ABB ACH180 event B687 is an informative logging event recorded whenever the drive receives a valid start command while operating in Auto mode. The drive initiates motor magnetizing and begins pulse-width modulation to accelerate the driven load.

When the drive is in Auto mode, start commands are governed by external sources mapped in parameter 20.01 Ext1 commands. Upon receiving a positive edge on a digital terminal (e.g., DI1) or a start bit in the embedded fieldbus control word, the processor verifies all safety interlocks. The drive logs event B687, charges intermediate motor flux, and begins switching output IGBTs to ramp output frequency toward setpoint per acceleration parameter 23.12 Acceleration time 1.

What Causes B687 in ABB ACH180?

  1. Closure of an external BMS contact wired to digital input terminal DI1 or DI2.
  2. Building management system issuing a Start command over BACnet MS/TP or Modbus RTU communications.
  3. Internal time-clock or scheduling macro triggering an automated motor start sequence.
  4. Process PID controller waking from sleep mode following an increase in system fluid demand.
  5. Momentary contact closure from a remote two-wire start circuit.

Step-by-Step Troubleshooting and Solutions

  1. Observe the motor and driven fan or pump to confirm smooth acceleration toward the commanded operating speed.
  2. If the start was unexpected, check parameter 20.01 Ext1 commands to identify the physical or communication source assigned to start logic.
  3. Measure voltage at the digital input terminal mapped to the start signal; confirm whether 24V DC is being applied intentionally.
  4. Inspect building automation scheduling calendars to verify whether scheduled occupancy commands triggered the start.
  5. Check parameter group 40 Process PID set 1 to verify if wake-up deviation parameters commanded an automated restart.

Preventative Maintenance to Avoid B687 Faults

Audit building automation schedules periodically, check external relay contacts for contact bounce, and review event log timestamps to verify that automated equipment starts align with planned operational hours.

Frequently Asked Questions (FAQs)

What is the meaning of B687 alarm in ABB ACH180 drive?

Event B687 is an informational status record documenting that the drive received a valid start command while operating under Auto mode control.

What are the primary causes of B687 alarm?

This event is triggered by remote BMS run commands, digital input closures on terminal DI1, time-clock schedules, or Process PID wake-up functions.

How do I troubleshoot and correct B687 alarm?

No corrective action is required for normal operation; if uncommanded starts occur, review start sources in parameter 20.01 and check BMS schedules.