cause: A fault has been reset from the control panel, Drive composer PC tool, fieldbus or I/O. Remedy:
|
| B686 Checksum mismatch | Cause: Parameter checksum 96.68 Actual checksumA does not match 96.71 Approved checksum A and/ or parameter checksum 96.69 Actual checksumB does not match 96.72 Approved checksum B. Remedy:
|
| A2A1 Current calibration | Cause: Current offset and gain measurement calibration will occur at next start. Remedy:
|
| A2B1 Overcurrent | Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this warning may also be caused by an earth fault or supply phase loss. Remedy:
|
| A2B3 Earth leakage | Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable. Remedy:
|
| A2B4 Short circuit | Cause: Short-circuit in motor cable(s) or motor. Remedy:
|
| A2BA IGBT overload | Cause: Excessive IGBT junction to case temperature. This warning protects the IGBT(s) and can be activated by a short circuit in the motor cable. Remedy:
|
| A3A1 DC link overvoltage | Cause: Intermediate circuit DC voltage too high (when the drive is stopped). Remedy:
|
| A3A2 DC link undervoltage | Cause: Intermediate circuit DC voltage too low (when the drive is stopped). Remedy:
|
| A3AA DC not charged | Cause: The voltage of the intermediate DC circuit has not yet risen to operating level. Remedy:
|
| A490 Incorrect temperature sensor setup | Cause: Temperature cannot be supervised due to incorrect adapter setup. AO settings do not match with 35.11 and 35.21. Remedy:
|
| A491 External temperature 1 | Cause: Measured temperature 1 has exceeded warning limit. (Editable message text) Remedy:
|
| A492 External temperature 2 | Cause: Measured temperature 2 has exceeded warning limit. (Editable message text) Remedy:
|
| A4A0 Control board temperature | Cause: Control unit temperature is too high. Aux code (none): Temperature above warning limit. Aux code 1: Thermistor broken. Remedy:
|
| A4A1 IGBT overtemperature | Cause: Estimated drive IGBT temperature is excessive. Remedy:
|
| A4A9 Cooling | Cause: Drive module temperature is excessive. Remedy:
|
| A4B0 Excess temperature | Cause: Power unit module temperature is excessive. Remedy:
|
| A4B1 Excess temperature difference | Cause: High temperature difference between the IGBTs of different phases. Remedy:
|
| A4F6 IGBT temperature | Cause: Drive IGBT temperature is excessive. Remedy:
|
| A581 Fan | Cause: Cooling fan feedback missing. For frame sizes R6 or larger. Remedy:
|
| A5A0 Safe torque off | Cause: Safe torque off function is active, that is, safety circuit signal(s) connected to connector STO is lost. Remedy:
|
| A5EA Measurement circuit temperature | Cause: Problem with internal temperature measurement of the drive. Aux code depends on control unit type. Aux codes: 0001 (IGBT), 0003 (Board), 0006 (Power supply). Remedy:
|
| A5EB PU board powerfail | Cause: Power unit power supply failure. Remedy:
|
| A5ED Measurement circuit ADC | Cause: Measurement circuit fault. Remedy:
|
| A5EE Measurement circuit DFF | Cause: Measurement circuit fault. Remedy:
|
| A5EF PU state feedback | Cause: State feedback from output phases does not match control signals. Remedy:
|
| A5F0 Charging feedback | Cause: Charging feedback signal missing. Remedy:
|
| A682 Flash erase speed exceeded | Cause: The flash memory (in the memory unit) has been erased too frequently, compromising the lifetime of the memory. Remedy:
|
| A686 Checksum mismatch | Cause: Parameter checksum 96.68 Actual checksumA does not match 96.71 Approved checksum A etc. Remedy:
|
| A6A4 Motor nominal value | Cause: The motor parameters are set incorrectly. The drive is not dimensioned correctly. Aux codes: 0001: Slip frequency too small. 0002: Sync and nominal speeds differ too much. 0003: Nom speed higher than sync speed. 0004: Nom current outside limits. 0005: Nom voltage outside limits. 0006: Nom power higher than apparent power. 0007: Nom power not consistent with speed/torque. Remedy:
|
| A6A5 No motor data | Cause: Parameters in group 99 have not been set. Remedy:
|
| A6A6 Voltage category unselected | Cause: The voltage category has not been defined. Remedy:
|
| A6A7 System time not set | Cause: System time is not set. Timed functions cannot be used and fault log dates are not correct. Remedy:
|
| A6B0 User lock is open | Cause: The user lock is open, ie. user lock configuration parameters 96.100…96.102 are visible. Remedy:
|
| A6B1 User pass code not confirmed | Cause: A new user pass code has been entered in parameter 96.100 but not confirmed in 96.101. Remedy:
|
| A6D1 FBA A parameter conflict | Cause: The drive does not have a functionality requested by a PLC, or requested functionality has not been activated. Remedy:
|
| A6E5 AI parametrization | Cause: The current/voltage hardware setting of an analog input does not correspond to parameter settings. Remedy:
|
| A6E6 ULC configuration | Cause: User load curve configuration error. Remedy: Check the auxiliary code (format XXXX ZZZZ). "ZZZZ" indicates the problem:
|
| A780 Motor stall | Cause: Motor is operating in stall region because of, for example, excessive load or insufficient motor power. Remedy:
|
| A783 Motor overload | Cause: Motor current is too high. Remedy:
|
| A784 Motor disconnect | Cause: All three output phases are disconnected from motor. Remedy:
|
| A793 BR excess temperature | Cause: Brake resistor temperature has exceeded warning limit defined by parameter 43.12 Brake resistor warning limit. Remedy:
|
| A794 BR data | Cause: Brake resistor data has not been given. Remedy: One or more of the resistor data settings (parameters 43.08...43.10) is incorrect. The parameter is specified by the auxiliary code:
|
| A79C BC IGBT excess temperature | Cause: Brake chopper IGBT temperature has exceeded internal warning limit. Remedy:
|
| A7A2 Mechanical brake opening failed | Cause: Status of mechanical brake acknowledgement is not as expected during brake open. Remedy:
|
| A7AB Extension I/O configuration failure | Cause: I/O module is not connected to the device or parameterization conflict with connected I/O module. Remedy:
|
| A7AC I/O Module internal error | Cause: Calibration data is not stored in the I/O module. Analog signals are not working with full accuracy. Remedy:
|
| A7C1 FBA A communication | Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost. Remedy:
|
| A7CE EFB comm loss | Cause: Communication break in embedded fieldbus (EFB) communication. Remedy:
|
| A7EE Panel loss | Cause: Control panel or PC tool selected as active control location for drive has ceased communicating. Remedy:
|
| A88F Cooling fan | Cause: Maintenance timer limit exceeded. Remedy:
|
| A8A0 AI supervision | Cause: An analog signal is outside the limits specified for the analog input. Remedy:
|
| A8A1 RO life warning | Cause: The relay has changed states more than the recommended number of times. Remedy: Change the control unit or stop using the relay output.
|
| A8A2 RO toggle warning | Cause: The relay output is changing states faster than recommended (e.g., fast changing frequency signal connected). The relay lifetime will be exceeded shortly. Remedy: Replace the signal connected to the relay output source with a less frequently changing signal.
|
| A8B0 ABB Signal supervision 1 | Cause: Warning generated by the signal supervision function 1. Remedy:
|
| A8B1 ABB Signal supervision 2 | Cause: Warning generated by the signal supervision function 2. Remedy:
|
| A8B2 ABB Signal supervision 3 | Cause: Warning generated by the signal supervision function 3. Remedy:
|
| A8B3 ABB Signal supervision 4 | Cause: Warning generated by the signal supervision function 4. Remedy:
|
| A8B4 ABB Signal supervision 5 | Cause: Warning generated by the signal supervision function 5. Remedy:
|
| A8B5 ABB Signal supervision 6 | Cause: Warning generated by the signal supervision function 6. Remedy:
|
| A8BE ULC overload warning | Cause: Selected signal has exceeded the user overload curve. Remedy:
|
| A8BF ULC underload warning | Cause: Selected signal has fallen below the user underload curve. Remedy:
|
| A981 External warning 1 | Cause: Fault in external device 1. Remedy:
|
| A982 External warning 2 | Cause: Fault in external device 2. Remedy:
|
| A983 External warning 3 | Cause: Fault in external device 3. Remedy:
|
| A984 External warning 4 | Cause: Fault in external device 4. Remedy:
|
| A985 External warning 5 | Cause: Fault in external device 5. Remedy:
|
| AF88 Season configuration warning | Cause: You have configured a season which starts before the previous season. Remedy:
|
| AF90 Speed controller autotuning | Cause: The speed controller autotune routine did not complete successfully. Remedy: Check the auxiliary code:
|
| AFAA Autoreset | Cause: A fault is about to be autoreset. Remedy:
|
| AFE1 Emergency stop (off2) | Cause: Drive has received an emergency stop (mode selection off2) command. Remedy:
|
| AFE2 Emergency stop (off1 or off3) | Cause: Drive has received an emergency stop (mode selection off1 or off3) command. Remedy:
|
| AFE9 Start delay | Cause: The start delay is active and the drive will start the motor after a predefined delay. Remedy:
|
| AFEB Run enable missing | Cause: No run enable signal is received. Remedy:
|
| AFED Enable to rotate | Cause: Signal to rotate has not been received within a fixed time delay of 240 s. Remedy:
|
| AFF6 Identification run | Cause: Motor ID run will occur at next start. Remedy:
|
| AFF8 Motor heating active | Cause: Pre-heating is being performed. Remedy:
|
| B5A0 STO event | Cause: Safe torque off function is active, i.e. safety circuit signal(s) connected to connector STO is lost. Remedy:
|
| D50A Running dry | Cause: Dry run protection is activated. Remedy:
|
| D50B Pipe fill-timeout | Cause: Soft pipe fill has reached the timeout limit. The PID output reached the setpoint after reference ramping ended and timeout limit elapsed. Remedy:
|
| D501 No more available PFC motors | Cause: No more PFC motors can be started because they can be interlocked or in the Hand mode. Remedy:
|
| D502 All motors interlocked | Cause: All the motors in the PFC system are interlocked. Remedy:
|
| D503 VSD controlled PFC motor interlocked | Cause: The motor connected to the drive is interlocked (unavailable). Remedy:
|
| D505 Max cleaning warning | Cause: Maximum number of cleanings are reached in defined time. The Pump cleaning is unable to clean the pump and hence, manual cleaning is required. Remedy:
|
| D506 Pump cleaning not possible | Cause: Pump cleaning cannot be started. The drive needs to be in remote control and start signal is activated. Remedy:
|
| D507 Pump cleaning needed | Cause: Dirt detection indicates that the pump needs cleaning but automatic pump cleaning is not allowed. Remedy:
|
| D511 Cavitation control | Cause: Cavitation control warning. Remedy:
|
| 0001 Cavitation detected warning | Cause: The pump is not getting enough liquid. Check the system. Remedy:
|
| 0002 Cavitation tune required | Cause: Cavitation control has been selected (86.11); however, there is missing data in 86.21 – 86.25. Remedy:
|
| 0003 Cavitation curve autotune | Cause: Cavitation curve autotune has been selected and will be performed on next start (in Hand). Remedy:
|
| D58B Gas pressure outside limits | Cause: The compressor gas pressure is outside the limits. Remedy:
|
| D590 Restart delay | Cause: Compressor Restart delay. Remedy:
|
| 001 Compressor short cycle protection | Cause: Short cycle protection active. Remedy:
|
| D591 Min. run time | Cause: Compressor minimum run time. Remedy:
|
| D602 Cavitation tune completed | Cause: Cavitation auto tune has finished and stopped the drive. Remedy:
|
| 1080 Backup/Restore timeout | Cause: Control panel or PC tool has failed to communicate with the drive when backup was being made or restored. Remedy:
|
| 1081 Rating ID fault | Cause: Drive software has not been able to read the rating ID of the drive. Remedy:
|
| 2340 Short circuit | Cause: Short-circuit in motor cable(s) or motor. Remedy:
|
| 2310 Overcurrent | Cause: Output current has exceeded internal fault limit. Can be caused by earth fault or supply phase loss. Remedy:
|
| 2330 Earth leakage | Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable. Remedy:
|
| 2381 IGBT overload | Cause: Excessive IGBT junction to case temperature. This fault protects the IGBT(s) and can be activated by a short circuit in the motor cable. Remedy:
|
| 3130 Input phase loss | Cause: Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Remedy:
|
| 3181 Wiring or earth fault | Cause: Incorrect input power and motor cable connection (i.e. input power cable is connected to drive motor connection). Remedy:
|
| 3210 DC link overvoltage | Cause: Excessive intermediate circuit DC voltage. Remedy:
|
| 3220 DC link undervoltage | Cause: Intermediate circuit DC voltage is not sufficient because of a missing supply phase, blown fuse or fault in the rectifier bridge. Remedy:
|
| 3381 Output phase loss | Cause: Motor circuit fault due to missing motor connection (all three phases are not connected). Remedy:
|
| 4110 Control board temperature | Cause: Control unit temperature is too high. Remedy:
|
| 4210 IGBT overtemperature | Cause: Estimated drive IGBT temperature is excessive. Remedy:
|
| 4290 Cooling | Cause: Drive module temperature is excessive. Remedy:
|
| 42F1 IGBT temperature | Cause: Drive IGBT temperature is excessive. Remedy:
|
| 4310 Excess temperature | Cause: Power unit module temperature is excessive. Remedy:
|
| 4380 Excess temperature difference | Cause: High temperature difference between the IGBTs of different phases. Remedy:
|
| 4981 External temperature 1 | Cause: Measured temperature 1 has exceeded fault limit. Remedy:
|
| 4982 External temperature 2 | Cause: Measured temperature 2 has exceeded fault limit. Remedy:
|
| 5080 Fan | Cause: Cooling fan feedback missing. Remedy:
|
| 5090 STO hardware failure | Cause: STO hardware diagnostics has detected hardware failure. Remedy:
|
| 5091 Safe torque off (STO indication run/stop) | Cause: Safe torque off function is active; safety circuit signal connected to connector STO is broken during start or run. Remedy:
|
| 5092 PU logic error | Cause: Power unit memory has cleared. Remedy:
|
| 5093 Rating ID mismatch | Cause: The hardware of the drive does not match the information stored in the memory (may occur after firmware update). Remedy:
|
| 5094 Measurement circuit temperature | Cause: Problem with internal temperature measurement of the drive. Remedy:
|
| 5089 SMT circuit malfunction | Cause: Safe motor temperature fault generated but STO event/fault not generated. Remedy:
|
| 5098 I/O communication loss | Cause: Communication failure to standard I/O. Remedy:
|
| 50A0 Fan | Cause: Cooling fan stuck or disconnected. Remedy:
|
| 5682 Power unit lost | Cause: Connection between the drive control unit and the power unit is lost. Remedy:
|
| 5691 Measurement circuit ADC | Cause: Measurement circuit fault. Remedy:
|
| 5692 PU board powerfail | Cause: Power unit power supply failure. Remedy:
|
| 5693 Measurement circuit DFF | Cause: Measurement circuit fault. Remedy:
|
| 5697 Charging feedback | Cause: Charging feedback signal missing. Remedy:
|
| 5698 Unknown PU fault | Cause: The power unit logic has generated a fault which is not known by the software. Remedy:
|
| 6181 FPGA version incompatible | Cause: Firmware and FPGA versions are incompatible. Remedy:
|
| 6200 Checksum mismatch | Cause: Parameter checksum 96.68 (Actual A) != 96.71 (Approved A) or 96.69 (Actual B) != 96.72 (Approved B). Remedy:
|
| 6306 FBA A mapping file | Cause: Fieldbus adapter A mapping file read error. Remedy:
|
| 6481 Task overload | Cause: Internal fault. Remedy:
|
| 6487 Stack overflow | Cause: Internal fault. Remedy:
|
| 64A1 Internal file load | Cause: File read error. Remedy:
|
| 64A4 Rating ID fault | Cause: Rating ID load error. Remedy:
|
| 64A6 Adaptive program | Cause: Error running the adaptive program. Remedy:
|
| 64A6 (Aux: 000A) Adaptive program | Cause: Program corrupted or block non-existent. Remedy:
|
| 64A6 (Aux: 000C) Adaptive program | Cause: Required block input missing. Remedy:
|
| 64A6 (Aux: 0011) Adaptive program | Cause: Program too large. Remedy:
|
| 64A6 (Aux: 0012) Adaptive program | Cause: Program is empty. Remedy:
|
| 64A6 (Aux: 001C) Adaptive program | Cause: A non-existing parameter or block is used in the program. Remedy:
|
| 64A6 (Aux: 001D) Adaptive program | Cause: Parameter type invalid for selected pin. Remedy:
|
| 64A6 (Aux: 001E) Adaptive program | Cause: Output to parameter failed because parameter was write-protected. Remedy:
|
| 64A6 (Aux: 0023) Adaptive program | Cause: Program file incompatible with current firmware version. Remedy:
|
| 64B1 Internal SSW fault | Cause: Internal fault. Remedy:
|
| 64B2 User set fault | Cause: Loading of user parameter set failed (set missing, incompatible, or drive switched off during load). Remedy:
|
| 64E1 Kernel overload | Cause: Operating system error. Remedy:
|
| 6581 Parameter system | Cause: Parameter load or save failed. Remedy:
|
| 6591 Backup/Restore timeout | Cause: Control panel or PC-tool failed to communicate during backup/restore. Remedy:
|
| 65A1 FBA A parameter conflict | Cause: Drive lacks functionality requested by PLC, or functionality not activated. Remedy:
|
| 6681 EFB comm loss | Cause: Communication break in embedded fieldbus (EFB). Remedy:
|
| 6682 EFB config file | Cause: Embedded fieldbus (EFB) configuration file could not be read. Remedy:
|
| 6683 EFB invalid parameterization | Cause: EFB parameter settings inconsistent or not compatible with protocol. Remedy:
|
| 6684 EFB load fault | Cause: EFB protocol firmware could not be loaded or version mismatch. Remedy:
|
| 6685 EFB fault 2 | Cause: Fault reserved for the EFB protocol application. Remedy:
|
| 6686 EFB fault 3 | Cause: Fault reserved for the EFB protocol application. Remedy:
|
| 6882 Text 32-bit table overflow | Cause: Internal fault. Remedy:
|
| 6885 Text file overflow | Cause: Internal fault. Remedy:
|
| 7081 Control panel loss | Cause: Control panel or PC tool selected as active control location has ceased communicating. Remedy:
|
| 7082 I/O module comm loss | Cause: Communication between IO module and drive is not working properly. Remedy:
|
| 7085 Incompatible option module | Cause: Fieldbus option module not supported. Remedy:
|
| 7086 AI Overvoltage | Cause: An overvoltage has been detected on an analog input (switched to voltage mode temporarily). Remedy:
|
| 7087 I/O module configuration | Cause: I/O module configuration not supported or illegal. Remedy:
|
| 7087 (Aux: 0001) I/O config | Cause: S1/S2 DIP switch position on BIO-01 has changed after power up. Remedy:
|
| 7087 (Aux: 0002) I/O config | Cause: S1/S2 DIP switch positions are invalid (DO1 would be in both S1 and S2 pins). Remedy:
|
| 7121 Motor stall | Cause: Motor is operating in stall region (excessive load or insufficient power). Remedy:
|
| 7122 Motor overload | Cause: Motor current is too high. Remedy:
|
| 7183 BR excess temperature | Cause: Brake resistor temperature has exceeded fault limit (param 43.11). Remedy:
|
| 7192 BC IGBT excess temperature | Cause: Brake chopper IGBT temperature has exceeded internal fault limit. Remedy:
|
| 7310 Overspeed | Cause: Motor is turning faster than highest allowed speed. Remedy:
|
| 73B0 Emergency ramp failed | Cause: Emergency stop did not finish within expected time. Remedy:
|
| 73F0 Overfrequency | Cause: Maximum allowed output frequency exceeded. Remedy:
|
| 73F0 (Aux: 0xFA) Overfrequency | Cause: Motor turning faster than allowed due to min/max freq settings or high supply voltage. Remedy:
|
| 7510 FBA A communication | Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost. Remedy:
|
| 8001 ULC underload fault | Cause: User load curve: Signal has been too long under the underload curve. Remedy:
|
| 8002 ULC overload fault | Cause: User load curve: Signal has been too long over the overload curve. Remedy:
|
| 80A0 AI supervision | Cause: An analog signal is outside the limits specified for the analog input. Remedy:
|
| 80A0: 0001 AI1LessMIN | Cause: Analog Input 1 value is less than minimum setting. Remedy:
|
| 80A0: 0002 AI1GreaterMAX | Cause: Analog Input 1 value is greater than maximum setting. Remedy:
|
| 80A0: 0003 AI2LessMIN | Cause: Analog Input 2 value is less than minimum setting. Remedy:
|
| 80A0: 0004 AI2GreaterMAX | Cause: Analog Input 2 value is greater than maximum setting. Remedy:
|
| 80B0 Signal supervision 1 | Cause: Fault generated by the signal supervision function 1. Remedy:
|
| 80B1 Signal supervision 2 | Cause: Fault generated by the signal supervision function 2. Remedy:
|
| 80B2 Signal supervision 3 | Cause: Fault generated by the signal supervision function 3. Remedy:
|
| 80B3 Signal supervision 4 | Cause: Fault generated by the signal supervision function 4. Remedy:
|
| 80B4 Signal supervision 5 | Cause: Fault generated by the signal supervision function 5. Remedy:
|
| 80B5 Signal supervision 6 | Cause: Fault generated by the signal supervision function 6. Remedy:
|
| 9081 External fault 1 | Cause: Fault in external device 1. Remedy:
|
| 9082 External fault 2 | Cause: Fault in external device 2. Remedy:
|
| 9083 External fault 3 | Cause: Fault in external device 3. Remedy:
|
| 9084 External fault 4 | Cause: Fault in external device 4. Remedy:
|
| 9085 External fault 5 | Cause: Fault in external device 5. Remedy:
|
| D401 Max cleaning fault | Cause: The maximum number of cleanings are reached in the defined time. The pump cleaning is unable to clean the pump and hence, manual cleaning is required. Remedy:
|
| D404 Running dry | Cause: Dry run protection is activated. Remedy:
|
| D405 Pipe fill-timeout | Cause: Soft pipe fill has reached timeout limit. The PID output is not reached the setpoint after reference ramping is ended and the timeout limit is elapsed. Remedy:
|
| D40C Cavitation detected | Cause: The pump is not getting enough liquid. Remedy:
|
| FA81 Safe torque off 1 | Cause: Safe torque off function is active, ie. STO circuit 1 is broken. Remedy:
|
| FA82 Safe torque off 2 | Cause: Safe torque off function is active, ie. STO circuit 2 is broken. Remedy:
|
| FF61 ID run | Cause: Motor ID run was not completed successfully. Remedy:
|
| FF61: 0001 Maximum current limit too low | Cause: Current limit restriction during ID run. Remedy:
|
| FF61: 0002 Maximum speed limit or calculated field weakening point too low | Cause: Speed/Frequency limits restricted. Remedy:
|
| FF61: 0003 Maximum torque limit too low | Cause: Torque limit restricted. Remedy:
|
| FF61: 0004 Current measurement calibration | Cause: Calibration did not finish within reasonable time. Remedy:
|
| FF61: 0005...0008 Internal error | Cause: Internal software/hardware error during ID run. Remedy:
|
| FF61: 0009 Acceleration fail (Async motors) | Cause: Acceleration did not finish within reasonable time. Remedy:
|
| FF61: 000A Deceleration fail (Async motors) | Cause: Deceleration did not finish within reasonable time. Remedy:
|
| FF61: 000B Speed drop (Async motors) | Cause: Speed dropped to zero during ID run. Remedy:
|
| FF61: 000C First accel fail (PM motors) | Cause: First acceleration did not finish within reasonable time. Remedy:
|
| FF61: 000D Second accel fail (PM motors) | Cause: Second acceleration did not finish within reasonable time. Remedy:
|
| FF61: 000E...0010 Internal error | Cause: Internal error. Remedy:
|
| FF61: 0011 Pulse test error (Synch Reluctance) | Cause: Pulse test error. Remedy:
|
| FF61: 0012 Motor too large for advanced standstill ID run | Cause: Motor size incompatibility. Remedy:
|
| FF61: 0013 Motor data error (Async motors) | Cause: Motor data error. Remedy:
|
| FF63 STO diagnostics failure | Cause: SW internal malfunction. Remedy:
|
| FF81 FB A force trip | Cause: A fault trip command has been received through fieldbus adapter A. Remedy:
|
| FF8E EFB force trip | Cause: A fault trip command has been received through the embedded fieldbus interface. Remedy:
|
How to Clear & Reset ABB ACS480 Drive Faults
- Keypad Reset: Press the red Reset softkey on the assistant control panel. If operating in remote automation mode (REM), press the Loc/Rem key to switch to local mode (LOC) first before attempting manual reset.
- Digital Input Reset (DI): If mapped in parameter 31.11 (Fault reset selection) or via Menu > Primary settings > Advanced functions > Reset faults manually, provide a momentary 24V pulse to the assigned digital input terminal (DI1 to DI6).
- Drive Composer PC Tool: Connect your PC via the USB mini-B port on the control panel, open Drive Composer (Entry or Pro), and click the “Reset” button in the top drive status bar.
- Fieldbus Control Word: Pulse Bit 7 (Fault Reset) from `0` to `1` in Control Word 1 using the embedded Modbus RTU interface (RIIO-01 / EIA-485) or optional fieldbus adapter module (FPBA-01, FENA-21, etc.).
- Power Cycle: Disconnect the incoming AC line power, wait at least 5 minutes for the intermediate DC bus capacitors to discharge completely until all keypad LEDs turn off, and then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [UDC+] and [UDC-] before inspecting motor leads, opening terminal covers, or touching terminals U2, V2, and W2 on the ABB ACS480 drive.