ABB ACS510 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the ABB ACS510 standard fan and pump drive series. Search or filter through the complete fault code directory below.

Standard Fan & Pump Drive Power: 1.1 to 160 kW (1.5 to 215 HP) PFC Multi-Pump Macros
Power Range 1.1 – 160 kW (1.5 – 215 HP)
Supply Voltage 380–480V AC (3-Phase)
Control Modes Scalar & Vector Pump Control
Operator Interface Assistant Control Panel (ACS-CP-D)

Complete ABB ACS510 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F0001, F0016, or Overcurrent).

Fault Code and MeaningCause and Remedy
F0001
OVERCURRENT

Cause: Output current is excessive.



Remedy:

  • Check for excessive motor load.

  • Check for insufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2).

  • Check for faulty motor, motor cables or connections.


F0002
DC OVERVOLT

Cause: Intermediate circuit DC voltage is excessive.



Remedy:

  • Check for static or transient overvoltages in the input power supply.

  • Check for insufficient deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2).

  • Check for undersized brake chopper (if present).

  • Verify that overvoltage controller is ON (using parameter 2005).


F0003
DEV OVERTEMP

Cause: Drive heatsink is overheated. Temperature is at or above limit (R1…R4: 115 °C, R5/R6: 125 °C).



Remedy:

  • Check for Fan failure.

  • Check for Obstructions in the air flow.

  • Check for Dirt or dust coating on the heat sink.

  • Check for Excessive ambient temperature.

  • Check for Excessive motor load.


F0004
SHORT CIRC

Cause: Fault current.



Remedy:

  • Check for a short-circuit in the motor cable(s) or motor.

  • Check for Supply disturbances.


F0006
DC UNDERVOLT

Cause: Intermediate circuit DC voltage is not sufficient.



Remedy:

  • Check for missing phase in the input power supply.

  • Check for blown fuse.

  • Check for Undervoltage on mains.


F0007
AI1 LOSS

Cause: Analog input 1 loss. Analog input value is less than AI1FAULT LIMIT (3021).



Remedy:

  • Check source and connection for analog input.

  • Check Parameter settings for AI1FAULT LIMIT (3021) and 3001 AI

F0008
AI2 LOSS

Cause: Analog input 2 loss. Analog input value is less than AI2 FAULT LIMIT (3022).



Remedy:

  • Check source and connection for analog input.

  • Check Parameter settings for AI2 FAULT LIMIT (3022) and 3001 AI

F0009
MOT OVERTEMP

Cause: Motor is too hot, based on either the drive’s estimate or on temperature feedback.



Remedy:

  • Check for overloaded motor.

  • Adjust the parameters used for the estimate (3005…3009).

  • Check the temperature sensors and Group 35 parameters.


F0010
PANEL LOSS

Cause: Panel communication is lost.



Remedy:

  • Check Communication lines and connections.

  • Check Parameter 3002 PANEL COMM ERR.

  • Check Parameters in Group 10: Command Inputs and Group 11: Reference Select (if drive operation is REM).


F0012
MOTOR STALL

Cause: Motor or process stall. Motor is operating in the stall region.



Remedy:

  • Check for Excessive load.

  • Check for Insufficient motor power.

  • Check Parameters 3010…3012.


F0014
EXT FAULT 1

Cause: Digital input defined to report first external fault is active.



Remedy:

  • See parameter 3003 EXTERNAL FAULT 1.


F0015
EXT FAULT 2

Cause: Digital input defined to report second external fault is active.



Remedy:

  • See parameter 3004 EXTERNAL FAULT 2.


F0016
EARTH FAULT

Cause: Possible ground fault detected in the motor or motor cables.



Remedy:

  • Check for/correct faults in the input wiring.

  • Verify that motor cable does not exceed maximum specified length.

  • Note: A delta grounded input power supply and motor cables with high capacitance may result in erroneous error reports.


F0018
THERM FAIL

Cause: Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted.



Remedy:

  • Contact your local ABB representative.


F0022
SUPPLY PHASE

Cause: Ripple voltage in the DC link is too high.



Remedy:

  • Check for Missing mains phase.

  • Check for Blown fuse.


F0034
MOTOR PHASE

Cause: Fault in the motor circuit. One of the motor phases is lost.



Remedy:

  • Check for Motor fault.

  • Check for Motor cable fault.

  • Check for Thermal relay fault (if used).

  • Check for Internal fault.


F0035
OUTPUT WIRING

Cause: Possible power wiring error detected (improper connection between input power and drive output).



Remedy:

  • Check Proper input wiring – line voltage is NOT connected to drive output.

  • The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT.


F0037
CB OVERTEMP

Cause: Drive control board is overheated. The fault trip limit is 88 °C.



Remedy:

  • Check for Excessive ambient temperature.

  • Check for Fan failure.

  • Check for Obstructions in the air flow.


F1000
PAR HZRPM

Cause: Parameter values are inconsistent.



Remedy:

  • Check if 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ.

  • Check if 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50).

  • Check if 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50).


F1001
PAR PFC REF NEG

Cause: Parameter values are inconsistent.



Remedy:

  • Check if 2007 MINIMUM FREQ is negative, when 8123 PFC ENABLE is active.


F1003
PAR AI SCALE

Cause: Parameter values are inconsistent.



Remedy:

  • Check: 1301 AI1 MIN > 1302 AI1 MAX.

  • Check: 1304 AI2 MIN > 1305 AI2 MAX.


F1005
PAR PCU 2

Cause: Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power.



Remedy:

  • Check relationship: 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 3.0


F1012
PAR PFC IO 1

Cause: IO configuration is not complete – not enough relays are parameterized to PFC.



Remedy:

  • Check for conflict between Group 14, parameter 8117, NR OF AUX MOT, and parameter 8118, AUTOCHNG INTERV.


A2001
OVERCURRENT

Cause: Current limiting controller is active.


Remedy:

  • Check for excessive motor load.

  • Check for insufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2).

  • Check for faulty motor, motor cables or connections.


A2002
OVERVOLTAGE

Cause: Overvoltage controller is active.


Remedy:

  • Check for static or transient overvoltages in the input power supply.

  • Check for insufficient deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2).


A2003
UNDERVOLTAGE

Cause: Undervoltage controller is active.


Remedy:

  • Check for undervoltage on mains.


A2004
DIR LOCK

Cause: The change in direction being attempted is not allowed.


Remedy:

  • Do not attempt to change the direction of motor rotation.

  • Or, change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).


A2005
I/O COMM

Cause: Fieldbus communication has timed out.


Remedy:

  • Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME).

  • Check communication settings (Group 51 or 53 as appropriate).

  • Check for poor connections and/or noise on line.


A2006
AI1 LOSS

Cause: Analog input 1 is lost, or value is less than the minimum setting.


Remedy:

  • Check input source and connections.

  • Check parameter that sets the minimum (3021).

  • Check parameter that sets the Alarm/Fault operation (3001).


A2007
AI2 LOSS

Cause: Analog input 2 is lost, or value is less than the minimum setting.


Remedy:

  • Check input source and connections.

  • Check parameter that sets the minimum (3022).

  • Check parameter that sets the Alarm/Fault operation (3001).


A2008
PANEL LOSS

Cause: Panel communication is lost.


Remedy:

  • Check communication lines and connections.

  • Check parameter 3002 PANEL COMM ERR.

  • Check parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).


A2009
DEVICE OVERTEMP

Cause: Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault may be near.

R1…R4 & R7/R8: 100 °C (212 °F)

R5/R6: 110 °C (230 °F)


Remedy:

  • Check for fan failure.

  • Check for obstructions in the air flow.

  • Check for dirt or dust coating on the heat sink.

  • Check for excessive ambient temperature.

  • Check for excessive motor load.


A2010
MOTOR TEMP

Cause: Motor is hot, based on either the drive’s estimate or on temperature feedback.


Remedy:

  • Check for overloaded motor.

  • Adjust the parameters used for the estimate (3005…3009).

  • Check the temperature sensors and Group 35 parameters.


A2012
MOTOR STALL

Cause: Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.


Remedy:

  • Check motor load and stall parameters.


A2013
AUTORESET

Cause: The drive is about to perform an automatic fault reset, which may start the motor.


Remedy:

  • To control automatic reset, use parameter group 31 AUTOMATIC RESET.


A2014
AUTOCHANGE

Cause: The PFC autochange function is active.


Remedy:

  • To control PFC, use parameter group 81 PFC CONTROL.


A2015
PFC I LOCK

Cause: The PFC interlocks are active, which means the drive cannot start the motor(s).


Remedy:

  • Check Interlock connections and signals.


A2018
PID SLEEP

Cause: The PID sleep function is active. Motor could accelerate when sleep ends.


Remedy:

  • To control PID sleep, use parameters 4022…4026 or 4122…4126.


A2021
START ENABLE 1 MISSING

Cause: The Start Enable 1 signal is missing.


Remedy:

  • Check Digital input configuration.

  • Check Communication settings.

  • To control Start Enable 1 function, use parameter 1608.


A2022
START ENABLE 2 MISSING

Cause: The Start Enable 2 signal is missing.


Remedy:

  • Check Digital input configuration.

  • Check Communication settings.

  • To control Start Enable 2 function, use parameter 1609.


A2023
EMERGENCY STOP

Cause: Emergency stop activated.


Remedy:

  • Check emergency stop circuit and release the E-stop button.


A2024
Accessory Alarm

Cause: Accessory specific alarm.


Remedy:

  • Refer to the appropriate accessory manual.


A2025
FIRST START

Cause: This alarm occurs a few seconds during the scalar flystart first active.


Remedy:

  • No action required (Informational).


A2027
USER LOAD CURVE

Cause: Condition defined by parameter 3701 USER LOAD C MODE has been valid longer than half of the time defined by 3703.


Remedy:

  • Check load conditions and User Load Curve parameters.


A2028
START DELAY

Cause: Shown during the Start delay.


Remedy:

  • See parameter 2113 START DELAY.


A5001
Panel Alarm

Cause: Drive is not responding.


Remedy:

  • Check panel connection.


A5002
Panel Alarm

Cause: The communication profile is incompatible with the drive.


Remedy:

  • Check drive firmware and panel compatibility.


A5010
Panel Alarm

Cause: The panel’s parameter backup file is corrupted.


Remedy:

  • Retry backup or reset panel.


A5011
Panel Alarm

Cause: Drive is controlled from another source.


Remedy:

  • Change control to Local/Panel if required.


A5012
Panel Alarm

Cause: Rotation direction is locked.


Remedy:

  • Check direction lock parameters.


A5013
Panel Alarm

Cause: Button is disabled, because start is inhibited.


Remedy:

  • Remove start inhibit condition.


A5014
Panel Alarm

Cause: Button is disabled, because drive is faulted.


Remedy:

  • Reset the active fault.


A5015
Panel Alarm

Cause: Button is disabled, because local mode lock is on.


Remedy:

  • Disable local mode lock to use the button.


A5018
Panel Alarm

Cause: Parameter default value can’t be found.


Remedy:

  • Check parameter set availability.


A5019
Panel Alarm

Cause: Writing a non-zero value is prohibited (can only write a zero value).


Remedy:

  • Only write 0 to this parameter.


A5020
Panel Alarm

Cause: Group or parameter does not exist or parameter value is inconsistent.


Remedy:

  • Check parameter existence.


A5021
Panel Alarm

Cause: Group or parameter is hidden.


Remedy:

  • Check access levels.


A5022
Panel Alarm

Cause: Group or parameter is write protected.


Remedy:

  • Disable write protection.


A5023
Panel Alarm

Cause: Modification is not allowed while the drive is running.


Remedy:

  • Stop the drive to modify parameter.


A5024
Panel Alarm

Cause: Drive is busy.


Remedy:

  • Try again later.


A5025
Panel Alarm

Cause: Write is not allowed while upload or download is in progress.


Remedy:

  • Wait for transfer to complete.


A5026
Panel Alarm

Cause: Value is at or below low limit.


Remedy:

  • Increase value.


A5027
Panel Alarm

Cause: Value is at or above high limit.


Remedy:

  • Decrease value.


A5028
Panel Alarm

Cause: Value is invalid – doesn't match any values in the discrete values list.


Remedy:

  • Select a valid value.


A5029
Panel Alarm

Cause: Memory is not ready.


Remedy:

  • Try again.


A5030
Panel Alarm

Cause: Request is invalid.


Remedy:

  • Check request parameters.


A5031
Panel Alarm

Cause: Drive is not ready, e.g due to Low DC voltage.


Remedy:

  • Check drive input power and DC bus.


A5032
Panel Alarm

Cause: Parameter error was detected.


Remedy:

  • Check parameter configurations.


A5040
Panel Alarm

Cause: Selected parameter set can’t be found in the current parameter backup.


Remedy:

  • Perform a new backup.


A5041
Panel Alarm

Cause: Parameter backup doesn't fit into memory.


Remedy:

  • Check memory capacity.


A5042
Panel Alarm

Cause: Selected parameter set can’t be found in the current parameter backup.


Remedy:

  • Check backup file.


A5043
Panel Alarm

Cause: No start inhibit was granted.


Remedy:

  • Check start inhibit status.


A5044
Panel Alarm

Cause: Parameter backup versions do not match.


Remedy:

  • Ensure drive firmware and backup versions match.


A5050
Panel Alarm

Cause: Parameter upload was aborted.


Remedy:

  • Retry upload.


A5051
Panel Alarm

Cause: File error was detected.


Remedy:

  • Check file integrity.


A5052
Panel Alarm

Cause: Parameter upload attempt has failed.


Remedy:

  • Retry upload.


A5060
Panel Alarm

Cause: Parameter download was aborted.


Remedy:

  • Retry download.


A5062
Panel Alarm

Cause: Parameter download attempt has failed.


Remedy:

  • Retry download.


A5070
Panel Alarm

Cause: Panel backup memory write error was detected.


Remedy:

  • Check panel memory.


A5071
Panel Alarm

Cause: Panel backup memory read error was detected.


Remedy:

  • Check panel memory.


A5080
Panel Alarm

Cause: Operation is not allowed, because the drive is not in local mode.


Remedy:

  • Switch drive to local mode.


A5081
Panel Alarm

Cause: Operation is not allowed, because a fault is active.


Remedy:

  • Reset fault before proceeding.


A5082
Panel Alarm

Cause: Operation is not allowed, because override mode is enabled.


Remedy:

  • Disable override mode.


A5083
Panel Alarm

Cause: Operation is not allowed, because parameter lock is not open.


Remedy:

  • Open parameter lock.


A5084
Panel Alarm

Cause: Operation is not allowed, because drive is busy.


Remedy:

  • Try again later.


A5085
Panel Alarm

Cause: Download is not allowed, because drive types are incompatible.


Remedy:

  • Check drive type compatibility.


A5086
Panel Alarm

Cause: Download is not allowed, because drive models are incompatible.


Remedy:

  • Check drive model compatibility.


A5087
Panel Alarm

Cause: Download is not allowed, because parameter sets do not match.


Remedy:

  • Check parameter sets.


A5088
Panel Alarm

Cause: Operation failed, because a drive memory error was detected.


Remedy:

  • Contact support or replace control board.


A5089
Panel Alarm

Cause: Download failed, because a CRC error was detected.


Remedy:

  • Retry download, check cable.


A5090
Panel Alarm

Cause: Download failed, because a data processing error was detected.


Remedy:

  • Retry download.


A5091
Panel Alarm

Cause: Operation failed, because a parameter error was detected.


Remedy:

  • Check parameter data.


A5092
Panel Alarm

Cause: Download failed, because parameter sets do not match.


Remedy:

  • Verify parameter set compatibility.


How to Clear & Reset ABB ACS510 Drive Faults

  1. Assistant Control Panel Reset: Press the red RESET softkey directly on the Assistant Control Panel (or press the STOP button). If operating under remote automation control (REM), switch to local mode (LOC) first.
  2. Digital Input Reset (DI): If configured in parameter 1604 (FAULT RESET SEL), toggle the assigned digital input terminal (DI1 to DI6 on terminal block X1).
  3. DriveWindow Light Software: Connect your PC via the front panel communication cable, open DriveWindow Light, and click “Fault Reset” in the drive status monitor.
  4. Modbus RTU Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the embedded fieldbus communication control word via RS-485 serial link.
  5. Power Cycle: Disconnect main AC line power, wait until the control panel display turns off completely (approx. 5 minutes for internal capacitor discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [UDC+] and [UDC-] before inspecting motor leads, opening terminal covers, or touching terminals U2, V2, and W2 on the ABB ACS510 drive.