ABB ACH180 alarm A6E6 signals an internal configuration error within parameter group 37 User load curve. The drive raises this warning when envelope coordinates violate geometric rules, temporarily disabling ULC supervision to prevent false load tripping.

The User Load Curve establishes a multi-point envelope of torque versus speed or frequency to detect broken belts or mechanical overloads. The internal algorithm requires that speed and frequency coordinates ascend monotonically ($Point_1 < Point_2 < Point_3 < Point_4 < Point_5$) and that every overload limit remains strictly above its corresponding underload limit. Inverted or equal coordinate points break table interpolation, forcing the drive to suspend curve monitoring while continuing basic motor modulation.

What Causes A6E6 in ABB ACH180?

  1. Auxiliary code 0000: Speed points in parameters 37.11... 37.15 are not strictly monotonically increasing.
  2. Auxiliary code 0001: Frequency points in parameters 37.16... 37.20 are not strictly monotonically increasing.
  3. Auxiliary code 0002: Underload torque points (parameters 37.21... 37.25) are programmed above overload torque points.
  4. Auxiliary code 0003: Overload torque points (parameters 37.31... 37.35) are programmed below underload torque points.
  5. Inadvertent manual entry of identical speed or frequency values across adjacent curve coordinates.

Step-by-Step Troubleshooting and Solutions

  1. Open the drive event log on the control panel to identify the specific auxiliary code (0000, 0001, 0002, or 0003).
  2. If aux code 0000 or 0001 appears, audit parameters 37.11... 37.15 (speed) or 37.16... 37.20 (frequency); ensure each subsequent point is strictly greater than the preceding value.
  3. If aux code 0002 or 0003 appears, compare underload parameters 37.21... 37.25 directly against overload parameters 37.31... 37.35 at each speed point.
  4. Adjust overload torque points so they maintain at least a 10% to 15% positive margin above the corresponding underload threshold.
  5. Save parameter modifications and verify that alarm code A6E6 clears from the active alarm screen immediately.

Preventative Maintenance to Avoid A6E6 Faults

Plot custom User Load Curve envelopes on paper or in a spreadsheet before entering values into the drive keypad, verify motor torque curves during commissioning, and utilize Drive Composer for graphical envelope verification.

Frequently Asked Questions (FAQs)

What is the meaning of A6E6 alarm in ABB ACH180 drive?

Alarm A6E6 indicates an invalid User Load Curve configuration where speed points do not increase sequentially or overload points fall below underload limits.

What are the primary causes of A6E6 alarm?

This alarm is caused by non-sequential speed or frequency points in group 37, or inverted overload and underload torque envelope coordinates.

How do I troubleshoot and correct A6E6 alarm?

Inspect the event auxiliary code, verify that speed points 37.11... 37.15 ascend sequentially, and ensure overload limits exceed underload limits at every point.