AFE1 Emergency Stop (Off2) Warning in ABB ACS180 Drive

Home/ABB/ABB ACS180 drive/AFE1 Emergency Stop (Off2) Warning in ABB ACS180 Drive

The AFE1 warning indicates that the drive has registered an emergency stop command configured for Off2 mode (coast to stop). Upon receiving this command, the drive immediately inhibits inverter gate firing, cutting power to the motor and allowing the load to coast to an unguided standstill.

Under Off2 operational logic, the ACS180 de-energizes the output phase terminals T1/U, T2/V, and T3/W instantly without executing a controlled ramp-down or activating dynamic braking resistors. This mode is typically deployed in conveyor, mixer, or fan applications where deceleration energy could exacerbate mechanical binding or overvoltage the DC bus. The drive asserts AFE1 and interlocks all restart attempts until the emergency stop circuit is physically cleared.

What Causes AFE1 in ABB ACS180?

  1. Actuation of an external field-mounted emergency stop push button or pull-rope safety switch.
  2. Interruption or opening of the discrete safety circuit wired to parameter 21.05 Emergency stop source.
  3. Tripped external safety relay or master emergency stop contactor cutting the safety input channel.
  4. Unintended fieldbus communication telegram asserting the emergency stop Off2 bit in the control word.
  5. Loose, broken, or corroded wiring connected across digital input terminals assigned to emergency stop functions.

Step-by-Step Troubleshooting and Solutions

  1. Ensure operational safety across the machine workspace, verify that personnel are clear, and determine why the E-stop was engaged.
  2. Twist and release the actuated emergency stop push button to restore the safety contact to its normally closed position.
  3. Navigate to parameter 21.05 Emergency stop source to confirm which digital input terminal (e.g., DI1 or DI2) governs E-stop signals.
  4. Measure DC voltage across the assigned digital input terminal and +24V common to ensure a continuous 24V DC permissive signal is present.
  5. Verify parameter 21.04 Emergency stop mode is properly assigned (Off2 vs. Off1/Off3) according to machine risk assessment specifications, then reset the drive.

Preventative Maintenance to Avoid AFE1 Faults

Conduct monthly functional audits of all physical emergency stop push buttons, cable pull switches, and safety relays. Ensure safety interlock circuits utilize positive-break contacts and verify screw terminal tightness during preventative maintenance turnarounds.

Frequently Asked Questions (FAQs)

What is the meaning of AFE1 fault in ABB ACS180 drive?

The AFE1 code is an operational safety warning indicating that an emergency stop command has engaged the Off2 coast-to-stop safety routine.

What are the primary causes of AFE1 fault?

The primary root causes include pressed emergency stop push buttons, open safety circuit wiring, tripped external safety relays, or fieldbus E-stop commands.

How do I troubleshoot and correct AFE1 fault?

Verify machine safety, release the pressed emergency stop button, test for 24V DC on the terminal assigned in parameter 21.05, and reset the drive.