A2006 alarm in ABB ACS150 drive

Home/ABB/ABB ACS150 drive/A2006 alarm in ABB ACS150 drive

The A2006 alarm indicates that the analog input 1 (AI1) reference signal has dropped below the minimum supervision threshold set in parameter 3021 (AI1 FAULT LIMIT). Unlike a tripping fault, this alarm warns operators that reference frequency loss has occurred while the drive executes its programmed fail-safe speed response.

When analog input AI1 drops below the configured percentage (typically 4 mA or 2 V when programmed for live-zero operation), the ACS150 control board detects an open-circuit loop or lost signal. In response, pulse-width modulation (PWM) to the inverter IGBT bridge shifts from following dynamic analog command voltages to executing the fallback behavior defined by parameter 3001 (AI), such as freezing the last known speed, switching to a preset constant speed, or stopping deceleration gracefully.

What Causes A2006 in ABB ACS150?

  1. Broken, loose, or corroded wiring connected to control terminals AI1 (terminal 2) or analog common GND (terminal 3).
  2. Misconfiguration of parameter 3021 (AI1 FAULT LIMIT) where the alarm threshold is set higher than the incoming transducer output.
  3. Failure or power loss of an external 4–20 mA process transmitter, potentiometer, or PLC analog output module.
  4. Incorrect input signal selection switch position (J1 jumper set incorrectly between 0–10 V voltage and 0–20 mA current modes).
  5. Excessive electromagnetic interference (EMI) or ground potential differences corrupting unshielded analog control cables.

Step-by-Step Troubleshooting and Solutions

  1. Measure the incoming analog command signal with a calibrated digital multimeter across control terminals AI1 and GND to confirm voltage or milliamp levels.
  2. Inspect parameter 3021 (AI1 FAULT LIMIT) and parameter 3001 (AI) to ensure trip thresholds reflect process transmitter boundaries.
  3. Verify the hardware jumper J1 setting matches the configured analog format (voltage vs. current mode) and corresponds with parameter 1104/1105 limits.
  4. Inspect terminal block connections for loose clamp screws, pinched conductors, insulation fraying, or shield grounding issues at the drive chassis.
  5. Isolate signal cables from high-voltage motor output lines (U2, V2, W2) inside conduits to eliminate coupled electrical noise inducing signal dropouts.

Preventative Maintenance to Avoid A2006 Faults

Periodic torque verification of I/O control terminal screws and verification of shielded twisted-pair signal wiring integrity prevent random signal drops. Calibrate field transmitters semi-annually and inspect 24 VDC auxiliary loop supplies to guarantee signal continuity.

Frequently Asked Questions (FAQs)

What is the meaning of A2006 fault in ABB ACS150 drive?

An A2006 alarm signifies that the primary analog speed reference at terminal AI1 has fallen below the safety floor programmed in parameter 3021.

What are the primary causes of A2006 fault?

The primary causes include severed control wiring, a dead field transmitter, an incorrectly configured J1 jumper, or an excessively high threshold setting in parameter 3021.

How do I troubleshoot and correct A2006 fault?

Troubleshoot by measuring live current or voltage at AI1 terminals, inspecting wire terminations, and aligning parameter 3021 with the transmitter operating range.