The A2013 alarm indicates that an automatic fault reset routine is currently active in the ABB ACS150 drive. The drive processor is executing a programmed delay countdown before re-engaging gate modulation to restart the motor automatically.
When transient line anomalies, brief overcurrent spikes, or minor undervoltage dips occur, the drive supervisory system halts PWM switching to protect the output IGBT stage while keeping intermediate DC link circuits energized. Rather than locking out operation with a persistent hardware fault trip, the automatic reset controller pauses inverter firing according to delay parameters in group 31 AUTOMATIC RESET. Once the designated wait interval expires without hardware conflict, the drive attempts an autonomous flying or ramped start.
What Causes A2013 in ABB ACS150?
- An intermittent overcurrent condition cleared and initiated an automatic retry cycle via parameter
3104 AR OVERCURRENT. - Momentary intermediate DC link undervoltage triggered an automatic restart configured in parameter
3106 AR UNDERVOLTAGE. - Transient DC link overvoltage occurred during regenerative braking, activating parameter
3105 AR OVERVOLTAGE. - Loss of external analog control signal reference triggered an automated reset sequence under parameter
3107 AR AI. - The trial counter in parameter
3101 NUMBER OF TRIALShas begun cycling through programmed reset attempts.
Step-by-Step Troubleshooting and Solutions
- Review parameter group
31 AUTOMATIC RESET, checking parameter3101 NUMBER OF TRIALSand parameter3103 DELAY TIMEto verify automated retry thresholds. - Access the drive fault logger in parameter group
04 FAULT HISTORYto determine which underlying fault originally initiated the autoreset countdown. - Inspect incoming AC line terminals
U1, V1, W1with a digital multimeter to confirm that intermittent supply dips or loose lugs are not triggering cyclic reset alarms. - Check motor output cables on terminals
U2, V2, W2using a 500V megohmmeter to ensure intermittent insulation breakdown is not inducing repetitive trip-reset cycling. - Confirm that mechanical safety guarding and machine interlocking permit automatic restarting without creating operator hazards.
Preventative Maintenance to Avoid A2013 Faults
Periodically audit the fault log history in parameter group 04, check line voltage quality using a power logger, and torque input power terminal connections annually to prevent intermittent transient trips from triggering excessive automated restart cycles.
Frequently Asked Questions (FAQs)
What is the meaning of A2013 fault in ABB ACS150 drive?
Alarm A2013 informs the user that an automated reset sequence is active and the drive is timing down before attempting to restart the motor.
What are the primary causes of A2013 fault?
Primary causes include intermittent overcurrent events, transient line voltage fluctuations, analog signal loss, and active configuration within parameter group 31.
How do I troubleshoot and correct A2013 fault?
Inspect fault history in group 04 to identify the initiating trigger, adjust parameters in group 31, and eliminate intermittent line or load anomalies.