ABB MicroFlex e100 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the ABB MicroFlex e100 real-time Ethernet servo drive series. Search or filter through the complete fault code directory below.
Current Rating
3 – 9 A Continuous (Up to 200% Peak)
Supply Voltage
105–250V AC (1-Phase / 3-Phase)
Motor Feedback
Resolver / EnDat / Incremental Encoder
Motion Bus
Ethernet POWERLINK / CANopen DS402
Complete ABB MicroFlex e100 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type 10001, 10006, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Status LED: Solid Green Normal Operation | Cause: Drive is enabled and functioning normally. Remedy:
|
| Status LED: Flickering Green Firmware Update | Cause: Firmware download or update is in progress. Remedy:
|
| Status LED: Solid Red Drive Disabled | Cause: Drive is disabled, but no errors are latched. Remedy:
|
| Error Code 1 (1 Red Flash) DC bus overvoltage trip | Cause: DC bus voltage exceeded the limit. Remedy:
|
| Error Code 2 (2 Red Flashes) IPM trip | Cause: Integrated Power Module (IPM) fault. Remedy:
|
| Error Code 3 (3 Red Flashes) Overcurrent trip | Cause: Current exceeded limits. Remedy:
|
| Error Code 4 (4 Red Flashes) Overspeed trip | Cause: Motor exceeded speed limit. Remedy:
|
| Error Code 5 (5 Red Flashes) Feedback trip | Cause: Issue with encoder or feedback device. Remedy:
|
| Error Code 6 (6 Red Flashes) Motor overload (I²t) trip | Cause: Motor has operated above rated current for too long. Remedy:
|
| Error Code 7 (7 Red Flashes) Overtemperature trip | Cause: Drive or motor overheating. Remedy:
|
| Error Code 8 (8 Red Flashes) Drive overload (It) trip | Cause: Drive internal overload. Remedy:
|
| Error Code 9 (9 Red Flashes) Following error trip | Cause: Difference between demand and actual position is too large. Remedy:
|
| Error Code 10 (10 Red Flashes) Error input triggered | Cause: External error input activated. Remedy:
|
| Error Code 11 (11 Red Flashes) Phase search error | Cause: Failed to find commutation angle. Remedy:
|
| Error Code 12 (12 Red Flashes) All other errors | Cause: Internal supply error, encoder supply error, parameter restore failure, or power base not recognized. Remedy:
|
| Status LED: Alt. Red/Green Undervoltage warning | Cause: DC-bus voltage dropped below powerbase undervoltage level (no AC power). Remedy:
|
| Communication Fault Status LED is off | Cause: Control circuit power is missing or disconnected. Remedy:
|
| Firmware Fault ETHERNET LEDs blinking green and red simultaneously | Cause: Firmware download failed or no firmware present. Remedy:
|
| Connection Fault Mint WorkBench fails to detect the MicroFlex e100 | Cause: Cabling issues, driver issues, or incorrect configuration. Remedy:
|
| Power On Fault Drive does not start when applying AC power | Cause: Motor output phases might be short-circuited. Remedy:
|
| Mint WorkBench Fault The Spy window does not update | Cause: System refresh has been disabled. Remedy:
|
| USB Communication Fault Mint WorkBench loses contact while using USB | Cause: Power loss or PC USB interface issue. Remedy:
|
| Error 10010 Cannot enable the MicroFlex e100 | Cause: Drive enable input issue. Remedy:
|
| Tuning Issue Motor is unstable when enabled | Cause: Load coupling or tuning parameters. Remedy:
|
| Ethernet Fault Slow response when issuing command from host | Cause: TCP/IP socket closed due to inactivity (30 seconds). Remedy:
|
| CANopen Fault CANopen bus is 'passive' | Cause: Tx/Rx errors > 127 (Passive Threshold). Remedy:
|
| CANopen Fault CANopen bus is 'off' | Cause: Tx/Rx errors > 255 (Fatal Threshold). Remedy:
|
| CANopen Fault Manager node cannot scan/recognize a node | Cause: Node configuration or compatibility issue. Remedy:
|
How to Clear & Reset ABB MicroFlex e100 Drive Faults
- Mint Workbench PC Software: Connect via USB or Ethernet, open Mint Workbench, navigate to the Drive Status / Error Log pane, and click the “Reset Drive” button.
- Programmatic Mint Command: Issue the Mint software instruction
DRIVEFAULTRESETor setDRIVEENABLE = 1in your control application script. - Digital Input Reset: Trigger the digital input terminal configured for the Fault Reset function (mapped in Mint Workbench digital I/O assignment).
- Ethernet POWERLINK / CANopen Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the DS402 motion profile control word via the central PLC or motion controller.
- Power Cycle: Disconnect AC line power and 24V DC logic backup power, wait until the internal DC bus completely discharges (display turns off completely), and reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [UDC+] and [UDC-] before inspecting servo motor leads, resolver feedback lines, or touching motor power terminals U, V, and W on the ABB MicroFlex e100 drive.