The F0018 fault indicates an internal hardware failure where the heatsink temperature-sensing thermistor circuit is open or short-circuited. The ABB ACS150 locks out motor modulation to prevent unmonitored thermal destruction of the power stage.
The ACS150 power module relies on an embedded negative temperature coefficient (NTC) thermistor to continuously relay junction heatsink temperatures to the main analog-to-digital converter. If this circuit opens, shorts to ground, or experiences component failure, the processor loses thermal feedback. To eliminate catastrophic fire or explosive silicon delamination risks, the drive immediately inhibits gate modulation across the IGBT bridge and locks out further operation until internal hardware integrity is restored.
What Causes F0018 in ABB ACS150?
- Internal NTC thermistor sensor on the power semiconductor heatsink has failed open or shorted.
- Broken solder trace, damaged connector, or board delamination between the power stage and control board.
- Extreme physical shock or machine vibration causing internal thermal sensor lead detachment.
- Severe electrical overvoltage surge puncturing analog sensor input circuits on the internal processor board.
- Ambient operating conditions dropping below supported cold-start operating limits (below -10 °C).
Step-by-Step Troubleshooting and Solutions
- Disconnect incoming AC line power from terminals
U1, V1, W1, wait 5 minutes for intermediate DC bus capacitors to discharge, and reapply power to check if the error was a transient processor ADC lockup. - Verify ambient air temperature around the drive enclosure to ensure it falls within operational specifications (-10 °C to +50 °C).
- Inspect the drive chassis for physical damage, heavy vibration stress, or liquid contamination that could cause internal sensor circuit shorts.
- Check parameter group
04 FAULT HISTORYto observe thermal readings immediately preceding the failure event. - Because F0018 represents an internal hardware component fault, contact an authorized ABB service center to arrange board-level repair or drive replacement.
Preventative Maintenance to Avoid F0018 Faults
Mount drives in climate-controlled enclosures with anti-vibration dampeners, install input line surge arresters to suppress transient spikes, and maintain enclosure filters to prevent internal corrosive atmospheric buildup.
Frequently Asked Questions (FAQs)
What is the meaning of F0018 fault in ABB ACS150 drive?
Fault F0018 indicates that the drive’s internal heatsink temperature measurement thermistor circuit is broken, open-circuited, or short-circuited.
What are the primary causes of F0018 fault?
The primary causes are failed internal thermistor hardware, cracked printed circuit boards from vibration, line voltage surges, or sub-zero ambient temperatures.
How do I troubleshoot and correct F0018 fault?
Power cycle the drive to rule out temporary processor errors, verify ambient temperatures, and arrange drive replacement or repair if persistent.