The 64FF event log code in the ABB ACS180 drive indicates an informational confirmation that an active trip condition has been cleared. It registers when a reset command is initiated through the keypad, input/output terminals, PC software, or fieldbus network.
Unlike hardware trip events, code 64FF does not disrupt gate driver pulsing or de-energize the intermediate DC link. Instead, it signifies a transition in the drive internal state machine from a fault state to ready-to-run status. The drive controller acknowledges the command, verifies that root trip thresholds are no longer breached, clears the active latch, and updates the diagnostic history in parameter group 04 Warnings and faults.
What Causes 64FF in ABB ACS180?
- An operator manually pressed the reset push-button on the integrated control panel.
- A digital input pulse configured in parameter
31.11 Fault reset selection(such as terminalDI3) was energized. - A supervisory PLC toggled the reset bit (Bit 7 of the Control Word) via embedded Modbus RTU communication over terminals
+Band-A. - A commissioning engineer initiated a remote reset command using the ABB Drive Composer PC tool interface.
- An automated reset function triggered through parameter group
31 Fault functionssuccessfully executed after an intermittent trip.
Step-by-Step Troubleshooting and Solutions
- Inspect parameter
31.11 Fault reset selectionto determine which digital input, fieldbus bit, or panel source is assigned to execute fault resets. - Navigate to parameter
04.11 Carried faultand review parameter group04 Warnings and faultsto identify the underlying trip that triggered the reset. - Check control wiring across digital terminals (e.g.,
+24V,DCOM, andDI1–DI4) to ensure electrical transient noise is not pulsing the reset line. - Verify PLC communication logic to ensure the fieldbus control word reset pulse is momentary (pulsed high for 100 ms) and not continuously latched.
- Confirm that the motor load and output terminals
T1/U,T2/V, andT3/Ware electrically safe before allowing the machine to resume normal operation.
Preventative Maintenance to Avoid 64FF Faults
Ensure that all control signal cables use twisted-pair shielded conductors with shield drains grounded strictly at the drive chassis earth clamp. Train operators to identify and correct root trip causes in parameter group 04 prior to issuing manual resets, and verify automated reset routines in parameter group 31 are not masking persistent mechanical issues.
Frequently Asked Questions (FAQs)
What is the meaning of 64FF fault in ABB ACS180 drive?
The 64FF code is an informational event indicating that a previous drive fault has been cleared by an operator, digital input, or communication network command.
What are the primary causes of 64FF fault?
It is caused by manual keypad reset actions, digital input transitions assigned in parameter 31.11, PLC communication reset bits, or PC commissioning tool commands.
How do I troubleshoot and correct 64FF fault?
Review the event history in parameter group 04 to diagnose the original fault condition, verify reset input wiring, and ensure control signals pulse correctly.