The A5011 alarm informs the user that manual keypad commands are locked because the drive is currently configured for external control. The ABB ACS310 displays this alarm whenever an operator presses the Start, Stop, or Direction key while the drive is controlled by field inputs.
In standard industrial installations, the ACS310 prioritizes control locations between Local (keypad) and Remote (I/O terminals or embedded Modbus). When operating in Remote mode (indicated by REM on the panel display), control words originate from terminal inputs like DI1 or parameter 1001 EXT1 COMMANDS. Attempting to override the drive directly from the keypad triggers A5011 to prevent conflicting control commands from disrupting automated process sequencing.
What Causes A5011 in ABB ACS310?
- Pressing Start, Stop, or Reference arrows on the keypad while the drive is operating in
REM(Remote) mode. - Active external start command applied to digital inputs (e.g.,
DI1orDI2) governed by parameter1001 EXT1 COMMANDS. - Drive controlled remotely over the embedded fieldbus interface via RS-485 Modbus RTU.
- Local control disabled or restricted by parameter
1606 LOCAL LOCK. - External control source switching controlled by parameter
1102 EXT1/EXT2 SELmaintaining continuous remote operation.
Step-by-Step Troubleshooting and Solutions
- Press the
LOC/REMbutton on the control panel to transition the drive operating state fromREMtoLOCmode. - Check parameter
1606 LOCAL LOCK; if set to1 (LOCKED), switch it to0 (NOT SEL)to permit local keypad authorization. - Verify control source assignments in parameter
1001 EXT1 COMMANDSand parameter1002 EXT2 COMMANDSto confirm intended operational logic. - Measure voltages at digital inputs
DI1throughDI5against common groundGNDto see if a remote PLC command is active. - If operating over automation networks, verify parameter group
53 EFB PROTOCOLto ensure fieldbus start logic matches supervisory PLC programming.
Preventative Maintenance to Avoid A5011 Faults
Provide clear operator labeling on control panels regarding Local/Remote operational policies, and audit parameter 1606 settings during commissioning to prevent unauthorized mode conflicts.
Frequently Asked Questions (FAQs)
What is the meaning of A5011 alarm in ABB ACS310 drive?
This is an informational warning indicating that panel control commands were rejected because the drive is actively assigned to an external control source.
What are the primary causes of A5011 alarm?
The alarm is triggered by pressing keypad control buttons while in Remote mode, having local control locked via parameter 1606, or receiving PLC network commands.
How do I troubleshoot and correct A5011 alarm?
Press the LOC/REM keypad key to switch into local mode, unlock parameter 1606 if disabled, or execute control commands via the configured remote I/O.