5697 Charging Feedback Fault in ABB ACH180 Drive

Home/ABB/ABB ACH180 drive/5697 Charging Feedback Fault in ABB ACH180 Drive

Fault 5697 in the ABB ACH180 drive indicates that the pre-charging circuit feedback signal was not received or failed to verify DC bus charging completion. The drive refuses to run to protect the internal charging resistors from continuous thermal overload and prevent rectifier destruction.

Upon power-up, the intermediate DC link capacitor bank appears as a near dead short. To prevent immense inrush currents from destroying the input rectifier diodes, an internal pre-charge circuit routes current through current-limiting charging resistors or an active thyristor bridge. Once the DC bus charges to nominal operating level, an internal bypass contactor or charging relay closes to shunt the charging resistor, and an auxiliary feedback contact confirms closure to the microcontroller. If this feedback signal is absent or the DC bus fails to charge within a calibrated timeout period, fault 5697 trips.

What Causes 5697 in ABB ACH180?

  1. Defective pre-charge bypass relay or thyristor switch failing to close once DC link capacitors are energized.
  2. Open-circuit, burned, or thermally cracked pre-charge current-limiting resistor on the power unit board.
  3. Severely depressed incoming AC line voltage on terminals L1, L2, L3 preventing the DC bus from reaching pre-charge threshold.
  4. Damaged auxiliary feedback optocoupler or broken feedback sensing circuit trace on the control board.
  5. Excessive DC bus load during power-up caused by a shorted dynamic brake chopper, defective IGBT, or excessive external DC bus loading.

Step-by-Step Troubleshooting and Solutions

  1. Measure incoming AC mains voltage at input terminals L1, L2, L3 to verify that supply voltage matches nominal drive specifications.
  2. Monitor parameter 01.11 DC voltage immediately after switching on power to check if intermediate DC bus voltage rises smoothly to approximately 1.35 to 1.41 times the AC line voltage.
  3. Power down the drive, follow lockout/tagout procedures, wait for capacitors to bleed down, and measure resistance across the pre-charge resistor to verify it is not open.
  4. Check for external DC bus loads or an unintentionally grounded DC circuit connected across external braking terminals.
  5. If incoming voltage is nominal and no external shorts exist but the charging feedback contact never asserts, replace the charging board or entire drive unit.

Preventative Maintenance to Avoid 5697 Faults

Avoid rapid, repeated power-cycling of the ACH180 mains supply; ensure a minimum delay of three to five minutes between successive power-ups to allow charging resistors to cool down. Routinely verify input power quality and maintain clean enclosure filters to avoid heat trapping inside pre-charge resistor bays.

Frequently Asked Questions (FAQs)

What is the meaning of 5697 fault in ABB ACH180 drive?

The 5697 fault indicates that the drive did not detect confirmation that the intermediate DC bus pre-charging sequence completed and the bypass circuit engaged.

What are the primary causes of 5697 fault?

Main causes include low incoming AC line voltage, open pre-charge resistors, defective bypass relays, damaged feedback optocouplers, and excessive DC bus loading.

How do I troubleshoot and correct 5697 fault?

Verify the AC mains voltage, observe the DC bus ramp profile in parameter 01.11, inspect pre-charge resistor continuity, and replace the drive if the internal relay has failed.