AFE1 Emergency stop (off2) alarm in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/AFE1 Emergency stop (off2) alarm in ABB ACH180 drive

ABB ACH180 alarm AFE1 indicates that the drive has received an active Emergency Stop Off2 (coast-to-stop) command. The inverter immediately halts pulse-width modulation, disabling output IGBT gating and allowing the driven motor to coast freely to rest.

Emergency Stop Off2 corresponds to an uncontrolled stop under IEC 60204-1 Stop Category 0. When the dedicated safety input—defined in parameter 21.05 Emergency stop source—is opened, the drive processor bypasses deceleration ramps and cuts transistor gate firing pulses instantaneously. The motor is electrically disconnected from the intermediate DC bus and coasts to rest governed solely by fluid resistance and bearing friction, with restarts locked out until the circuit is manually restored.

What Causes AFE1 in ABB ACH180?

  1. Depression of an external emergency stop push button wired to a digital input terminal.
  2. Opening of an external safety relay, HVAC fire alarm interlock, or duct smoke detector contact.
  3. Broken, disconnected, or loose wiring landed on the digital input assigned in parameter 21.05 Emergency stop source.
  4. Emergency stop command transmitted via embedded fieldbus (EFB) control word bits.
  5. Incorrect logic selection (normally open vs normally closed) assigned to the emergency stop digital input.

Step-by-Step Troubleshooting and Solutions

  1. Verify that the plant operating area is completely safe, then check and pull out any depressed emergency stop push buttons.
  2. Check parameter 21.05 Emergency stop source to confirm which digital input terminal (e.g., DI1...DI4) or fieldbus source is designated for the stop signal.
  3. Measure DC voltage across the assigned emergency stop digital input and +24V common using a multimeter; confirm 24V DC is present when the circuit is healthy.
  4. Inspect external safety interlocks, fire alarm shutdown relays, and duct smoke detectors wired in series with the e-stop loop.
  5. Once safety circuits are verified and closed, toggle the drive start/stop signal to acknowledge the interlock and resume normal operation.

Preventative Maintenance to Avoid AFE1 Faults

Perform monthly physical push-button testing on all field emergency stop stations, ensure safety circuit wiring utilizes shielded multi-conductor cables, and verify terminal screw tightness annually.

Frequently Asked Questions (FAQs)

What is the meaning of AFE1 alarm in ABB ACH180 drive?

Alarm AFE1 indicates that the drive has executed an Emergency Stop Off2 coast-to-stop command, immediately disabling inverter modulation.

What are the primary causes of AFE1 alarm?

This trip occurs due to pressed emergency stop buttons, tripped safety relays, open fire alarm interlocks, or disconnected wiring on parameter 21.05 terminals.

How do I troubleshoot and correct AFE1 alarm?

Ensure machine area safety, reset depressed push buttons, verify 24V DC on the terminal assigned in parameter 21.05, and cycle the start command.