The A2015 alarm indicates that one or more PFC interlock circuits are open, inhibiting the drive from starting the selected speed-regulated or auxiliary motor. The ABB ACS310 raises this warning to protect machinery and personnel when safety or thermal interlocks prevent normal equipment staging.
When the PFC macro operates with interlocks enabled via parameter 8120 INTERLOCKS, each pump or motor in the system requires an active digital feedback signal (e.g., thermal overload, isolation disconnect switch, or flow sensor switch) before the drive can release inverter modulation. If the assigned digital input (such as DI2, DI3, or DI4) drops to 0V DC, the internal state machine locks out the associated motor and posts A2015 while attempting to transfer control to an available alternate motor.
What Causes A2015 in ABB ACS310?
- Tripped external motor protection switch or thermal overload relay on an auxiliary pump motor.
- Open position on an auxiliary motor disconnect switch or service isolator.
- Incorrect interlock assignment configured in parameter
8120 INTERLOCKS. - Broken, disconnected, or corroded wiring on the assigned digital input terminals (
DI1–DI5). - Defective
24V DCcontrol power supply or blown safety circuit auxiliary fuse.
Step-by-Step Troubleshooting and Solutions
- Identify which digital input corresponds to the open interlock by evaluating parameter
8120 INTERLOCKSand cross-referencing your wiring drawing. - Measure the DC voltage between the assigned digital input terminal (e.g.,
DI3) and common terminalGNDusing a multimeter; confirm presence of24V DC. - Inspect external motor circuit breakers, flow switches, and thermal overloads to verify that all physical safety switches are closed.
- Examine terminal strip screws on the control board and field junction boxes for loose wire connections or broken conductors.
- If interlocks are not physically wired in the installation, modify parameter
8120 INTERLOCKSto0 (OFF)to clear the warning.
Preventative Maintenance to Avoid A2015 Faults
Periodically test all auxiliary motor interlock switches, verify tightness of terminal strip fasteners, and conduct routine checks on external disconnect auxiliary contacts to ensure uninterrupted signal transmission to the drive.
Frequently Asked Questions (FAQs)
What is the meaning of A2015 alarm in ABB ACS310 drive?
This warning indicates that an external PFC interlock switch is open, preventing the drive from starting either a specific motor or any motor in the staging system.
What are the primary causes of A2015 alarm?
The primary causes are tripped external motor overloads, open isolator switches, broken digital input wiring, and incorrect interlock parameter settings in group 81.
How do I troubleshoot and correct A2015 alarm?
Locate the assigned interlock digital inputs, verify 24V DC continuity across external switches, reset any tripped breakers, and adjust parameter 8120 if interlocks are absent.