The A5014 alarm indicates that local panel control is disabled on the ABB ACS310 drive because an unacknowledged drive fault is currently active. The control processor blocks local keypad commands to protect the power electronic stages from unsafe re-energization.
During an active drive trip, the main microcontroller disables all pulse-width modulation (PWM) firing signals across the six inverter IGBTs. Even though the intermediate DC bus remains charged to approximately 540V DC from the three-phase AC mains, motor terminals U2, V2, W2 remain electrically disconnected. Pressing the LOC/REM or START buttons on the Basic or Assistant Control Panel will not engage modulation until the underlying fault condition is identified, rectified, and acknowledged in the control registers.
What Causes A5014 in ABB ACS310?
- An active latched drive fault such as overcurrent (
F0001), DC overvoltage (F0002), or motor overtemperature (F0009). - Attempting to switch to local keypad control mode while an auxiliary trip circuit or safety interlock remains open.
- Defective or unseated panel communication interface causing intermittent data handshake errors.
- Unacknowledged motor stall condition or earth fault condition detected during previous run operation.
Step-by-Step Troubleshooting and Solutions
- Inspect the control panel display or access parameter
0401 LAST FAULTto determine the primary trip code disabling keypad operation. - Rectify the root cause of the primary fault, then press the red
RESETkey on the panel or pulse digital inputDI1throughDI5configured in parameter1604 FAULT RESET SEL. - Check wiring connections on digital control terminals
+24V,DCOM, and interlock terminals to verify supply voltage measures a stable24V DC. - Test motor insulation integrity across terminals
U2, V2, W2to ground with a500V DCmegger tester, verifying resistance exceeds1 MΩbefore resetting.
Preventative Maintenance to Avoid A5014 Faults
Periodically download the drive fault log from parameter group 04 FAULT HISTORY, maintain clean panel contact pins, and rectify recurring transient alarms before they escalate into persistent trip states.
Frequently Asked Questions (FAQs)
What is the meaning of A5014 alarm in ABB ACS310 drive?
Alarm A5014 indicates that the drive panel cannot switch into local control because a primary fault has tripped the drive.
What are the primary causes of A5014 alarm?
The alarm occurs when an unresolved power stage fault is latched in memory or an emergency interlock prevents local manual start commands.
How do I troubleshoot and correct A5014 alarm?
Read the primary fault code in parameter 0401, correct the electrical or mechanical issue, and press the keypad reset button.