ABB MicroFlex e100 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the ABB MicroFlex e100 real-time Ethernet servo drive series. Search or filter through the complete fault code directory below.

Real-Time Ethernet POWERLINK Current: 3 to 9 A Continuous Multitasking Mint Motion Control
Current Rating 3 – 9 A Continuous (Up to 200% Peak)
Supply Voltage 105–250V AC (1-Phase / 3-Phase)
Motor Feedback Resolver / EnDat / Incremental Encoder
Motion Bus Ethernet POWERLINK / CANopen DS402

Complete ABB MicroFlex e100 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 10001, 10006, or Overcurrent).

Fault Code and MeaningCause and Remedy
Status LED: Solid Green

Normal Operation

Cause:

Drive is enabled and functioning normally.


Remedy:


  • None required.


Status LED: Flickering Green

Firmware Update

Cause:

Firmware download or update is in progress.


Remedy:


  • Wait for the update to complete. Do not remove power.


Status LED: Solid Red

Drive Disabled

Cause:

Drive is disabled, but no errors are latched.


Remedy:


  • Enable the drive to resume operation.


Error Code 1 (1 Red Flash)

DC bus overvoltage trip

Cause:

DC bus voltage exceeded the limit.


Remedy:


  • Check AC power connection.

  • Check braking resistor/regeneration.

  • Refer to Mint WorkBench "Error Handling" book (Press F1).


Error Code 2 (2 Red Flashes)

IPM trip

Cause:

Integrated Power Module (IPM) fault.


Remedy:


  • Check for short circuits.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 3 (3 Red Flashes)

Overcurrent trip

Cause:

Current exceeded limits.


Remedy:


  • Check motor wiring and mechanics.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 4 (4 Red Flashes)

Overspeed trip

Cause:

Motor exceeded speed limit.


Remedy:


  • Check tuning and load.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 5 (5 Red Flashes)

Feedback trip

Cause:

Issue with encoder or feedback device.


Remedy:


  • Check feedback cables and connections.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 6 (6 Red Flashes)

Motor overload (I²t) trip

Cause:

Motor has operated above rated current for too long.


Remedy:


  • Check sizing and duty cycle.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 7 (7 Red Flashes)

Overtemperature trip

Cause:

Drive or motor overheating.


Remedy:


  • Check ambient temperature and cooling.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 8 (8 Red Flashes)

Drive overload (It) trip

Cause:

Drive internal overload.


Remedy:


  • Check load and duty cycle.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 9 (9 Red Flashes)

Following error trip

Cause:

Difference between demand and actual position is too large.


Remedy:


  • Check mechanics (stalling) and tuning.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 10 (10 Red Flashes)

Error input triggered

Cause:

External error input activated.


Remedy:


  • Check external safety devices or inputs.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 11 (11 Red Flashes)

Phase search error

Cause:

Failed to find commutation angle.


Remedy:


  • Check motor setup and parameters.

  • Refer to Mint WorkBench "Error Handling" book.


Error Code 12 (12 Red Flashes)

All other errors

Cause:

Internal supply error, encoder supply error, parameter restore failure, or power base not recognized.


Remedy:


  • Check power supplies and encoder wiring.

  • Refer to Mint WorkBench "Error Handling" book.


Status LED: Alt. Red/Green

Undervoltage warning

Cause:

DC-bus voltage dropped below powerbase undervoltage level (no AC power).


Remedy:


  • Check that AC power is connected.


Communication Fault

Status LED is off

Cause:

Control circuit power is missing or disconnected.


Remedy:


  • Check that the 24 V DC control circuit supply is connected correctly to connector X2.

  • Ensure 24 V DC supply is switched on.


Firmware Fault

ETHERNET LEDs blinking green and red simultaneously

Cause:

Firmware download failed or no firmware present.


Remedy:


  • Download new firmware to the MicroFlex e100.


Connection Fault

Mint WorkBench fails to detect the MicroFlex e100

Cause:

Cabling issues, driver issues, or incorrect configuration.


Remedy:


  • Ensure the drive is powered and Status LED is illuminated.

  • Check Ethernet or USB cable connections.

  • Try an alternative cable or different PC port.

  • In Mint WorkBench "Select Controller" dialog, increase "Search up to Nodexx" value.

  • For USB: Check device is listed in Windows Device Manager as 'USB Motion Controller'.

  • For Ethernet: Check PC Ethernet port is configured for TCP/IP operation.


Power On Fault

Drive does not start when applying AC power

Cause:

Motor output phases might be short-circuited.


Remedy:


  • Check that motor output phases are not short circuited.

  • Remove all power, correct the short circuit, and restart the drive.


Mint WorkBench Fault

The Spy window does not update

Cause:

System refresh has been disabled.


Remedy:


  • Go to Tools > Options > System tab.

  • Choose a System Refresh Rate (500 ms recommended).


USB Communication Fault

Mint WorkBench loses contact while using USB

Cause:

Power loss or PC USB interface issue.


Remedy:


  • Check that the MicroFlex e100 is powered.

  • Check that 'USB Motion Controller' is listed in Windows Device Manager.


Error 10010

Cannot enable the MicroFlex e100

Cause:

Drive enable input issue.


Remedy:


  • Check the drive enable input on connector X3 pins 9 and 19 is connected and powered correctly.


Tuning Issue

Motor is unstable when enabled

Cause:

Load coupling or tuning parameters.


Remedy:


  • Check that the load is firmly coupled to the motor.

  • Use Mint WorkBench Drive Setup Wizard to confirm motor data.

  • Use Mint WorkBench Autotune Wizard to retune the motor.

  • If still unstable, lower bandwidth in Autotune Options (Current/Position/Speed sliders).


Ethernet Fault

Slow response when issuing command from host

Cause:

TCP/IP socket closed due to inactivity (30 seconds).


Remedy:


  • Include a timed procedure in your application (period < 30s) that issues a command (e.g., reading AAABuild) to keep the socket open.


CANopen Fault

CANopen bus is 'passive'

Cause:

Tx/Rx errors > 127 (Passive Threshold).


Remedy:


  • Check 12-24 V is applied to OPT 1 connector (pins 9 and 6/3).

  • Ensure at least one other node is on the network.

  • Check termination is only at ends.

  • Check baud rate and unique node IDs.

  • Check integrity of CAN cables.


CANopen Fault

CANopen bus is 'off'

Cause:

Tx/Rx errors > 255 (Fatal Threshold).


Remedy:


  • Remove source of errors (check cabling, termination, power).

  • Reset bus using Mint BUSRESET keyword or reset the drive.


CANopen Fault

Manager node cannot scan/recognize a node

Cause:

Node configuration or compatibility issue.


Remedy:


  • Check node has a unique ID.

  • Ensure node supports node guarding (MicroFlex e100 does not support Heartbeat).

  • Power-cycle the node in question.

  • Note: Only DS401/DS403/ABB nodes are recognized by NODESCAN.


How to Clear & Reset ABB MicroFlex e100 Drive Faults

  1. Mint Workbench PC Software: Connect via USB or Ethernet, open Mint Workbench, navigate to the Drive Status / Error Log pane, and click the “Reset Drive” button.
  2. Programmatic Mint Command: Issue the Mint software instruction DRIVEFAULTRESET or set DRIVEENABLE = 1 in your control application script.
  3. Digital Input Reset: Trigger the digital input terminal configured for the Fault Reset function (mapped in Mint Workbench digital I/O assignment).
  4. Ethernet POWERLINK / CANopen Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the DS402 motion profile control word via the central PLC or motion controller.
  5. Power Cycle: Disconnect AC line power and 24V DC logic backup power, wait until the internal DC bus completely discharges (display turns off completely), and reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [UDC+] and [UDC-] before inspecting servo motor leads, resolver feedback lines, or touching motor power terminals U, V, and W on the ABB MicroFlex e100 drive.