A5013 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A5013 alarm in ABB ACS310 drive

The A5013 alarm indicates that control panel starting is disabled because an active start inhibit interlock or emergency stop command is present. The ABB ACS310 displays this alarm to prevent unauthorized local motor operation when external safety conditions require the inverter to stay off.

Whenever an emergency stop or 3-wire stop circuit is activated via external control logic, the drive enters an inhibited state. If an operator switches to Local mode and presses the Start button on the keypad, the ACS310 checks safety registers configured under parameter 2109 EMERG STOP SEL and parameter 2108 START INHIBIT. Because an active stop command holds the run permissives low, the inverter suppresses PWM gate pulses to the IGBT stage, preventing accidental shaft rotation.

What Causes A5013 in ABB ACS310?

  1. Active emergency stop button or open safety loop wired to digital inputs mapped in parameter 2109 EMERG STOP SEL.
  2. Maintaining an open circuit on a 3-wire stop push button wired according to parameter 1001 EXT1 COMMANDS.
  3. Active start inhibit function enabled via parameter 2108 START INHIBIT while mains power is recycled with start commands present.
  4. Loose, broken, or miswired field wires on digital input terminals (such as DI1 through DI5).
  5. Loss of internal or external 24V DC control circuit power feeding the run permissive loop.

Step-by-Step Troubleshooting and Solutions

  1. Inspect all hardwired emergency stop push buttons, safety pull cords, and safety relay outputs to ensure they are manually reset.
  2. Check parameter 2109 EMERG STOP SEL to determine which digital input (e.g., DI1 or DI4) is configured for emergency stopping.
  3. Measure the DC voltage between the emergency stop digital input and terminal GND; confirm steady 24V DC is present.
  4. If 3-wire control is utilized in parameter 1001 EXT1 COMMANDS, verify that the normally closed stop circuit contact is fully closed.
  5. Inspect parameter 2108 START INHIBIT; if dynamic start inhibit is unnecessary for your safety design, adjust it to 0 (OFF).

Preventative Maintenance to Avoid A5013 Faults

Conduct monthly functional audits of all emergency stop buttons and safety contact blocks, torque field terminal screw blocks annually, and replace oxidised push button contacts that cause intermittent open-circuit trips.

Frequently Asked Questions (FAQs)

What is the meaning of A5013 alarm in ABB ACS310 drive?

This alarm indicates that starting from the control panel is locked out because an external emergency stop or start inhibit command is actively engaged.

What are the primary causes of A5013 alarm?

Primary causes include an engaged emergency stop button, an open 3-wire stop circuit, parameter 2108 start inhibit activation, and missing 24V DC permissives.

How do I troubleshoot and correct A5013 alarm?

Reset all physical emergency stop buttons, verify 24V DC voltage on assigned digital inputs, and inspect parameters 1001, 1002, and 2109.