The 5697 fault indicates that the charging feedback signal is missing in the ABB ACS180 drive. The drive blocks operation because it cannot confirm that the internal DC bus pre-charge circuit has successfully bypassed its charging resistor.
During initial power application, the ACS180 charges its electrolytic capacitor bank through a series current-limiting pre-charge resistor to restrain destructive inrush currents. Once the DC bus reaches approximately 80–85% of nominal potential, the control logic triggers an internal bypass relay or thyristor switch to provide an unrestricted current path. An auxiliary feedback contact confirms this transition. If this feedback signal is missing, running under load would route full motor current through the pre-charge resistor, causing immediate thermal failure.
What Causes 5697 in ABB ACS180?
- Failure, mechanical binding, or contact pitting of the internal DC bus pre-charge bypass relay.
- Severe incoming AC supply voltage sag or brownout preventing the DC link from reaching bypass threshold.
- Open-circuit failure or thermal burnout of the internal charging resistor.
- Damaged optical feedback isolator or sensing circuit trace on the power unit circuit board.
- Frequent, rapid power-cycling of incoming mains power exhausting the thermal rating of the pre-charge circuit.
Step-by-Step Troubleshooting and Solutions
- Measure incoming three-phase AC mains voltage across terminals
L1, L2, L3; confirm stable line voltage within nominal ratings. - Examine intermediate DC link voltage using diagnostic parameter
01.11 DC voltageto see if it reaches 1.35 times incoming line voltage. - Avoid short power-cycle intervals; ensure incoming line power remains off for at least 5 minutes before re-energizing the drive.
- De-energize the drive, wait until capacitors discharge, and inspect input terminal tightness and supply fuses.
- If incoming AC voltage is correct and the fault reappears upon power application, the internal bypass mechanism has failed, requiring unit service.
Preventative Maintenance to Avoid 5697 Faults
Avoid using line-side contactors for operational start/stop control, as repeated cycling stresses pre-charge resistors and relays. Program operational start/stop commands exclusively through digital inputs or fieldbus communications while keeping line power energized.
Frequently Asked Questions (FAQs)
What is the meaning of 5697 fault in ABB ACS180 drive?
It indicates that the drive did not receive confirmation that its DC link pre-charge bypass circuit closed successfully during startup.
What are the primary causes of 5697 fault?
The primary causes include defective bypass relays, low incoming line voltage, burned pre-charge resistors, or rapid input power cycling.
How do I troubleshoot and correct 5697 fault?
Verify incoming mains voltage across L1, L2, and L3, confirm normal DC bus potential in parameter 01.11, allow proper discharge intervals, and repair internal hardware if needed.