A2021 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2021 alarm in ABB ACS310 drive

The A2021 alarm notifies the operator that the ABB ACS310 drive has received a run command while the Start Enable 1 interlock circuit remains open. The drive controller prevents inverter modulation until this permissive input signal is safely asserted.

While this permissive signal is absent, gating pulses to the six IGBT switches are inhibited, preventing magnetic flux generation in the motor stator. The DC link capacitors remain fully energized through the three-phase input bridge rectifier, but output terminals U2, V2, W2 remain in a high-impedance state. This safety and process interlocking scheme protects upstream machinery from unexpected movement when safety gates, limit switches, or run permissives are de-energized.

What Causes A2021 in ABB ACS310?

  1. Parameter 1608 START ENABLE 1 assigned to a digital input that is not receiving a +24V DC signal.
  2. Open safety interlock contacts, blown external auxiliary fuses, or broken wiring to terminals DI1 through DI5.
  3. Fieldbus communication timeout or misconfigured cyclic control word bit when parameter 1608 is set to COMM.
  4. Failure of internal auxiliary voltage supply terminal +24V feeding the control circuit loop.

Step-by-Step Troubleshooting and Solutions

  1. Examine the setting in parameter 1608 START ENABLE 1 to identify whether an active digital input (such as DI1 through DI5) or a fieldbus control word is selected.
  2. Measure DC voltage between the assigned digital input terminal (e.g., DI1) and common terminal GND using a multimeter; verify a steady +24V DC signal is present.
  3. Check external interlock devices including emergency pull-cords, guard switches, and relay contacts for open circuit states or contact chatter.
  4. Inspect fieldbus communication cables, termination switches, and parameter 5319 EFB PAR 19 if start permissives are controlled over Modbus RTU.

Preventative Maintenance to Avoid A2021 Faults

Inspect terminal block screw tensions periodically, verify proper strain relief on digital control wiring cables, and keep safety interlock push buttons and microswitches free from moisture, industrial oils, and dust ingress.

Frequently Asked Questions (FAQs)

What is the meaning of A2021 alarm in ABB ACS310 drive?

Alarm A2021 indicates that the drive received a start request but cannot run because the configured Start Enable 1 interlock signal is missing.

What are the primary causes of A2021 alarm?

The condition occurs due to an open digital input contact, broken control wiring, an unasserted fieldbus control bit, or an incorrect assignment in parameter 1608.

How do I troubleshoot and correct A2021 alarm?

Check parameter 1608 configuration, verify 24V DC at the designated digital input terminal with a meter, and inspect external interlock switches.