A2006 AI1 LOSS alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2006 AI1 LOSS alarm in ABB ACS310 drive

The A2006 AI1 LOSS alarm in the ABB ACS310 drive indicates that the analog input 1 signal has fallen below the safety limit specified in parameter 3021 AI1 FAULT LIMIT. This function protects systems against erratic modulation caused by severed process sensor wiring.

When the control board detects an analog signal drop below the programmed threshold on terminal 2 (AI1), internal logic prevents erratic speed commands from destabilizing system operation. Depending on parameter 3001 AI, the drive either runs at a fixed safe frequency via parameter 1208 CONST SPEED 7 or maintains the average speed of the previous 10 seconds, stabilizing DC link voltage while alerting operators.

What Causes A2006 in ABB ACS310?

  1. Broken, disconnected, or corroded signal wiring connected to analog input terminal 2 (AI1) or common terminal 3 (AGND).
  2. Failure or loss of external 24 VDC auxiliary loop power supplying the field transmitter.
  3. Hardware jumper J1 set incorrectly for voltage (0–10V) instead of current (0/4–20mA) operation.
  4. Incorrect threshold scaling configured in parameter 3021 AI1 FAULT LIMIT or parameter 1301 MINIMUM AI1.
  5. Transducer hardware failure resulting in zero milliamp current output during normal process operation.

Step-by-Step Troubleshooting and Solutions

  1. Measure loop current at terminal 2 (AI1) using an in-line digital multimeter to verify whether the incoming signal is below 4.0 mA.
  2. Verify the position of hardware selection jumper J1 behind the control panel to confirm whether it matches the sensor output type (current or voltage).
  3. Check parameter 3021 AI1 FAULT LIMIT (typically set to 20.0% for a 4–20 mA loop) and parameter 3001 AI settings.
  4. Inspect auxiliary power supply terminal 9 (+24V) and verify steady DC output voltage to external transmitters.
  5. Perform a loop calibration check using an external 4–20 mA signal generator to confirm analog channel responsiveness.

Preventative Maintenance to Avoid A2006 Faults

Ensure that all analog instrumentation wiring employs twisted-pair shielded cables with the shield grounded exclusively at drive terminal 1 (SCR). Routinely inspect analog terminals on the X1A terminal block for tightness, and verify transducer calibration annually to prevent signal drift.

Frequently Asked Questions (FAQs)

What is the meaning of A2006 AI1 LOSS fault in ABB ACS310 drive?

It means the analog input signal connected to channel AI1 has dropped below the minimum operational limit defined in the drive supervisory parameters.

What are the primary causes of A2006 fault?

The primary causes are a broken 4 to 20 milliamp loop wire, a failed process transmitter, an incorrect J1 jumper position, or an improperly scaled fault threshold.

How do I troubleshoot and correct A2006 fault?

Measure the input loop current with a multimeter, inspect wiring on terminal 2, verify jumper J1 orientation, and calibrate parameter 3021 to match the transmitter range.