A6B1 alarm in ABB ACS180 drive

Home/ABB/ABB ACS180 drive/A6B1 alarm in ABB ACS180 drive

The A6B1 alarm warns that a newly created user pass code has not been confirmed in the ABB ACS180 drive memory. The drive alerts personnel to complete the two-step verification sequence before parameter lock settings can take effect.

The ACS180 firmware utilizes an active verification sequence to prevent lockout due to typographical errors in security pass codes. When an operator inputs a new security code into parameter 96.100 Change user pass code, the non-volatile memory buffer holds the new key in a pending state until parameter 96.101 Confirm user pass code receives an identical numerical match. If unconfirmed, the security subsystem generates warning A6B1, keeping parameter write restrictions uncommitted while protecting ongoing motor control processes.

What Causes A6B1 in ABB ACS180?

  1. Entering a new value in parameter 96.100 without following up in parameter 96.101.
  2. Typographical discrepancy between values entered in parameter 96.100 and parameter 96.101.
  3. Control panel timeout occurring during an ongoing security code reconfiguration session.
  4. Communication interruption between a remote commissioning tool and the drive during code updates.

Step-by-Step Troubleshooting and Solutions

  1. Open parameter 96.101 Confirm user pass code via the drive keypad or Drive Composer software.
  2. Re-enter the exact same numerical sequence that was programmed into parameter 96.100 Change user pass code.
  3. If the intended pass code sequence is forgotten, cancel the operation by closing the user lock without entering confirmation.
  4. Close the user lock by inputting an invalid dummy value into parameter 96.02 Pass code to revert security parameters.
  5. Verify that warning A6B1 clears immediately once code matching or abort routines are finalized.

Preventative Maintenance to Avoid A6B1 Faults

Maintain an encrypted master registry of machine security credentials accessible only to plant engineering managers. Always verify pass code entries using a connected PC tool during scheduled software maintenance to avoid keypad entry mismatches.

Frequently Asked Questions (FAQs)

What is the meaning of A6B1 fault in ABB ACS180 drive?

It indicates that a newly entered security pass code is pending confirmation in parameter 96.101.

What are the primary causes of A6B1 fault?

The warning is caused by setting a new code in parameter 96.100 without inputting the identical code into parameter 96.101.

How do I troubleshoot and correct A6B1 fault?

Confirm the new password by entering the matching code into parameter 96.101, or cancel the modification by closing the user lock.