A2026 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2026 alarm in ABB ACS310 drive

The A2026 alarm on the ABB ACS310 indicates that intermediate circuit DC voltage ripple has exceeded 14% of nominal DC voltage due to a missing input phase or blown fuse. The drive continues to run while signaling this supervisory warning to prevent internal electrolytic capacitor damage.

When an incoming three-phase AC line is lost, the input rectifier bridge degenerates into single-phase rectification. This causes the intermediate DC circuit ripple frequency to collapse from a balanced six-pulse wave down to a severe two-pulse oscillation. The intermediate DC capacitors endure excessive ripple current, heating the internal electrolyte and causing voltage instability across the inverter IGBT stage. If left uncorrected under heavy load, the condition will trigger a hard F0022 supply phase fault trip.

What Causes A2026 in ABB ACS310?

  1. A blown line fuse or tripped branch circuit protector on the incoming AC supply line.
  2. Severe AC mains phase-to-phase voltage imbalance exceeding 3% caused by grid disturbances.
  3. Loose, corroded, or incorrectly torqued electrical connections at input terminals L1, L2, L3.
  4. Pitted, worn, or oxidized contacts within an upstream magnetic contactor or manual isolator switch.
  5. Supervision sensitivity configuration or monitoring settings within parameter 3016 SUPPLY PHASE.

Step-by-Step Troubleshooting and Solutions

  1. Isolate power and check continuity across all upstream input power fuses using a digital multimeter.
  2. Measure three-phase AC line voltages across terminals L1, L2, L3 under load to verify voltage balance within 3%.
  3. Inspect and re-torque all incoming electrical wiring terminals on the drive and upstream switchgear to rated torque specifications.
  4. Review parameter 3016 SUPPLY PHASE to ensure the phase loss supervision response is properly configured for your plant power network.
  5. Monitor parameter 0107 DC BUS VOLTAGE on the display panel to observe intermediate DC bus ripple stability during operation.

Preventative Maintenance to Avoid A2026 Faults

Perform scheduled thermal imaging audits on incoming power terminals and upstream line fuses to catch loose connections early, check line balance during routine electrical maintenance, and verify that all enclosure terminals maintain proper torque specifications.

Frequently Asked Questions (FAQs)

What is the meaning of A2026 fault in ABB ACS310 drive?

The A2026 code indicates that the drive’s intermediate DC bus voltage ripple has exceeded 14%, signaling that an incoming three-phase supply line is degraded or lost.

What are the primary causes of A2026 fault?

This warning is primarily caused by blown upstream line fuses, severe AC utility phase unbalance, or loose electrical terminations on the input supply lines.

How do I troubleshoot and correct A2026 fault?

Test input line fuses for continuity, measure phase-to-phase voltages at terminals L1, L2, and L3, and verify the settings in parameter 3016.