A5015 alarm in ABB ACS150 drive

Home/ABB/ABB ACS150 drive/A5015 alarm in ABB ACS150 drive

The A5015 alarm warns that switching to local keypad control has been disabled by security parameter 1606 (LOCAL LOCK). The ACS150 enforces this software lock to prevent unauthorized operators from overriding remote PLC or process supervisory commands.

In integrated industrial automation architectures, unauthorized local manual intervention can disrupt automated batch recipes, plant sequencing, or networked line speeds. Parameter 1606 (LOCAL LOCK) allows system integrators to disable the panel LOC/REM key entirely or assign its lock state to an external digital input (such as DI1–DI5). When a plant technician presses the keypad mode key while this protection is active, the drive refuses local command handover, leaves inverter PWM switching under external control, and triggers alarm A5015.

What Causes A5015 in ABB ACS150?

  1. Operator pressing the LOC/REM button while parameter 1606 is set to 1 (LOCKED).
  2. Digital input assigned in parameter 1606 (such as DI3) actively holding the local lockout state.
  3. Plant supervisory security protocol configured during commissioning to prohibit manual local drive manipulation.
  4. Accidental parameter change locking keypad access following maintenance or factory parameter restoration.
  5. Remote PLC supervisory command holding the local lockout bit active through hardwired digital logic.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter 1606 (LOCAL LOCK) and change the setting to 0 (NOT SEL) to re-enable local panel switching.
  2. If parameter 1606 is assigned to a digital input terminal (e.g., DI1–DI5), verify incoming 24 VDC voltage and switch status.
  3. Verify plant operating procedures to confirm that switching to local mode does not violate automated machine safety protocols.
  4. Review Group 16 system control parameters to audit user passcodes or unauthorized configuration changes.
  5. Once parameter 1606 is unlocked, press the LOC/REM key on the ACS150 panel to transfer control authority to local mode.

Preventative Maintenance to Avoid A5015 Faults

Maintain a secure parameter backup record using the ABB FlashDrop tool or commissioning software. Restrict access to Group 16 parameters and clearly tag equipment cabinets where remote-only lockout protocols are enforced.

Frequently Asked Questions (FAQs)

What is the meaning of A5015 fault in ABB ACS150 drive?

The A5015 alarm indicates that transferring the drive to local keypad control is blocked by parameter 1606 local lock protection.

What are the primary causes of A5015 fault?

Primary causes include setting parameter 1606 to LOCKED, an active digital input holding local lock, and unauthorized mode change attempts.

How do I troubleshoot and correct A5015 fault?

Troubleshoot by accessing parameter 1606, resetting its value to NOT SEL, and testing the LOC/REM keypad button for local handover.