The A5015 alarm indicates that local keypad control is prohibited because the local control mode lock function has been intentionally enabled. The drive firmware ignores the LOC/REM keypad button to prevent unauthorized manual parameter manipulation or speed changes.
When this security interlock is engaged, the inverter continues operating strictly under remote supervisory automation, such as external digital inputs or embedded Modbus commands. PWM gate firing for the output IGBT transistors is controlled solely by remote reference channels, while the intermediate DC bus remains stable at approximately 540V DC. Local start, stop, and reference alterations from the control panel membrane keys are rejected by software to prevent conflict with automated supervisory plant PLC sequencing.
What Causes A5015 in ABB ACS310?
- Parameter
1606 LOCAL LOCKset toTRUE, permanently disabling local control keypad access. - Parameter
1606mapped to a digital input terminal (such asDI1throughDI5) that is held at a high+24V DClevel. - Supervisory PLC or SCADA system setting a local lockout control bit over the RS-485 Modbus fieldbus link.
- Operator pressing the
LOC/REMkey on the keypad while commissioning lockout security rules are in effect.
Step-by-Step Troubleshooting and Solutions
- Navigate to parameter group
16 SYSTEM CONTROLSand check the current value configured in parameter1606 LOCAL LOCK. - If parameter
1606is assigned to a digital input, measure DC voltage across that terminal (e.g.,DI3) and commonGNDusing a multimeter to confirm input voltage state. - Deactivate the local lock by changing parameter
1606 LOCAL LOCKtoNOT SELusing an authorized engineering profile or communication master. - Verify external fieldbus register mappings if an external PLC supervisory program is transmitting cyclic control words restricting manual override.
Preventative Maintenance to Avoid A5015 Faults
Document security settings within engineering parameter backups, clearly label locked local control stations, and train site operators on whether field equipment is configured for remote-only automation.
Frequently Asked Questions (FAQs)
What is the meaning of A5015 alarm in ABB ACS310 drive?
Alarm A5015 signifies that manual panel operation is disabled because parameter 1606 is locking the drive into remote control.
What are the primary causes of A5015 alarm?
This warning is triggered when an operator presses the local button while parameter 1606 or a digital input has locked keypad commands.
How do I troubleshoot and correct A5015 alarm?
Check parameter 1606 in group 16, verify digital input voltage on the assigned terminal, and disable the local lock function.